Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Owing to the respective characteristics of LV and MV conductors, they have been dealt with in
separate paragraphs.
(Insulated) cable
Assembly comprising:
- one or more insulated conductors
- their eventual individual screening
- any eventual assembly protection
- any eventual protective shielding
It may also comprise one or several bare conductors.
Multi-core cable
Cable comprising more than one conductor, which may eventually include bare conductors.
Note: the term three-core cable is used to designate the cable making up the phases of a three-phase
system.
Single-core cable
Cable comprising a single insulated conductor.
Note: the term single-core cable is especially used to designate a cable making up one of the phases of a
three-phase system.
Wiring system
Assembly made up of one or more electric conductors and the devices ensuring their fixation and, if
necessary, their mechanical protection.
Cable channel
Ventilated or enclosed duct located above or in the ground, having dimensions preventing persons from
moving around inside it but allowing access to the cables over their entire length during and after
installation.
Note: a cable channel may or may not form part of the building construction.
Cable tray
Holder made up of a base and sides but no cover.
Note: A cable tray may be perforated or unperforated.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
(Insulated) conductor
Assembly comprising the conductor, its insulating envelope and eventual screens.
(Circular) conduit
Enclosed envelope, having a circular cross-section, designed for the installation or the replacement of
insulated conductors or cables by capstan, in electrical installations.
Ducting
Assembly of closed envelopes having a non circular cross-sectional area, designed for the installation or
the replacement of insulated conductors or cables by capstan, in electrical installations.
Brackets
Horizontal cable supports fixed at one of their ends, arranged from point to point and on which the cables
rest.
Cable ladder
Cable support made up of a series of non-touching elements firmly fixed to main vertical rods.
Sheath
Enclosure located above ground level having dimensions preventing persons from moving around inside
it but allowing access to the cables over their entire length. A sheath may or may not be built into the
masonry.
Trough
Assembly of envelopes closed by a cover and ensuring mechanical protection of insulated conductors or
cables not installed or removed by a capstan and which allow other electrical equipment to be added .
Building void
Space in a structure or building parts which is only accessible at certain places.
Note: - spaces in walls, supported floors, ceilings and certain types of window or door frames and
jamb linings are examples of building voids.
- specially built building voids are also called "ducts".
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
- carry the maximum design current and its normal transient peaks
- protect the wiring system against any overcurrents up to the short-circuit current
The logigram in figure 6-1 sums up the principle of the method which may be described by the
following stages:
1st stage:
- using the load power, the maximum design current I B is calculated and the rated current
I n of the protective device is deduced from this
- the maximum short-circuit current Isc at the origin of the circuit is calculated and the
breaking capacity of the protective device is deduced from this.
2nd stage:
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
3rd stage:
- the thermal withstand of the conductors in the event of a short circuit is checked
- for TN and IT systems, the maximum length relating to the protection of persons against
indirect contact is checked.
The conductor cross-sectional area meeting all these conditions is then chosen.
Note: an economic cross-sectional area larger than the cross-sectional area determined above may
be chosen if necessary (see § 6.3).
maximum wiring
system length chek
TT earthing
system
economic
cross-sectional
area possibly chosen
Figure 6-1: wiring system cross-sectional area and protective device choice logigram
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In the case of individual power supply to a device, the current I B will be equal to the rated
current of the device being fed. On the other hand, if the wiring system feeds several devices,
the current I B will be equal to the sum of currents absorbed, taking into account the
installation utilisation and coincidence factors.
In the case of motor starting or cyclical operating conditions of loads (spot welding station,
see § 3.4.2), current inrushes must be taken into account when their thermal effects are
cumulated.
Some installations are subject to future extensions. The current corresponding to this
extension will be added to the existing value.
S S
In alternating current: I = in single-phase and I = in three-phase.
U U 3
S : apparent power consumed (VA)
U : . voltage between the two conductors for a single-phase power supply
. phase-to-phase voltage for a three-phase power supply
When high harmonic currents circulate in the conductor, they must be taken into account. In
order to choose the cross-sectional area, the following must therefore be taken:
1
∞
I r .m.s. =
∑ I p2
(see § 8)
p =1
- assuming that compensation is in operation: in case of failure of the capacitors, the wiring
system is placed out of service
- assuming that compensation is out of service; in case of failure of the capacitors, the
conductor cross-sectional area is sufficient and availability is thus improved.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
P
S= in kVA
η × Fp
P : active power in kW
η : efficiency
Fp : power factor
1
We define the coefficient: a =
η × Fp
In an industrial installation, it is assumed that loads will never be used at their full power level.
A utilisation factor ( b ) is therefore introduced which generally varies from 0.3 to 1.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n coincidence factor: c
In an industrial installation, the loads (of a workshop, for example) fed by the same wiring
system do not operate simultaneously in all cases. To take this phenomenon, which is linked to
the operating conditions of the installation, into account, the coincidence factor is applied to
the sum of the load powers in conductor sizing.
In the absence of precise indications resulting from experience of standard installations, the
values of tables 6-1 et 6-2 may be applied:
Lighting 1
2 and 3 0.9
4 and 5 0.8
5 to 9 0.7
The value of factor d must be estimated according to the foreseeable extensions of the
installation.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
IB = P × a × b × c × d × e
P : active power in kW
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n general rule
In compliance with IEC 364, a protective device (circuit-breaker or fuse) correctly fulfils its
function if the conditions outlined below are met.
This must be between the design current and the current carrying capacity I a of the wiring
system:
case of circuit-breakers
I2 = 1.45 In
I2 = 1.30 I set
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
case of fuses
Standard IEC 269-1 specifies that I 2 is the current which ensures that the fuse fuses in the
conventional time (1 h or 2 h); I 2 is referred to as the conventional fusing current (see § 6.3.1
of the Protection guide).
k2
k3 =
1.45
I
In ≤ a
k3
For gG fuses:
- I n ≤ 10 A à k3 = 1.31
- 10 A < I n ≤ 25 A à k3 = 1.21
- I n > 25 A à k3 = 1.10
o breaking capacity
This must be higher than the three-phase maximum short-circuit current ( Isc 3 ) at its
installation point:
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The use of a protective device having a breaking capacity below the short-circuit current at the
point where it is installed is permitted by standard IEC 364 under the following conditions:
- there is another device upstream having at least the necessary breaking capacity
- the energy that the device placed upstream lets through is lower than the energy that the
downstream device and wiring systems protected by these devices can withstand without
being damaged.
. in circuit-breaker/fuse associations
. in the cascading technique which uses the high current limitation capacity of certain
circuit-breakers (e.g. the Compact).
The possible associations resulting from actual tests performed in a laboratory are given in
manufacturer catalogues.
