Specifications
Mounting Arrangements
Conditions of Sale
S&C Three-Pole Alduti-Rupter Switches are available in
STANDARD: Seller’s standard conditions of sale set Standard Mounting Arrangements as described in S&C
forth in Price Sheet 150 apply, except as modified under Data Bulletin 761-80. Departures from Standard Mounting
“WARRANTY QUALIFICATIONS” on page 2. Arrangements are also available and fall into three
categories:
SPECIAL TO THIS PRODUCT: 1. Standard Minor Modifications of Standard Mounting
Arrangements are those which are so frequently
INCLUSIONS: S&C Alduti-Rupter Switches are available encountered that they are included on S&C’s basic
in a wide variety of styles and mounting configurations. erection drawings (ED). Applicability of Standard
Three-Pole Integer Style switches are pre-engineered, Minor Modifications is listed in the table on page 18.
preassembled, and preadjusted—all three poles are The applicable Standard Minor Modifications may be
mounted on a one-piece base with necessary electrical specified by adding the appropriate “-S” suffix to the
clearances built in. The complete three-pole interrupter erection drawing (ED) number.
switch assembly and its operating mechanism are provided 2. Special Minor Modifications of Standard Mounting
as a single package that includes removable lifting means, Arrangements are those which include such departures
shipped in place, for convenient rigging and hoisting during as special base drillings or special mounting brackets for
installation. operating-mechanism components. For this category of
Alduti-Rupter Switches are also available in three-pole “special,” S&C will prepare a custom erection drawing
group-operated designs that feature pole-units mounted (ED) based on the Standard Mounting Arrangement
on individual bases. Switches in these styles are especially erection drawing (ED). Switches will be supplied with an
designed for installation on substation structures or operating mechanism for the Special Minor Modification
on overhead lines not suited to integer style switch of a Standard Mounting Arrangement as required.
configurations. 3. Special Mounting Arrangements are those which
Single-Pole Style switches are available in vertical and involve complete departures from the Standard Mounting
inverted mounting configurations for use in single-phase Arrangements brought about by customizing an S&C
switching applications. Single-pole style switches are Alduti-Rupter Switch to fit the user’s structure. Custom
operable using a conventional hookstick. erection drawings (ED) will be provided as required.
All three-pole Alduti-Rupter Switches are provided with EXCLUSIONS: Alduti-Rupter Switches do not include
an operating mechanism that includes: connectors. Various connector arrangements are available
• Three switch poles (integer style switches are shipped as listed in the table on page 20. When ordering, specify
complete with interphase drive, factory-assembled on a the quantity and catalog number of connector arrangement
single base). desired.
• A detailed erection drawing (ED) of the applicable
mounting arrangement.
• All required interphase and vertical operating pipe as
specified on the erection drawing (ED). Refer to the
tables on pages 6 through 16 for vertical operating pipe
included with each Standard Mounting Arrangement.
• The appropriate set of operating-mechanism com-
ponents; e.g., handle, rod guides, or guide bearings,
couplings, bell crank assembly, etc.
• Complete installation instructions.
Upright Clockwise
Opening678 14.4 17.0 110 1200 1200 40 000 AEGHK(L) 137412R8-Er 137412R8r
ED-136R20 24
25 27 150 1200 1200 40 000 AE(GHKL) 137413R9-Er 137413R9r
Upright Clockwise
Opening678�
(Extra Mounting-
Pole Clearance) 14.4 17.0 110 1200 1200 40 000 AEGHK(L) 138412R2-E 138412R2
ED-136R20
25 27 150 1200 1200 40 000 AE(GHKL) 138413R2-E 138413R2
24
Upright
Counterclockwise 14.4 17.0 110 1200 1200 40 000 AEGHK(L) 137512R8-Er 137512R8r
Opening678 ED-135R20
25 27 150 1200 1200 40 000 AE(GHKL) 137513R9-Er 137513R9r
Tiered Outboard
Clockwise 14.4 17.0 110 1200 1200 40 000 AEGHK(L) 137812R7-E 137812R7
Opening78 ED-144R18
25 27 150 1200 1200 40 000 AE(GHKL) 137813R9-E 137813R9
28
25/34.5 38 150 600 600 40 000 AEGHKL 137767R3-Edf 137767R3d
ED-676R3 34.5 38 200 600 600 40 000 AEGHKL 137764R3-Ed 137764R3d
34.5 38 200 1200 1200 40 000 AE(G)HKL 147764-Eda 147764da
1 The switches shown include the appropriate set of operating- 8 Bracket assemblies for mounting either three or six surge arresters
mechanism components as specified on the erection drawing (ED) for can be provided by adding suffix “-A1” or “-A2,” respectively, to the
the switch. Switches do not include connectors (refer to table on page catalog number of the switch.