- using tables 6-3 to 6-5, define the installation method, its associated selection number and
letter, and correction factors to be applied
- using the installation conditions, the correction factor values which must be applied are
determined (see tables 6-6 to 6-15)
- calculate the overall correction factor f equal to the product of the correction factors
- using table 6-16 for selection letters B, C, E, F and table 6-17 for selection letter D, the
maximum current I 0 that the wiring system can carry under standard conditions
( f0 to f10 = 1 ) is determined
- calculate the maximum current that the wiring system can carry in relation to its installation
conditions: I a = f I 0 .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n installation methods
Tables 6-3 to 6-5 give the main installation methods used in industrial networks.
Factor f 0 corresponds to the installation method; factors f1 to f10 are explained below
(see tables 6-6 to 6-15).
- fixed on a wall 11 C 1 f1 f4 f5
- on unperforated trays 12 C 1 f1 f4 f5
cables
multi-core single-
core
- on brackets 14 E F 1 f1 f4 f5
- on ladders 16 E F 1 f1 f4 f5
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Single or multi-core
conductors :
- in false ceilings
25 B 0.95 f1 f4 f5 --
- in suspended ceilings
- run horizontally
31A B 0.9 f1 f4 f5 --
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n correction factors for ambient temperatures other than 30 °C (wiring systems above
ground): f1
When electrical wiring systems are built into walls having heating elements, it is generally
necessary to reduce current-carrying capacities by applying the reduction factors in table 6-6.
This supposes that the distribution of temperatures inside the heated walls in contact with the
electrical wiring system is known.
When the air temperature is other than 30 °C, the correction coefficient to be applied is given
in the formula:
θ p −θ0
f1 =
θ p − 30o
Insulation
Ambient Elastomers PVC XLPE and EPR
temperatures (°C) (rubber)
θ0 θ p = 60 °C θ p = 70 °C θ p = 90 °C
10 1.29 1.22 1.15
15 1.22 1.17 1.12
20 1.15 1.12 1.08
25 1.07 1.06 1.04
35 0.93 0.94 0.96
40 0.82 0.87 0.91
45 0.71 0.79 0.87
50 0.58 0.71 0.82
55 - 0.61 0.76
60 - 0.50 0.71
65 - - 0.65
70 - - 0.58
75 - - 0.50
80 - - 0.41
85 - - -
90 - - -
95 - - -
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
When the ground temperature is other than 20°C, the correction coefficient to be applied is
given in the formula:
θ p −θ0
f2 =
θ p − 20
10 1.10 1.07
15 1.05 1.04
25 0.95 0.96
30 0.89 0.93
35 0.84 0.89
40 0.77 0.85
45 0.71 0.80
50 0.63 0.76
55 0.55 0.71
60 0.45 0.65
65 - 0.60
70 - 0.53
75 - 0.46
80 - 0.38
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n correction factors for buried wiring systems, in relation to the soil thermal
resistivity: f 3
The soil thermal resistivity depends on the type and humidity of the ground. The correction
factor to be applied according to the soil resistivity is given in table 6-8.
- both touching and arranged in several layers (see fig. 6-3); correction factors f 4 and f5
must then be applied.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The factors in table 6-9 are to be applied to homogenous groups of cables, equally loaded, for
the given installation methods.
When the horizontal distance between neighbouring cables is greater than twice their external
diameter, no reduction factor is necessary.
- to multi-core cables.
1 2 3 4 5 6 7 8 9 12 16 20
11, 12 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 No extra
11A 1.00 0.85 0.76 0.72 0.69 0.67 0.66 0.65 0.64 reduction
13 1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72 factor for
14, 16 1.00 0.88 0.82 0.80 0.80 0.79 0.79 0.78 0.78 more than 9 cables
When cables are arranged in several layers, the correction factors in table 6-10 must be
applied.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n correction factors in relation to the number of conduits in air and their arrangement
(see table 6-11): f 6
Table 6-11: correction factors in relation to the number of conduits in the air and their arrangement
n correction factors in relation to the number of conduits buried or built into concrete
and their arrangement (see table 6-12): f 7
Table 6-12: correction factors in relation to the number of conduits buried or built into concrete and their
arrangement
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Table 6-13: correction factors for non-touching buried conduits run horizontally or vertically on the basis
of one cable or group of 3 single-core cables per conduit
a
multi-core cables
a
single-core cables
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n correction factors in the case of several circuits or cables in the same buried conduit
(see table 6-14): f 9
This is applicable to groups of cables with varying cross-sectional areas but having the same
allowable maximum temperature.
1 2 3 4 5 6 7 8 9 12 16 20
Installed in a buried
1 0.71 0.58 0.5 0.45 0.41 0.38 0.35 0.33 0.29 0.25 0.22
conduit
n correction factors for a group of several cables installed directly in the ground - single
or multi-core cables arranged horizontally or vertically (see table 6-15): f10
Table 6-15: correction factors for a group of several cables installed directly in the ground -
single or multi-core cables arranged horizontally or vertically
a a
multi-core cables single-core cables
The current carrying capacities given in table 6-16 are valid for simple circuits made up of the
following number of conductors:
Selection letter B:
Selection letter C:
E E F F
The number of conductors to be considered in a circuit is that of the conductors through which
the current actually flows. When, in a three-phase circuit, the currents are assumed to be
balanced, it is not necessary to take into account the corresponding neutral conductor.
When the current value of the neutral conductor is close to that of the phases, a reduction
factor of 0.84 is to be applied. Such currents may, for example, be due to the presence of third
harmonic currents in the phase conductors (see § 6.2).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Table 6-16: current carrying capacities (in amps) of wiring systems in standard installation conditions
( f0 to f10 = 1) for selection letters B, C, E, F
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The number of conductors to be considered in a circuit is that of the conductors through which
the current actually flows. When, in a three-phase circuit, the currents are assumed to be
balanced, it is not necessary to take into account the corresponding neutral conductor.
When the current value of the neutral conductor is close to that of the phases, a reduction
factor of 0.84 is to be applied. Such currents may, for example, be due to the presence of third
harmonic currents in the phase conductors (see § 6.2).
Table 6-17: current carrying capacities (in amps) of wiring systems in standard installation conditions
( f0 to f10 = 1) for selection letter D (buried wiring systems)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
I z1 I z2
Figure 6-7: logigram for determining the cross-sectional area of a LV wiring system
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The equipotential bonding conductors allow the exposed conductive parts and extraneous
conductive parts to be set at the same potential, or similar potentials.
In this chapter, we will limit ourselves to conductor sizing rules. Refer to paragraph 2 for the
protection and connection rules.
main LV switchboard
PE
Table 6-18 gives the protective conductor cross-sectional areas (in mm²) in relation:
- to the operating time t (in seconds) of the MV protection. When protection is ensured by a
fuse, the cross-sectional area to be taken into account corresponds to t = 0.2 s
In an IT earthing system, if an overvoltage limiter is inserted between the neutral and earth,
the same sizing is applied to its connecting conductors.
In the case where several transformers operate in parallel, the sum of their nominal powers will
be used to determine the cross-sectional area.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
≤ 63 ≤ 100 25 25 25 25 25 25 25 25 25
100 160 25 25 35 25 25 50 25 25 35
125 200 25 35 50 25 35 50 25 25 50
160 250 25 35 70 35 50 70 25 35 50
200 315 Potective conductor 35 50 70 35 50 95 35 50 70
n cross-sectional areas of low voltage exposed conductive part protective conductors: (PE)
The cross-sectional area of the PE conductor is defined in relation to the cross-sectional area
of the phases (for the same metal conductor) as follows:
S phase
- for S phase > 35 mm² , S PE =
2
(1) when the protective conductor is not part of the wiring system, it must have a cross-sectional area of
at least:
- 2.5 mm² if it comprises a mechanical protection
- 4 mm² if it does not comprise a mechanical protection
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In the TT earthing system, the protective conductor cross-sectional area may be limited to:
on condition that the neutral and exposed conductive part earth electrodes are separate,
otherwise the conditions of the TN earthing system are applicable (in a TT earthing
system, there may be an involuntary connection via the metal structure or other part between
the two earth electrodes; the earth fault current is then high).
Its cross-sectional area must be at least equal to half the cross-sectional area of the
installation's largest protective conductor, with a minimum of 6 mm². However, it may be limited
to 25 mm² for copper or 35 mm² for aluminium.
If it connects two exposed conductive parts, its cross-sectional area must not be smaller than
the smallest of the protective conductors connected to these parts (see fig. 6-9-a).
If S PE1 ≤ S PE 2
S
S LS = PE (*)
S LS = S PE1 2
S PE1 S PE2 S PE
S LS S LS
P1 P2 P
a) between two exposed conductive parts b) between an exposed conductive part and a
structure
(*) with a minimum of: - 2.5 mm² if the conductors are mechanically protected
- 4 mm² if the conductors are not mechanically protected
Conductors which are not incorporated in a cable are mechanically protected when they are
installed in conduits, troughs or casing or protected in a similar way.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In the case of a TNC earthing system, the protective conductor also plays the role of the
neutral conductor.
In this case, the cross-sectional area of the PEN must be at least equal to the greatest value
resulting from the following requirements:
- meet the conditions required for the neutral conductor cross-sectional area.
- The neutral conductor must have the same cross-sectional area as the phase conductors in
the following cases:
. single-phase circuit
. three-phase circuit having phase cross-sectional areas smaller than or equal to 16 mm²
for copper or 25 mm² for aluminium.
- For three-phase circuits having a phase cross-sectional area greater than 16 mm² for
copper or 25 mm² for aluminium, the neutral cross-sectional area may be smaller than that
of the phases as long as the following conditions are met:
. the maximum current likely to continuously circulate in the neutral is lower than the
current-carrying capacity of the chosen cross-sectional area. The unbalance of single-
phase loads and third and multiples of third harmonics which may require the use of a
cross-sectional area greater than the phases must be taken into account (see § 8.2 -
neutral conductor heating).
. the cross-sectional area of the neutral conductor is at least equal to 16 mm² for copper or
25 mm² for aluminium.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
L
∆V = b ρ1 cos ϕ + λ L sin ϕ × I B
S
∆V
for phase-to-neutral fed three-phase or single-phase circuits
Vn
∆V
for phase-to-phase fed single-phase circuits (in this case,
Un
∆V represents a phase-to-phase voltage drop)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The voltage drop is calculated by replacing the design current I B by the motor starting current.
Taking into account all the motors able to start simultaneously, the voltage drop must be lower
than 10% to ensure correct motor starting and not disturb the rest of the installation too much.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
6.1.8. Maximum lengths of wiring systems for protection against indirect contact ( TN
and IT earthing system)
Standard IEC 364 specifies that the fault current for TN and IT earthing systems must be
cleared in a time compatible with the protection of persons.
This time is determined by a curve in relation to the prospective touch voltage; it is based on
the physiological effects of the electrical current on the human body. To simplify matters, using
this curve, it is possible to determine a maximum disconnecting time in relation to the nominal
voltage of the installation (see table 6-20 and 6-21).
(Volts)
non-distributed neutral distributed neutral
120/240 0.8 5
Table 6-20: maximum disconnecting times in the IT earthing system (second fault)
120 0.8
230 0.4
277 0.4
400 0.2
(*) these values are not valid in premises containing a bath or shower.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Note 1: if the disconnecting time is more than the time t0 , but less than 5 seconds, protection is
allowed by IEC 364 (§ 413.1.3.5) in the following cases:
- in distribution circuits when the protective conductor at the downstream end of the circuit is
directly connected to the main equipotential bonding.
- in terminal circuits supplying stationary equipment only and having a protective conductor
that is connected to the main equipotential bonding and which is located in the area that is
influenced by the main equipotential bonding.
Note 2 : in the TT earthing system, protection is in general ensured by residual current devices which
are set to meet the following condition (see IEC 364, § 413.1.4.2):
RA IA ≤ 50 V
Note 3 : in an IT earthing system, when the exposed conductive parts are earthed individually or in
groups, the conditions of the TT earthing system given in Note 2 must be met (see IEC 364,
§ 413.1.5.3).
n circuit-breaker protection
IEC 364 specifies that the magnetic tripping threshold of the circuit-breaker in TN and IT
earthing systems must be lower than the minimum short-circuit current. Furthermore, any
eventual circuit-breaker time delay must be shorter than the maximum disconnecting time
defined in tables 6-20 and 6-21.
For a given circuit-breaker and cross-sectional area, there is thus a maximum circuit length not
to be exceeded in order to comply with the requirements concerning the protection of persons
against indirect contact.
In the following part of the chapter, we will apply the conventional method for determining
maximum circuit lengths. This is more restrictive than the impedance method, but can be
applied by carrying out the calculations by hand.
In the conventional method, we neglect the influence of the reactance of the conductors for
cross-sectional areas smaller than 150 mm².
For large cross-sectional areas, we will take into account the influence of the reactance by dividing
Lmax by:
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Note: for minimum short-circuit current calculations, refer to the "Industrial network protection guide"
§ 4.4.1.
o TN earthing system
0.8 × Vn × S ph
Lmax =
ρ × (1 + m) × Im
o IT earthing system
0.8 × 3 × Vn × S ph
Lmax =
2 ρ × (1 + m) × I m
0.8 × Vn × S1
Lmax =
2 ρ × (1 + m) × Im
o TT earthing system
No condition on the wiring system length is specified since the protection of persons is
ensured by the residual current device.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n fuse protection
Using the fuse fusing curve, we can determine the current I a ensuring fusion of the fuse in
the time t 0 specified in tables 6-20 and 6-21 (see fig. 6-10). We can then calculate the
maximum length of the wiring system in the same way as for the circuit-breaker replacing I m
by I a .
t0
Ia I
n application
In practice, checking the cross-sectional area of the wiring system in relation to the protection
of persons against indirect contact consists in making sure that the length of the wiring system
is less than Lmax for a given arrangement.