20). d This switch has a one-time duty-cycle fault-closing rating of
2 The applicable Standard Mounting Arrangement, designated by the 15,000 amperes, RMS asymmetrical when operated by the applicable
erection drawing (ED) number shown, should be specified when ordering. S&C Switch Operator—or a one-time duty-cycle fault-closing capability
The “-S” suffixes in parentheses identify available Standard Minor of 15,000 amperes, RMS asymmetrical as a manually operated switch
Modifications to the basic erection drawing (ED). The applicable Standard (without quick-make mechanism, and when operated vigorously through
Minor Modifications may be specified by adding the appropriate suffix to its full travel without hesitation at any point). These values represent
the erection drawing (ED) number. Refer to page 18 for description. the level of available fault current into which the switch can be closed
Special Minor Modifications and Special Mounting Arrangements are not once, with the switch remaining operable and able to carry and
available for these switches. interrupt rated continuous current.
3 Refer to the ED drawings for mounting dimensions and heights. f Applicable at 34.5 kV where leakage distance to ground meets user’s
4 The 3-second rating is 25,000 amperes, RMS symmetrical. requirements. For 25/34.5-kV Cypoxy station post insulators the leakage
distance is 26Z\v inches (667 mm).
5 Applications indicated by symbols in parentheses are conditional.
Refer to “CONDITIONAL APPLICATIONS” table, page 5. a Refer to the nearest S&C Sales Office for dimensional information.
6 Optional crossarm braces SDA‑10367‑1 are recommended for r This switch includes two-hole terminal pads as standard. If four-bolt
switches in the vertical mounting configuration and SDA-10367 for connectors are required, specify the two-to-four bolt adapter Catalog
switches in the upright mounting configuration. Number MDA-1162-1 and the four-bolt connector Catalog Number
4569R1-B. Refer to the “CONNECTORS” table on page 20 for more
7 These switches include dead-ending brackets as standard. Extension- information.
link assemblies can be provided by adding suffix “-D” to the catalog
number of the switch. Maximum dead-end loading: 2000 pounds (900 kg)
per conductor where pull-off forces are applied to only one side of the
switch; 8000 pounds (3600 kg) per conductor where equal pull-off forces
are applied to both sides of the switch.
22
Upright
Clockwise 14.4 17.0 110 1200 1200 40 000 AEGHK(L) 137392R2-Er 137392R2r
Opening890 ED-636R4 24
25 27 150 1200 1200 40 000 AE(GHKL) 137393R9-Er 137393R9r
Upright
Clockwise
Opening890
(Extra Mounting-
Pole Clearance) 14.4 17.0 110 1200 1200 40 000 AEGHK(L) 138392R2-Er 138392R2r
ED-636R4
25 27 150 1200 1200 40 000 AE(GHKL) 138393R2-Er 138393R2r
24
Upright
Counterclockwise 14.4 17.0 110 1200 1200 40 000 AEGHK(L) 137492R2-Er 137492R2r
Opening890 ED-635R4
25 27 150 1200 1200 40 000 AE(GHKL) 137493R9-Er 137493R9r
Tiered Outboard
Clockwise
Opening90
1 The switches shown include the appropriate set of operating- 9 Bracket assemblies for mounting either three or six surge arresters
mechanism components as specified on the erection drawing (ED) for can be provided by adding suffix “-A1” or “-A2,” respectively, to the
the switch. Switches do not include connectors (refer to table on page catalog number of the switch.
20). 0 For provisions only for dead-ending, add suffix “-C” to the catalog
2 Base is a fiberglass-reinforced pultruded structural tube especially number of the switch. Maximum dead-end loading: 700 pounds (315 kg)
constructed for high strength and is finished with a coat of gray per conductor where pull-off forces are applied to only one side of the
polyurethane enamel. switch; 8000 pounds (3600 kg) per conductor where equal pull-off forces
3 Fiberglass interphase shaft is standard with this style. are applied to both sides of the switch. Also specify, if required, one set of
six extension-link assemblies by adding suffix “-D” to the catalog number
4 The applicable Standard Mounting Arrangement, designated by the of the switch; i.e. Catalog Number 137392R1-CD.
erection drawing (ED) number shown, should be specified when ordering.
The “-S” suffixes in parentheses identify available Standard Minor r This switch includes two-hole terminal pads as standard. If four-bolt
Modifications to the basic erection drawing (ED). The applicable Standard connectors are required, specify the two-to-four bolt adapter Catalog
Minor Modifications may be specified by adding the appropriate suffix to Number MDA-1162-1 and the four-bolt connector Catalog Number
the erection drawing (ED) number. Refer to page 18 for description. 4569R1-B. Refer to the “CONNECTORS” table on page 20 for more
Special Minor Modifications and Special Mounting Arrangements are not information.
available for these switches. d This switch has a one-time duty-cycle fault-closing rating of 15,000
5 Refer to ED drawings for mounting dimensions and heights. amperes, RMS asymmetrical when operated by the applicable S&C
Switch Operator—or a one-time duty-cycle fault-closing capability of
6 The 3-second rating is 25,000 amperes, RMS symmetrical. 15,000 amperes, RMS asymmetrical as a manually operated switch
7 Applications indicated by symbols in parentheses are conditional. (without quick-make mechanism, and when operated vigorously through
Refer to “CONDITIONAL APPLICATIONS” table, page 5. its full travel without hesitation at any point). These values represent the
8 Optional crossarm braces SDA-10367-1 are recommended for level of available fault current into which the switch can be closed once,
switches in the vertical mounting configuration and SDA-10367 for with the switch remaining operable and able to carry and interrupt rated
switches in the upright mounting configuration. Crossarm provisions continuous current.
5053 are available when crossarms are supplied by the customer. f Refer to the nearest S&C Sales Office for dimensional information.
Vertical or Upright 14.4 17.0 110 600 600 40 000 AEGHK(L) 137212R3-E 137212R3
Counter-clockwise 30
Opening 25 27 150 600 600 40 000 AEG(HKL) 137213R7-E 137213R7
1 The switches shown include the appropriate set of operating- 6 Standard Minor Modifications of the Standard Mounting
mechanism components as specified on the erection drawing (ED) for Arrangement(s) for these switches are listed in the table on page 18. The
the switch. Switches do not include connectors (refer to table on page applicable Standard Minor Modifications listed therein may be specified
20). by adding the appropriate “‑S” suffix to the erection drawing (ED) number.
2 Switches are available in a variety of Standard Mounting Arrangements, Refer to page 1 for Special Minor Modifications and Special Mounting
designated by erection drawing (ED) number, as described in Data Arrangements for these switches.
Bulletin 761-80. Specify the applicable erection drawing (ED) number 7 Three-Pole Side-Break Heavy-Duty style switches rated 34.5 kV, while
when ordering. provided with design features for fault closing, are not assigned fault-
3 Refer to ED drawings for mounting dimensions and heights. closing ratings or capabilities because special mounting arrangements
may deny the requisite high-speed closing behavior.
4 The 3-second rating is 25,000 amperes, RMS symmetrical. f Refer to the nearest S&C Sales Office for dimensional information.
5 Applications indicated by symbols in parentheses are conditional.
Refer to “CONDITIONAL APPLICATIONS” table, page 5.
Upright ED-92AR9
Clockwise 14.4 17.0 110 600 600 40 000 AEGHK(L) 137032R1-E 137032R1
Opening ED-114AR11
32
Upright ED-91AR9
Counter-clockwise 14.4 17.0 110 600 600 40 000 AEGHK(L) 137232R1-E 137232R1
Opening ED-113AR12
1 The switches shown include the appropriate set of operating- suffix to the erection drawing (ED) number. Refer to page 18. Special
mechanism components as specified on the erection drawing (ED) for Minor Modifications or Special Mounting Arrangements are not available
the switch. Switches do not include connectors (refer to table on page for these switches.
20). 3 Refer to ED drawings for mounting dimensions and heights.
2 The applicable Standard Mounting Arrangement, designated by 4 The 3-second rating is 25,000 amperes, RMS symmetrical.
the erection drawing (ED) number shown, should be specified when
ordering. The “-S” suffixes in parentheses identify available Standard
5 Applications indicated by symbols in parentheses are conditional.
Refer to “CONDITIONAL APPLICATIONS” table, page 5.