If the wiring system length is greater than Lmax , we can take the following measures:
- choose a circuit-breaker (or trip relay) with a lower magnetic threshold if the selectivity
requirements permit this
- install a residual current circuit-breaker for TNS and IT earthing system (in a TNC
earthing system it is not possible to use a RCD)
- take larger phase and protective conductor cross-sectional areas meeting the maximum
length condition.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
2
tdis I sc ≤ k2 S2
The value of k depends on the core metal and the type of insulating material
(see table 6-22).
Aluminium 74 87
If the disconnecting time is given, the cross-sectional area must comply with:
I
S ≥ sc × tdis
k
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n circuit-breaker protection
The check must be carried out for the maximum short-circuit current at the circuit-breaker
location.
The curves in manufacturers' catalogues give the maximum disconnecting time of the circuit-
breaker. When circuit-breaker tripping is time delayed, the disconnecting time is taken to be
equal to the time delay.
To check the thermal withstand, the short-circuit current value must be calculated with a
resistivity ρ of the conductors taken to be equal to 1.5 times that at 20 °C :
On occurrence of a short circuit, current-limiting circuit-breakers only let a current below the
prospective fault current through (see fig. 6-11).
prospective Isc
limited peak I sc
The wiring system protected by this type of device is not therefore subjected to the
(prospective) calculated Isc thermal stress, but a much smaller stress defined by
manufacturers' limiting curves for each type of circuit-breaker.
2
The limiting curves give the thermal stress tdis I sc expressed in A 2 × second .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
o example
We want to check the thermal withstand of a PVC-insulated 6 mm² copper conductor protected
by a Compact NS 80H-MA 380/415 V circuit-breaker fitted with an LR2-D33 63 thermal relay.
The limiting curves in figure 6-12 give the maximum thermal stress of the circuit-breaker:
2 × 105 A2 × s .
The cable is thus protected up to the circuit-breaker breaking capacity.
n fuse protection
The current causing the most stress is the minimum short-circuit current at the end of the
wiring system.
The fusing time t f of the fuse corresponding to I sc min must comply with the relation:
2 2 2
t f Isc min ≤ k S
The method for calculating I sc min is given in paragraph 4.4.1 of the Protection guide.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Let us consider the diagram in figure 6-13 the data of which is given below.
Since the installation feeds loads requiring good continuity of service the IT earthing system
without distributed neutral is chosen.
o W2 wiring system
This is made up of a PVC insulated copper three-core cable which is installed touching 3 other
multi-core cables on perforated trays in an ambient temperature of 40°C. It is protected by
fuses. It feeds a load having the following characteristics:
- active power P = 15 kW
- efficiency η = 0.89
- cos ϕ = 0.85
o W1 wiring system
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
250 kVA
U sc = 4 %
unearthed neutral
400 V
W1
L1 = 100 m
cos = 0.8
400 V
25 A 50 A 40 A W2
L2 = 15 m
IB
R1
o W2 wiring system
- P = 15 kW
1
- the factor a = = 1.32
η cos ϕ
- the utilisation factor b = 0.9
- for a 400 V three-phase network, the power conversion factor in current is e = 1.4 .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
o W1 wiring system
The maximum design current of the W1 wiring system is obtained by calculating the sum of
currents ( I B ) of all the outgoing feeders fed by W1 and by applying a coincidence factor
estimated at 0.8 (see table 6-2):
n correction factors
o W2 wiring system
Table 6-3 gives the installation method N° 13 and the selection letter E .
o W1 wiring system
Table 6-3 gives the installation method N° 62 and the selection letter D .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
o W2 wiring system
I B = 24.9 A
f = 0.67
For 10 A < I n ≤ 25 A , the current I z of the wiring system protected by this fuse is:
I z = k3 In = 1.21 In = 30.3 A
The equivalent current that the wiring system must be able to carry in standard installation
I
conditions is: I 'z = z = 451
. A
f
Table 6-16 (selection letter E , PVC3, copper) gives a minimum cross-sectional area of
S = 10 mm2 which has a current-carrying capacity of I 0 = 60 A .
o W1 wiring system
I B = 115.9 A
f = 0.935
For an adjustable circuit-breaker, the setting current must comply with the condition Iset ≥ I B ;
I set = 120 A is chosen.
I z = I n = 120 A
The equivalent current that the wiring system must be able to carry in standard installation
I
conditions is: I 'z = z = 128.3 A
f
Table 6-17 (selection letter D , XLPE3, copper) gives a minimum cross-sectional area of
S = 25 mm2 which has a current-carrying capacity of I 0 = 144 A .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
o W2 wiring system
Table 6-20 gives a maximum disconnecting time of t = 0.4 s for a network with non-distributed neutral.
The time-current characteristic for a 25 A rated fuse gives us a current of I a = 200 A for a
disconnecting time of 0.4 s.
The length of the W2 wiring system (15 m) is far smaller than Lmax and the protection of
persons against indirect contact is thus ensured.
o W1 wiring system
S ph 25
whence m= = = 1.56
SPE 16
The circuit-breaker chosen is a Compact NS 125E with an STR 22SE trip relay having a
magnetic tripping threshold set at I m = 1 250 A because of the selectivity.
So as not to oversize the conductors, it is decided that the outgoing feeder should be fitted
with a residual current device which ensures the protection of persons against indirect contact.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
o W2 wiring system
S = 10 mm² , L = 15 m , I B = 24.9 A
15
We deduce from this that ∆ V = 0.0225 × × 0.85 + 0.08 × 10 −3 × 15 × 0.53 × 24.9
10
∆ V = 0.73 V
∆ V 0.73
whence = = 0.3 %
Vn 230
The total voltage drop is 4.2 % (the voltage drop in the W1 wiring system is 3.9 %, see below).
o W1 wiring system
λ = 0.09 × 10 −3 Ω / m
The overall power factor of the installation is cos ϕ = 0.8 , whence sin ϕ = 0.6 .
∆ V = 8.97 V
∆ V 8.97
whence = = 3.9 %
Vn 230
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
o W2 wiring system
For fuse protection, the current to be taken into account is the minimum short-circuit current at
the end of the wiring system. For the IT earthing system, this is the short-circuit current for a
double phase-earth fault.
By applying the conventional method (see § 4.4.1.2 of the Protection guide), we can calculate:
The time-current characteristic of the 25 A rated fuse gives us a fusing time of t f = 5 ms for a
current of 1.97 kA.
( )
2
2
Isc min × t = 1.97 × 10
3
× 5 × 10 −3 = 19.4 × 10 3 A2 × s
The permitted cable thermal withstand is: k 2 S 2 = (115) × 102 = 1322 × 103 A2 × s .
2
The cross-sectional area of S = 10 mm2 is thus largely able to withstand to the fuse thermal
stress.
o W1 wiring system
The maximum short-circuit current of the circuit-breaker (neglecting the connection linking the
circuit-breaker to the transformer) is:
We assume that the circuit-breaker trip relay is delayed by 0.1 second, the maximum short-
circuit thermal stress is then:
( )
2
2
Isc t = 9.02 × 10 3 × 0.1 = 8.14 × 10 6 A2 × s
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n conclusion
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
- determining the cross-sectional area S1 complying with the heating of the cable core under
normal operating conditions, which may be continuous or discontinuous. To do this, it is
necessary to know:
. the actual installation conditions of the wiring system and consequently the overall
correction factor f
- determining the cross-sectional area S 2 required for the thermal withstand of the cable in
the event of a three-phase short circuit
- determining the cross-sectional area S3 required for the thermal withstand of the cable
screen in the event of an earth fault
- possibly checking the voltage drop in the wiring system for the chosen cross-sectional
area S. The technical cross-sectional area S to be selected is the maximum value among
cross-sectional areas S1 , S 2 and S3 .
In medium voltage, a wiring system most often feeds a single load (transformer, motor,
furnace, steam generator), in this case I B is taken to be equal to the rated current of the
device.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n general rules
The current-carrying capacity is the maximum current that a wiring system can continuously
carry without this affecting its life span.
- using table 6-23, define the installation method, its associated table column number and
correction factors to be applied
- using the installation conditions, determine the correction factor values which must be
applied (see tables 6-24 to 6-28)
- calculate the overall correction factor f equal to the product of the correction factors
- using table 6-29 for impregnated paper-insulated cables and tables 6-30 to 6-34 for
synthetically-insulated cables, determine the maximum current that the wiring system can
carry in standard conditions ( f0 to f6 = 1)
- calculate the maximum current-carrying capacity of the wiring system in relation to its
installation conditions: I a = f I 0 .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n installation methods
Table 6-23 gives, for each installation method, the current-carrying capacity table column to be
used for choosing the cross-sectional area of the conductors (see tables 6-29 to 6-34).
A Conduits on wall
(3) 0.90 f1 f5
B Flush mounted
conduits (3) 0.90 f1 f5
F Installed on cable
trays (3) 1 f1 f5
G Installed on brackets
or cable ladders (3) 1 f1 f6
L1 Conduits in open or
ventilated channels (3) 0.80 f1 f5
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
L3 Directly installed in
open or ventilated
channels (3) 0.90 f1 -- f5
L4 Directly installed in
enclosed channels
(3) 0.80 f1 -- f5
L5 Directly installed in
channels filled with
sand (3) 0.80 f1 -- f5
P Manufactured blocks
(3) 0.90 f1 -- f5
P D
S1 Directly buried ____
___
(armoured cables) (1) (2)
1 f2 f3 f4
S2 Buried with
mechanical protection (1) (2) 1 f2 f3 f4
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
P D
S3 Buried in sleeves _______
(1) (2)
0.8 f2 f3 f4
S4 Cables installed in
trefoil formation in a
prefabricated channel, (1) (2) 0.8 f2 f3 f4
buried directly in the
ground, possibly with
extra backfill
S5 Single-core cables
installed in individual
channels, buried
directly in the (1) (2) 0.8 f2 f3 f4
ground, possibly with
extra backfill
Single-core cables in a
flat formation spaced
out in a prefabricated
channel, buried
directly in the
(1) (2) 0.8 f2 f3 f4
ground, possibly with
extra backfill
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n correction factors for ambient temperatures other than 30 °C (cables installed in air): f1
°C PVC XLPE
PE EPR
10 1.22 1.15
15 1.17 1.12
20 1.12 1.08
25 1.06 1.04
30 1.00 1.00
35 0.94 0.96
40 0.87 0.91
45 0.79 0.87
50 0.71 0.82
55 0.61 0.76
Table 6-24: correction factors for ambient temperatures other than 30 °C (cables installed in air)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
°C PVC XLPE
PE EPR
0 1.18 1.13
5 1.14 1.10
10 1.10 1.07
15 1.05 1.04
20 1.00 1.00
25 0.95 0.96
30 0.89 0.93
35 0.84 0.89
40 0.77 0.85
45 0.71 0.80
50 0.63 0.76
60 0.45 0.65
65 - 0.60
70 - 0.53
75 - 0.46
80 - 0.38
Table 6-25: correction factors for ground temperatures other than 20 °C (buried cables)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n correction factors for soil thermal resistivities other than 1 K.m/W (buried cables): f 3
Tableau 6-26: correction factors for soil thermal resistivities other than 1 K.m/W (buried cables)
Determination of the distance "a" in the case of single-core cables installed in a flat or trefloid
formation and three-core cables.
a
a
Table 6-27: correction factors for a group of several wiring systems (buried cables )
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
2 3 4 6 >9
Table 6-28: correction factors for a group of several circuits or several cables (cables installed in air and
away from direct sunlight)
References (1), (2) and (3) of tables 6-29 to 6-34 correspond to the column number given in
table 6-23.
Impregnated paper-insulated cables have stopped being manufactured for several years.
However, for calculation purposes for existing installations, the current-carrying capacities may
be calculated to an approximate value of ± 5% using the following formula:
I = 10 B × S A
I : current-carrying capacity, in A
S : nominal cross-sectional area of the cable, in mm²
A and B : are coefficients given for each type of cable (see table 6-29)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
A B A B
o synthetically-insulated cables
The detailed calculation method for current-carrying capacities of cables under steady-state
operating conditions is given in IEC publication 287.
The current-carrying capacities are given in tables 6-30 to 6-34, according to the type of
conductor, the type of insulating material and the rated voltage.
The rated voltage for which a cable is designed is expressed by a set of three values, in kV, as
U 0 / U (Um) , where:
- U0 : voltage between the conductor core and a reference potential (screen or earth)
- U : voltage between the cores of two phase conductors
- Um : maximum voltage which may occur between the network phases in normal operating
conditions
The expression of the rated voltage differs depending on whether the cable is an individually
screened type or not (see fig. 2.2.a and 2.2.b). For an individually screened cable, U 0 is
different from U , both values being generally in the ratio of 3 .