Minor Modifications to the basic erection drawing (ED). The applicable
Standard Minor Modifications may be specified by adding the appropriate
Pole-Top90
14.4 17.0 200 2400 1600 40 000 AE(G)HKL 135122-E 135122
25/34.5 38 150 600 600 40 000 AEGHKL 135624R2-E f 135624R2
ED-152R3 25/34.5 38 150 1200 1200 40 000 AE(G)HKL 135824R2-E f 135824R2 34
34.5 38 200 600 600 40 000 AEGHKL 135724R2-E 135724R2
34.5 38 200 1200 1200 40 000 AE(G)HKL 135924R2-E 135924R2
Upright90⁄
14.4 17.0 200 2400 1600 40 000 AE(G)HKL 135132-Eh 135132h
25/34.5 38 150 600 600 40 000 AEGHKL 135634R2-Ef 135634R2
ED-153R5 25/34.5 38 150 1200 1200 40 000 AE(G)HKL 135834R2-Ef 135834R2 35
34.5 38 200 600 600 40 000 AEGHKL 135734R2-E 135734R2
34.5 38 200 1200 1200 40 000 AE(G)HKL 135934R2-E 135934R2
Vertical0⁄
14.4 17.0 200 2400 1600 40 000 AE(G)HKL 135142-Eh 35142h
25/34.5 38 150 600 600 40 000 AEGHKL 135644R2-Ef 135644R2
ED-154R5 25/34.5 38 150 1200 1200 40 000 AE(G)HKL 135844R2-Ef 135844R2 36
34.5 38 200 600 600 40 000 AEGHKL 135744R2-E 135744R2
34.5 38 200 1200 1200 40 000 AE(G)HKL 135944R2-E 135944R2
Tiered
Outboard90
25/34.5 38 150 600 600 40 000 AEGHKL 135654R2-Ef 135654R2
Triangular90
25//34.5 38 150 600 600 40 000 AEGHKL 135664R2-Ef 135664R2
1 The switches shown include the appropriate set of operating- 7 No provisions for dead-ending are offered since the mounting
mechanism components as specified on the erection drawing (ED) pedestals are not intended for such duty.
for the switch. Switches do not include connectors (refer to table on 8 Select mounting pedestal from table on page 17.
page 20).
9 These switches include dead-ending brackets as standard. Maximum
2 The applicable Standard Mounting Arrangement, designated by dead-end loading: 2000 pounds (900 kg) per conductor where pull-off
the erection drawing (ED) number shown, should be specified when forces are applied to only one side of the switch; 8000 pounds (3600 kg)
ordering. The “-S” suffixes in parentheses identify available Standard per conductor where equal pull-off forces are applied to both sides of
Minor Modifications to the basic erection drawing (ED). The applicable the switch. If required, order one set of six extension-link assemblies by
Standard Minor Modifications may be specified by adding the appropriate adding suffix “-D” to the catalog number of the switch.
suffix to the erection drawing (ED) number. Refer to page 18. Special
Minor Modifications and Special Mounting Arrangements are not 0 Bracket assemblies for mounting either three or six surge arresters
available for these switches. can be provided by adding suffix “-A1” or “-A2,” respectively, to the
catalog number of the switch.
3 Refer to ED drawings for mounting dimensions and heights.
⁄ Optional crossarm braces SDA-10367-1 are recommended for
4 The 3-second rating for 600- and 1200-ampere switches is 25,000 switches in the vertical mounting configuration and SDA-10367 for
amperes, RMS symmetrical. switches in the upright mounting configuration.
5 The one-time duty-cycle fault closing capability for a manually operated h These switches can be applied at system voltages above 17.0 kV
switch (without quick-make mechanism, and when operated vigorously where 2400 ampere continuous current rating is required. Application
through its full travel without hesitation at any point) for 600‑ampere Classifications AE(G)HKL for 34.5-kV switches rated 1200 amperes
and 1200-ampere switches is 20,000 amperes and 30,000 amperes, continuous apply. Refer to “APPLICATION CLASSIFICATIONS” table on
RMS asymmetrical, respectively. The one-time duty-cycle fault-closing page 4. Applications indicated by symbols in parenthesis are conditional;
rating for 600-ampere and 1200-ampere switches is 20,000 amperes refer to the “CONDITIONAL APPLICATIONS” table on page 5.
and 30,000 amperes, RMS asymmetrical, respectively, when switches
are operated by the applicable S&C Switch Operator. The one-time duty- d Refer to the nearest S&C Sales Office for dimensional information.
cycle fault-closing rating defines the level of available fault current into f Applicable at 34.5 kV where leakage distance to ground meets user’s
which the switch can be closed once, with the switch remaining operable requirements. For 25/34.5-kV Cypoxy station post insulators the leakage
and able to carry and interrupt rated continuous current. distance is 26Z\v inches (667 mm).
6 Applications indicated by symbols in parentheses are conditional.
Refer to “CONDITIONAL APPLICATIONS” table on page 5.