However, due to the way it is made, a collectively screened cable has an equivalent insulation
level between two phases and between one phase and the screen. This results in U 0 and U
having identical values.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
72 78 62 10 86 94 78
56 61 48 10 67 73 60
72 79 62 16 86 94 79
Table 6-30: current-carrying capacities in three-core collectively screened cables having a rated voltage
lower than or equal to 6/6 (7.2) kV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Copper (1) (2) (3) (1) (2) (3) (1) (2) (3)
10 80 89 71 86 97 76 99 110 93
16 105 115 95 110 125 100 125 145 120
25 135 150 125 140 160 130 165 185 160
35 160 180 150 170 195 160 195 225 200
50 190 215 180 200 230 190 230 265 235
70 235 265 230 245 285 240 285 325 295
95 285 320 280 295 340 295 340 390 360
120 320 365 320 335 385 340 385 445 420
150 360 410 370 375 435 385 430 500 475
185 410 470 425 425 490 445 485 560 550
240 475 540 500 490 570 530 560 650 650
300 540 610 580 550 640 600 630 730 740
400 610 700 670 600 690 700 720 840 860
500 680 780 760 700 810 790 800 940 990
630 770 880 870 790 920 920 910 1 060 1 140
800 850 980 990 870 1 010 1 040 1 000 1 170 1 300
1 000 930 1 070 1 110 950 1 100 1 160 1 100 1 270 1 450
1 200 980 1 130 1 210 1 000 1 160 1 260 1 160 1 350 1 570
1 400 1 030 1 190 1 290 1 050 1 220 1 350 1 220 1 420 1 680
1 600 1 080 1 250 1 360 1 100 1 280 1 420 1 280 1 480 1 770
Aluminium (1) (2) (3) (1) (2) (3) (1) (2) (3)
10 62 69 55 67 76 59 77 87 72
16 80 89 73 86 97 78 98 110 95
25 105 115 96 110 125 100 125 145 125
35 125 140 115 130 150 125 150 175 150
50 150 170 140 160 180 150 180 205 185
70 180 205 175 190 220 185 220 250 230
95 220 250 215 230 265 230 260 300 280
120 250 285 250 260 300 265 300 345 325
150 280 320 285 290 335 300 335 385 370
185 320 365 330 330 380 345 380 440 425
240 370 425 390 385 445 410 440 510 510
300 420 485 455 435 500 470 500 580 580
400 480 550 530 495 580 550 570 660 680
500 540 630 610 560 650 640 640 750 790
630 620 720 710 640 750 750 740 860 920
800 700 810 820 720 840 860 830 970 1 070
1 000 780 900 940 800 930 980 920 1 070 1 220
1 200 840 970 1 030 860 1 000 1 080 990 1 150 1 340
1 400 890 1 030 1 110 910 1 060 1 160 1 050 1 230 1 450
1 600 940 1 080 1 180 950 1 110 1 230 1 100 1 290 1 530
(*) For cables having high density polythene insulation, the values are to be multiplied by:
1.05 for columns (1) and (2)
1.06 for column (3)
Table 6-31: current-carrying capacities in cables made up of three single-core cables having a rated
voltage lower than or equal to 6/10 (12) kV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Table 6-32: current-carrying capacities in cables made up of three single-core cables having a rated
voltage greater than 6/6 (7.2) kV and lower than or equal to 18/30 (36) kV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Copper (1) (2) (3) (1) (2) (3) (1) (2) (3)
10 80 87 71 85 94 75 97 110 92
16 100 115 90 110 120 98 125 140 120
25 130 145 120 140 155 125 160 180 155
35 160 175 145 165 190 155 190 215 190
50 185 205 175 195 220 185 225 250 225
70 230 255 215 240 270 230 275 310 280
95 275 305 260 285 320 275 330 370 340
120 310 345 300 325 365 315 370 420 385
150 345 385 340 365 415 365 420 475 445
185 390 435 385 410 465 410 470 535 510
240 450 500 450 475 530 485 540 610 590
300 500 560 520 530 605 560 610 690 680
Aluminium (1) (2) (3) (1) (2) (3) (1) (2) (3)
10 62 68 55 66 73 58 75 84 71
16 79 87 71 84 94 76 96 110 92
25 100 115 93 110 120 99 125 140 120
35 120 135 115 130 145 120 150 165 145
50 145 160 135 150 170 140 175 195 175
70 180 195 165 185 210 175 215 240 215
95 210 235 205 220 250 215 255 285 260
120 240 270 235 250 285 245 290 325 300
150 270 300 265 285 325 280 325 370 345
185 305 340 300 320 360 320 365 415 395
240 350 390 355 370 420 380 425 480 465
300 395 440 405 420 475 435 480 540 530
(*) For cables having high density polythene insulation, the values are to be multiplied by:
1.05 for columns (1) and (2)
1.06 for column (3)
Table 6-33: current-carrying capacities in three-core individually screened cables having a rated voltage
lower than or equal to 6/10 (12) kV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
16 96 105 95
Table 6-34: current-carrying capacities in three-core individually screened cables having a rated voltage
greater than 6/6 (7,2) kV and lower than or equal to 18/30 (36) kV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The thermal withstand of live conductors must be checked for the maximum short-circuit
current at the origin of the cable. It is calculated using the impedance method taking into
account the participation of all the network elements (motors, generators, etc., see Protection
guide § 4.2).
In the case of an installation with an internal generator set, the thermal withstand is
established on the basis of the short-circuit current during the transient period, this
approximately corresponding to the short-circuit clearance time (see Protection guide § 4.1.2).
For a short-circuit time less than 5 seconds, cable heating is considered to be adiabatic; this
means that the energy stored stays in the core and is not transmitted to the insulating material.
The thermal calculations are then simplified. They are given below.
Note: to check the thermal withstand of protective and equipotential bonding conductors, the earth
fault current must be taken into account (see § 4.2.2 of the Protection guide)
n general method
The heating calculation results are shown by the curves in figure 6-14. They give the current
density withstands δ 0 in different types of cable for a short-circuit time of one second, in
relation to the cable temperature before the short circuit.
The minimum conductor cross-sectional area complying with heating in the case of a short
circuit is determined by the fomula:
I
S = sc
δ
δ0
δ=
t
t : short-circuit time
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n simplified method
This assumes that the cable temperature before the short circuit is equal to the temperature
allowed in steady-state operating conditions.
In this case, the conductor cross-sectional area must meet the following condition:
I
S ≥ sc t
k
For protective conductors, the current to be taken into account is the earth fault current I f .
Insulating material
PVC XLPE
PE EPR
Live conductors
- in aluminium 74 94
Protective conductors a b a b
- in aluminium 95 75 116 94
- in steel 52 _ 64 _
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In the event of a phase-to-screen short circuit, the thermal withstand resulting from the
passage of the fault current I f for a time t , must not exceed the thermal withstand of the
cable screen. If is the earth fault current and the method for determining its value is
described in the Protection guide, paragraph 4-2.
The calculation of the overcurrent permitted in the cable screens depends on what the screen
is made of and the type of cable.
In the absence of precise indications, the values of tables 6-37, 6-38 and 6-39 can be used.
These values correspond to a screen made up of a copper band 0.1 mm thick wrapped around
the insulating material with an overlap of 15 %.
Table 6-36 gives, for each type of insulating material, the temperatures during normal service
and at the end of overcurrents used for calculating cable screen heating.
XLPE 70 250
EPR 70 250
PE 60 150
PVC 60 160
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Rated voltage 6/10 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 18/30 (36) kV
Conductor cross-sectional
area in mm²
50 1 600 1 150 1 000 1 750 1 350 1 050 1 950 1 450 1 150 2 500 1 950 1 550
70 1 750 1 250 1 050 1 900 1 450 1 150 2 100 1 600 1 250 2 700 2 050 1 650
95 1 850 1 350 1 100 2 050 1 550 1 200 2 200 1 700 1 300 2 800 2 150 1 700
120 1 900 1 400 1 150 2 150 1 650 1 300 2 500 1 950 1 550 3 100 2 400 1 900
150 2 150 1 650 1 300 2 400 1 850 1 500 2 600 2 000 1 600 3 150 2 450 1 950
185 2 400 1 850 1 450 2 600 2 000 1 600 2 750 2 150 1 700 3 350 2 600 2 100
240 2 700 2 050 1 650 2 800 2 150 1 700 3 100 2 400 1 950 3 600 2 750 2 200
300 2 800 2 150 1 750 3 150 2 450 1 950 3 300 2 550 2 050 3 800 2 950 2 350
400 3 050 2 350 1 800 3 450 2 650 2 150 3 650 2 800 2 250 4 200 3 300 2 650
500 3 400 2 550 1 950 3 800 2 950 2 350 4 100 3 200 2 550 4 550 3 550 2 850
630 3 750 3 000 2 300 4 250 3 300 2 650 4 450 3 450 2 800 4 950 3 850 3 100
800 4 400 3 400 2 600 4 650 3 600 2 900 4 850 3 750 3 000 5 300 4 150 3 300
1 000 5 100 3 900 3 050 5 200 4 050 3 250 5 350 4 200 3 350 5 850 4 550 3 650
1 200 5 350 4 100 3 300 5 450 4 250 3 400 5 650 4 400 3 550 6 150 4 800 3 850
1 400 5 600 4 400 3 550 5 900 4 550 3 650 6 050 4 700 3 800 6 550 5 100 4 100
1 600 6 000 4 700 3 800 6 200 4 850 3 900 6 400 5 000 4 000 6 900 5 350 4 300
Table 6-37: single-core or three-core individually screened cables with XLPE or EPR insulation -
short-circuit current permitted in the screen (A)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Rated voltage 6/10 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 18/30 (36) kV
Conductor cross-sectional
area in mm²
50 1 100 800 580 1 150 840 640 1 250 1 000 770 1 750 1 300 990
70 1 300 920 700 1 350 990 760 1 450 1 100 820 1 750 1 300 1 000
95 1 350 1 000 750 1 450 1 050 820 1 550 1 150 880 2 050 1 550 1 200
120 1 450 1 050 800 1 500 1 150 860 1 650 1 200 930 2 150 1 650 1 230
150 1 550 1 100 840 1 600 1 200 910 1 700 1 300 1 000 2 250 1 700 1 300
185 1 650 1 150 900 1 700 1 250 970 2 000 1 500 1 200 2 350 1 800 1 400
240 1 800 1 450 1 100 2 000 1 550 1 200 2 150 1 650 1 250 2 650 2 050 1 600
300 2 000 1 550 1 200 2 150 1 650 1 300 2 300 1 750 1 350 2 800 2 150 1 700
400 2 300 1 750 1 400 2 600 2 000 1 550 2 650 2 050 1 600 3 000 2 300 1 800
500 2 550 1 900 1 500 2 900 2 200 1 750 3 050 2 350 1 850 3 400 2 600 2 050
630 2 750 2 050 1 550 3 000 2 300 1 800 3 150 2 400 1 900 3 500 2 650 2 050
800 3 000 2 250 1 700 3 300 2 500 2 000 3 450 2 600 2 100 3 700 2 800 2 200
1 000 3 300 2 400 1 800 3 500 2 700 2 100 3 650 2 800 2 200 3 950 3 000 2 400
1 200 3 550 2 550 1 900 3 700 2 850 2 200 3 850 2 950 2 300 4 200 3 200 2 550
1 400 3 650 2 750 2 000 3 900 3 000 2 350 4 050 3 100 2 450 4 350 3 350 2 650
1 600 3 750 2 850 2 100 4 000 3 100 2 400 4 150 3 200 2 500 4 500 3 400 2 700
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Table 6-39: PVC-insulated three-core collectively screened cables with a rated voltage of 6/6 (7.2 kV) -
short-circuit current permitted in the screen (A)
o example
According to table 6-38, the minimum cross-sectional area of the conductor depends on the
short-circuit time:
The cross-sectional area S3 is selected in relation to I f and the short-circuit time, which is
taken to be equal to the longest time needed to clear the fault (e.g., the back-up protection
time delay).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
For a three-phase circuit, the voltage drop (single-phase voltage) is calculated by the fomula:
L
∆V = ρ1 cos ϕ + λ L sin ϕ I B
S
∆V
Vn
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
determination of the equivalent current (1) determination of the cross-sectional area S1 of the cable
cable column and IB able to carry I z in standard installation conditions in
overall correction Iz relation to the type of cable, its insulation and rated
f
factor (see tab. 8-23) voltage (see tab. 8-29 to 8-34)
economic cross-sectional
area possibly chosen
Figure 6-15: logigram for determining the minimum cross-sectional area of a medium voltage cable
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n single-core cables
The passage of a current in the cable core produces an induced voltage in the screen. This
voltage depends on the geometrical arrangement of the cables, the length and the current
carried:
E0 = 0.145 × log10 × l × I
2a
d
For very long cables, E0 may reach dangerous values for persons. The standard
recommends screen earthing at both ends when E0 is likely to exceed the limit of 50 V
under steady-state operating conditions.
However, screen earthing at both ends produces currents continuously circulating in the
screen.
For screen earthing at one end only, on occurrence of a short circuit, the potential induced on
the second end may be high and cause a breakdown of the screen insulation where it is
connected. The necessary precautions must therefore be taken.
In balanced steady-state operating conditions (or during a three-phase short circuit), the
induced voltage in screens earthed at both ends causes a three-phase current to circulate.