1 The switches shown include the appropriate set of operating- 8 Three-Pole Vertical-Break Style switches rated 25/34.5 kV and
mechanism components as specified on the erection drawing (ED) 34.5 kV, while provided with design features for fault closing, are not
for the switch. Switches do not include connectors (refer to table on page assigned fault-closing ratings or capabilities because special mounting
20). arrangements may deny the requisite high-speed closing behavior.
2 Switches are available in a variety of Standard Mounting Arrangements, a The one-time duty-cycle fault-closing capability for a manually
designated by erection drawing (ED) number, as described in Data operated switch rated 2400 amperes continuous (without quick-make
Bulletin 761-80. Specify the applicable erection drawing (ED) number mechanism, and when operated vigorously through its full travel without
when ordering. hesitation at any point) is 30,000 amperes, RMS, asymmetrical. The
3 Refer to ED drawings for mounting dimensions and heights. one-time duty-cycle fault-clearing rating is 30,000 amperes, RMS,
asymmetrical, when switches are operated by the applicable S&C Switch
4 The 3-second ratings for 600- and 1200-ampere switches are 25,000 Operator. The one-time duty-cycle fault-closing rating defines the level
and 40,000 amperes, RMS symmetrical, respectively, except for the of available fault current into which the switch can be closed once, with
25/34.5‑kV and 34.5-kV switches which have a 3-second rating of the switch remaining operable and able to carry and interrupt continuous
25,000 amperes, RMS symmetrical. current.
5 Applications indicated by symbols in parentheses are conditional. h These switches can be applied at system voltages above 17.0 kV
Refer to “CONDITIONAL APPLICATIONS” table, page 5. where 2400 ampere continuous current rating is required. Application
6 For switches to be supplied less operating pipe, specify by adding Classifications AE(G)HKL for 34.5-kV switches rated 1200 amperes
suffix “-P” to the erection drawing (ED) number. continuous apply. Refer to “APPLICATION CLASSIFICATIONS” table on
7 Standard Minor Modifications of the Standard Mounting page 4. Applications indicated by symbols in parenthesis are conditional;
Arrangement(s) for these switches are listed in the table on page 18. The refer to the “CONDITIONAL APPLICATIONS” table on page 5.
applicable Standard Minor Modifications listed therein may be specified f Applicable at 34.5 kV where leakage distance to ground meets user’s
by adding the appropriate “‑S” suffix to the erection drawing (ED) number. requirements. For 25/34.5-kV Cypoxy station post insulators the leakage
Refer to page 1 for Special Minor Modifications and Special Mounting distance is 26Z\v inches (667 mm).
Arrangements for these switches.
Vertical,
Upright, or 69 72.5 350 600 600 40 000 AEG N/A 320306 h
Tiered0
1 The switches shown include the appropriate set of operating- 7 For switches to be supplied less operating pipe, specify by adding
mechanism components as specified on the erection drawing (ED) for suffix “-P” to the erection drawing (ED) number.
the switch. Switches do not include connectors (refer to table on page 8 Standard Minor Modifications of the Standard Mounting
20). Arrangement(s) for these switches are listed in the table on page 18. The
2 Switches are available in a variety of Standard Mounting Arrangements, applicable Standard Minor Modifications listed therein may be specified
designated by erection drawing (ED) number, as described in Data by adding the appropriate “‑S” suffix to the erection drawing (ED) number.
Bulletin 761-80. Specify the applicable erection drawing (ED) number Refer to page 1 for Special Minor Modifications and Special Mounting
when ordering. Arrangements for these switches.
3 Refer to ED drawings for mounting dimensions and heights. 9 Switches with a “G” suffix are furnished with a grounding switch.
4 The 3-second rating is 25,000 amperes, RMS symmetrical. 0 Switches rated 69-kV may be power-operated using S&C Type LS-1
5 Three-Pole Double-Break Style switches rated 34.5 kV and 46 kV, Switch Operator.
while provided with design features for fault closing, are not assigned fault h Refer to the nearest S&C Sales Office for dimensional information.
closing ratings or capabilities because special mounting arrangements
may deny the requisite high-speed closing behavior.
6 Applications indicated by symbols in parentheses are conditional.
Refer to “CONDITIONAL APPLICATIONS” table, page 5.
Vertical8
Tiered
Outboard78
Pole-Top78
Pedestal890
1 The switches shown include the appropriate set of operating- 6 Applications indicated by symbols in parentheses are conditional.
mechanism components as specified on the erection drawing (ED) Refer to “CONDITIONAL APPLICATIONS” table, page 5.
for the switch. Switches do not include connectors (refer to table on 7 These switches include dead-ending brackets as standard. Maximum
page 20). dead-end loading: 2000 pounds (900 kg) per conductor where pull-off
2 The applicable Standard Mounting Arrangement, designated by the forces are applied to only one side of the switch; 8000 pounds (3600 kg)
erection drawing (ED) number shown, should be specified when ordering. per conductor where equal pull-off forces are applied to both sides of
The “-S” suffixes in parentheses identify available Standard Minor the switch. If required, order one set of six extension-link assemblies by
Modifications to the basic erection drawing (ED). The applicable Standard adding suffix “-D” to the catalog number of the switch.
Minor Modifications may be specified by adding the appropriate suffix to 8 These switches can be supplied with Lindsey current sensor(s),
the erection drawing (ED) number. Refer to page 18 for description. auxiliary switch, and control cable. Refer to “AUTOMATION
Special Minor Modifications and Special Mounting Arrangements are not COMPONENTS” table on page 19.
available for these switches.
9 No provisions for dead-ending are offered since the mounting
3 Refer to ED drawings for mounting dimensions and heights. pedestals are not intended for such duty.
4 The 3-second rating is 25,000 amperes, RMS symmetrical. 0 Select mounting pedestal from table on page 17.
5 The one-time duty-cycle fault closing capability for a manually
operated switch when operated vigorously through its full travel without
hesitation at any point is 18,000 amperes, RMS, asymmetrical.
1 Switches do not include connectors (refer to table on page 20). 3 Applications indicated by symbols in parentheses are conditional.
2 The 3-second ratings for 600- and 1200-ampere switches are 25,000 Refer to “CONDITIONAL APPLICATIONS” table, page 5.
and 40,000 amperes, RMS symmetrical, respectively.
1 Intermediate heights [less than 12 feet (3658 mm)] are available in Note: Maximum available column height is 129-00 (3658 mm).
3-inch (76.2 mm) increments. Specify by adding one of the following 2 Each anchor bolt is of galvanized steel and is furnished with two hex
suffixes to the catalog number of the mounting pedestal of nearest nuts and two flat washers to facilitate leveling the mounting pedestals.
lower height.
-S3 Three inches (76 mm) additional height
3 Nominal size of anchor bolts is 1Z\v0 3 39-80 (32 mm 3 1118 mm).
-S6 Six inches (152 mm) additional height
-S9 Nine inches (228 mm) additional height
Less Pipe -P
CONNECTORS
Catalog Number
Illustration Description Accommodating Conductor For 600-Ampere For 1200-Ampere
Switches Switches1
For 600-Ampere Standard Bronze Pad Terminal, 1/0 solid (53.5 mm2) through 500 kc mil
4565R1-B —
Switches or Four-Bolt, Tin Plated. Includes (335 mm2) copper or aluminum
two Z\x–1331Z\x0 Galvanized Steel
Bolts for attachment to terminal 2/0 stranded (89 mm2) through 800 kc mil
pads of switches 4567R1-B 4568R1-B
(539 mm2) copper or aluminum
1 Side-Break Integer Style Switches rated 14.4 kV, 1200 amperes and _ Mechanical interference with blade prevents use on single-pole
25 kV, 1200 amperes include two-hole terminal pads as standard. If four- heavy-duty style switches.
bolt connectors are required, specify the two-to-four bolt adapter Catalog d When used with aluminum compression connectors, switch terminal
Number MDA-1162-1 and the four-bolt connector Catalog Number pads should be tin plated. See “SPECIFICATION DEVIATIONS” on page 2.
4569R1-B.
1 Previous designs of Three-Pole Side-Break Heavy-Duty Style Number Supplements “R8” or lower) require Catalog Number 4551R2
switches (all those rated 400 amperes and all those bearing Catalog (7.2 kV) or 4552R4 (14.4 kV) interrupters. Contact your nearest S&C
Number Supplements “R1” or “R2” or no supplements, except those Sales Office.
rated 23 kV) require Catalog Number SA-30817R2 or SA-30818R4 l Previous designs of Three-Pole Double-Break Style switches (all those
(single-bolt) interrupters. bearing Catalog Number Supplement “-R9”) require interrupter Catalog
d Previous designs of 1200-ampere Three-Pole Vertical-Break Style Number 4559R1. Contact your nearest S&C Sales Office.