E0
I0 =
Rs2 + Xs2
Xs = 0.145 × log10 × l
2a
where
d
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
o example
Let us consider a 20 kV aluminium single-core cable with a cross-sectional area of 300 mm² ,
with PE insulation and a length of l = 3 km , buried in soil having a resistivity of ρ = 100 Ω ⋅ m ,
the characteristics of which are as follows:
- Icapacity = 500 A
- d = 33.5 mm
- a = 38.5 mm
- Rs = 0.45 Ω / km
- I B = 400 A
- Isc = 8 kA
2a
E0 = 0.145 × log10 × I B × l = 63 V
d
The 50 V limit is exceeded and the screen must therefore be earthed at both ends.
E0
I0 =
Rs2 + Xs2
Rs = 1.35 Ω
whence I0 = 46.4 A
Note: the circulation current in the screen is independent of the cable length.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
2a
E0 sc = 0.145 × log10 × I sc × l = 1 260 V
d
The circulation current in the screen is then:
I0 sc = 927 A
This current must be withstood by the screen for the maximum short-circuit time. This is the
case since it can withstand 1 350 A for 2 s (see table 6-38).
Note: if the cable length was 2 km, the screen would be earthed at one end only. The voltage induced
in the screen on occurrence of the short circuit will then be equal to 840 V. In this case it is
necessary to check that the screen insulation at the point where the terminal box is located is
sufficient.
Ws = Rs I02
Ws
We determine the ratio =6%
Wc
The screen losses represent 6 % of the core losses. They must therefore be taken into
account when determining the maximum current-carrying capacity of the cable.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
As we saw in the previous example, when the screen is earthed at both ends, the continuous
circulation of induced current in the screen causes extra heating in the cable and consequently
reduces its current-carrying capacity.
Generally, this phenomenon is only to be taken into account for cables with a cross-sectional
area greater than 240 mm².
- thin screen without armour, for S > 1 000 mm² the current-carrying capacity is reduced by 5 %
- cables with screen and armour, the current-carrying capacity is to be reduced by:
n three-core cables
For three-core collectively screened cables, the electromagnetic field is zero in balanced
operating conditions.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The W1 wiring system is made up of three single-core three-phase 6/10 (12) kV aluminium
cables with XLPE insulation, directly installed in a enclosed channel in a temperature of 35 °C.
The time delay of the protection against phase-to-phase short circuits is: t = 0.2 s .
20 kV
T1
S n = 10 MVA
U sc = 8 %
1000 A
U n = 5.5 kV
W1 wiring system
l = 1200 m
T2 S n = 630 kVA
U sc = 4 %
400 V
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The W1 wiring system only feeds the 630 kVA power transformer T2 .
Sn 630 × 10 3
I B = In = = = 66 A
3 Un 3 × 5.5 × 10 3
The equivalent current that the cable must be able to carry in standard installation conditions
is:
I
I z = B = 86 A
f
Table 6-31 (column (3), XLPE, aluminium) gives a minimum cross-sectional area of
S1 = 16 mm2 which has a current-carrying capacity of I 0 = 95 A .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Neglecting the impedance upstream of the transformer and the impedance of the transformer-
busbar connection, the maximum short-circuit current at the origin of the cable is equal to the
short-circuit current of the transformer.
( )
2
Un2 U sc 5.5 × 10 3 8
ZT 1 = × = × = 0.242 Ω
Sn 100 10 × 10 6 100
Un 5.5 × 10 3
Isc = 11
. = 11
. × = 14.4 kA (see Protection guide § 4.2.1)
3 ZT 1 3 × 0.242
I
S2 ≥ sc t
k
k = 94 : value of the coefficient corresponding to a XLPE-insulated aluminium conductor (see table 6-35)
t = 0.2 s : short-circuit time equal to the protection time delay
whence S 2 ≥ 69 mm2
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The 5.5 kV distribution network has an earthing system with a 1 000 A current limiting resistor.
Vn
If = + IC (see Protection guide § 4.3.2)
RN
The capacitive current of an industrial network is of the order of several amps to several dozen
amps and it can thus be neglected in relation to the 1 000 A limiting current.
We assume that the screen must be able to withstand the fault current for 2 seconds, in order
to take into account the maximum time delay of the protection against phase-earth faults and
eventual reclosing.
The cross-sectional area of the conductor complying with the thermal withstand of the cable
screen is then:
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
l
∆V = ρ1 cos ϕ + λl sin ϕ I B
S
We assume that the cable load has a cos ϕ = 0.6 (sin ϕ = 0.8)
1 200
whence ∆V = 0.036 × 0.8 + 0.15 × 10 −3 × 1 200 × 0.6 × 66
50
∆V = 53 V
∆V 53
The relative voltage drop is: = = 1.7 %
Vn 5500
3
In spite of a very long cable length for an industrial network, the voltage drop is acceptable.
S1 = 16 mm²
S 2 = 70 mm²
S3 = 50 mm²
S = 70 mm²
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
But it may be useful to take into account the economic criterion, based on the cost of
investment and the operating costs, when looking for the optimum cross-sectional area.
- the cable cost, linear function of the cross-sectional area S and length L ,
i.e. K1 L + K2 L S
- the cost of civil engineering and installation, depending on the length and regardless of the
cross-sectional area in a limited interval, i.e. K3 L .
To calculate the economic cross-sectional area, only the cost of the Joule losses w relative to
the wiring system is taken into account:
L HC
w=n×ρ × I2 Euros.
S 1 000
L : cable length
S : cross-sectional area of conductors
I : current carried, assumed to be constant, in A
H : number of cable operating hours (for a year H = 8 760)
C : cost of kWh, Euro/kWh.
The cost of investment and the cost of losses w do not have the same term of payment. It is
necessary to change in order to carry out the sum of their values. This can be done by
converting the operating costs paid at the end of consecutive years to current value, i.e. by
converting them to the period in which the cable is purchased.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
If N (years) is the amortizement time forecast for the cable, and if the price of energy and
the cable load are assumed to be constant for the entire period, the sum of converted values
of Joule losses is:
1 1 1 (1 + t ) N − 1
W =w + + ....... + = w×
1 + t (1 + t ) 2
(1 + t ) N t (1 + t )
N
t (1 + t )
N
w
We can write W = , where A =
A (1 + t ) N − 1
L 2 HC
P ( S) = K3 L + K1 L + K2 L S + n ρ I
S 1 000 × A
∂ P
The function P ( S ) goes via a minimum = 0
∂ S
nρHC
for a cross-sectional area of S0 = I
K2 A × 1 000
KI HC
S0 = , mm²
100 A
The value of the economic cross-sectional area to be chosen is the closest standard
value to S 0 .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n example
- design current I B = 66 A
0.08 × (1 + 0.08)
20
A= = 0.102
(1 + 0.08)20 − 1
The economic cross-sectional area is the closest standard value to S 0 , i.e. S = 150 mm2 .
In practice, the economic cross-sectional area is often greater than the technical cross-
sectional area.
- Improved voltage quality under normal operating conditions and reduced amplitude of
voltage surges during motor or other machine starting.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.