and 1200-ampere single-pole switches (all those bearing Catalog
Dimensions in inches
Rating
Net Wt., 3-Pole
Catalog Number Dimensions in Inches (to nearest Z\,0)
Assem., Lbs.
kV Amperes, RMS
Mounting Mounting Applications
Configura- Arrange- Cypoxy Porcelain (see pages
tion ments Cypoxy Porcelain Station Station 4 and 5)
Nom. Max BIL Cont. Mom. Station Post Station Post Aw B C D E F Kw U Post Post
(Asym.) Insulators Insulators Insula- Insula-
tors tors
14.4 17.0 110 1200 40 000 137612R6-E 137612R6 21 18C\v 106 34 20Z\, 23M\, — 45 288 330 AEGHK(L)
Vertical ED-140R20
25 27 150 1200 40 000 137613R9-E 137613R9 25 22C\v 120 40 23Z\, 26M\, — 53 309 390 AE(GHKL)
Clockwise
Opening
Steel
25/34.5 38 150 600 40 000 137167R1-E 137167R1 — 26Z\v 129 48 28 31B\, 29Z\x 53 419 500 AEGHKL
Base ED-672R4
34.5 38 200 600 40 000 137164R1-E 137164R1 — 30Z\v 129 48 28 31B\, 33Z\x 53 456 570 AEGHKL
14.4 17.0 110 1200 40 000 137192R2-E 137192R2 22C\, 20 91 34 20Z\, 23M\, — 36 308 350 AEGHK(L)
Vertical ED-640R4
25 27 150 1200 40 000 137193R9-E 137193R9 26C\, 24 103 40 23Z\, 26M\, — 41 344 425 AE(GHKL)
Clockwise
Opening
Insulated
Base ED-642R4 34.5 38 200 600 40 000 137194R1-E 137194R1 — 31Z\v 129 48 28 31B\, 34Z\x 53 486 600 AEGHKL
w Dimension shown specifies the distance from the switch base to the
outermost projection of the switch.
Dimensions in inches
Rating
Net Wt., 3-Pole
Catalog Number Dimensions in Inches (to nearest Z\,0)
Assem., Lbs.
kV Amperes, RMS
Mounting Applications
Mounting Cypoxy Porcelain
Arrange- (see pages
Configuration Cypoxy Porcelain Station Station
ments 4 and 5)
Nom. Max BIL Cont. Mom. Station Post Station Post Aw B C D H U Post Post
(Asym.) Insulators Insulators Insula- Insula-
tors tors
Upright 14.4 17.0 110 1200 40 000 137412R8-E 137412R8 21Z\v 18M\, 106 34 15 45 308 350 AEGHK(L)
Clockwise Opening ED-136R20
Steel Base 25 27 150 1200 40 000 137413R9-E 137413R9 25Z\x 23 120 40 15 53 329 410 AE(GHKL)
Upright
Clockwise Opening 14.4 17.0 110 1200 40 000 138412R2-E 138412R2 21Z\v 18M\, 128 34 24 58 333 375 AEGHK(L)
(Extra Mounting-Pole ED-136R20
Clearance) 25 27 150 1200 40 000 138413R2-E 138413R2 25Z\x 23 128 40 24 52 339 420 AE(GHKL)
Steel Base
Upright
Counterclockwise 14.4 17.0 110 1200 40 000 137512R8-E 137512R8 21Z\v 18M\, 106 34 15 45 308 350 AEGHK(L)
ED-135R20
Opening 25 27 150 1200 40 000 137513R9-E 137513R9 25Z\x 23 120 40 15 53 329 410 AE(GHKL)
Steel Base
Upright 14.4 17.0 110 1200 40 000 137392R2-E 137392R2 22C\, 20 91 34 15 36 323 365 AEGHK(L)
Clockwise Opening ED-636R4
Insulated Base 25 27 150 1200 40 000 137393R9-E 137393R9 26C\, 24 103 40 15 41 359 440 AE(GHKL)
Upright
Clockwise Opening 14.4 17.0 110 1200 40 000 138392R2-E 138392R2 22C\, 20 117 34 24 52 338 380 AEGHK(L)
(Extra Mounting-Pole ED-636R4
Clearance) 25 27 150 1200 40 000 138393R2-E 138393R2 26C\, 24 129 40 24 54 374 455 AE(GHKL)
Insulated Base
Upright
Counterclockwise 14.4 17.0 110 1200 40 000 137492R2-E 137492R2 22C\, 20 91 34 15 36 323 365 AEGHK(L)
ED-635R4
Opening 25 27 150 1200 40 000 137493R9-E 137493R9 26C\, 24 103 40 15 41 359 440 AE(GHKL)
Insulated Base
w Dimension shown specifies the distance from the switch base to the
outermost projection of the switch.
Dimensions in inches
Rating Dimensions
Net Wt., 3-Pole
Fault- Catalog Number in Inches
kV Amperes, RMS Assem., Lbs.
Closing, (to nearest Z\,0)
Mounting Duty-Cycle, Applications
Mounting
Arrange- One-Time; Cypoxy Porcelain (see pages
Configuration
ments Amperes,� Cypoxy Porcelain Station Station 4 and 5)
Nom. Max BIL Cont. Mom. Station Post Station Post B Kw Post Post
RMS
(Asym.) Insulators Insulators Insula- Insula-
Asym.
tors tors
Upright 25/34.5 38 150 600 40 000 15 000 137367R3-E 137367R3 26Z\v 29Z\x 404 485 AEGHKL
Clockwise Opening ED-667R3
Steel Base 34.5 38 200 600 40 000 15 000 137364R3-E 137364R3 30Z\v 33Z\x 441 555 AEGHKL
Upright
Counterclockwise 25/34.5 38 150 600 40 000 15 000 137467R3-E 137467R3 26Z\v 29Z\x 404 485 AEGHKL
ED-669R3
Opening 34.5 38 200 600 40 000 15 000 137464R3-E 137464R3 30Z\v 33Z\x 441 555 AEGHKL
Steel Base
Upright
Clockwise Opening ED-637R3 34.5 38 200 600 40 000 15 000 137394R1-E 137394R1 31Z\v 34Z\x 461 575 AEGHKL
Insulated Base
Upright
Counterclockwise
ED-639R3 34.5 38 200 600 40 000 15 000 137494R1-E 137494R1 31Z\v 34Z\x 461 575 AEGHKL
Opening
Insulated Base
w Dimension shown specifies the distance from the switch base to the
outermost projection of the switch.
Dimensions in inches
4⁹⁄₃₂
Rating
Net Wt., 3-Pole
Catalog Number Dimensions in Inches (to nearest Z\,0)
Assem., Lbs.
kV Amperes, RMS
Mounting Mounting Applications
Configura- Arrange- Cypoxy Porcelain (see pages
tion ments Cypoxy Porcelain Station Station 4 and 5)
Nom. Max BIL Cont. Mom. Station Post Station Post Aw B C D E F Kw Post Post
(Asym.) Insulators Insulators Insula- Insula-
tors tors
14.4 17.0 110 1200 40 000 137812R7-E 137812R7 21Z\, 18C\v 107M\, 40 20Z\, 23M\, — 328 370 AEGHK(L)
Tiered ED-144R18
25 27 150 1200 40 000 137813R9-E 137813R9 25C\, 22M\, 119M\, 46 23Z\, 26M\, — 344 425 AE(GHKL)
Outboard
Clockwise
Opening
25/34.5 38 150 600 40 000 137767R3-E 137767R3 — 26Z\, 123M\, 48 28 31B\, 29C\, 404 485 AEGHKL
Steel Base ED-676R3
34.5 38 200 600 40 000 137764R3-E 137764R3 — 30Z\, 123M\, 48 28 31B\, 33C\, 431 545 AEGHKL
Tiered
Outboard
Clockwise 14.4 17.0 110 1200 40 000 137792R2-E 137792R2 22C\, 20 107M\, 40 20Z\, 23M\, — 338 380 AEGHK(L)
ED-644R1
Opening 25 27 150 1200 40 000 137793R9-E 137793R9 26C\, 24 119M\, 46 23Z\, 26M\, — 364 445 AE(GHKL)
Insulated
Base
w Dimension shown specifies the distance from the switch base to the
outermost projection of the switch.
Dimensions in inches
14.4 kV
25 kV
Rating
Net Wt., 3-Pole
Catalog Number Dimensions in Inches (to nearest Z\,0)
Assem., Lbs.
kV Amperes, RMS
Mounting Applications
Opening
Configura- Cypoxy Porcelain (see pages
Direction
tion Cypoxy Porcelain Station Station 4 and 5)
Nom. Max BIL Cont. Mom. Station Post Station Post A B C D F G L M R Post Post
(Asym.) Insulators Insulators Insula- Insula-
tors tors
14.4 17.0 110 600 40 000 137012R3-E 137012R3 19B\, 10 34 4C\v 18Z\, 13 30 20Z\, 21B\, 84 98 AEGHK(L)
Clockwise
Vertical, 25 27 150 600 40 000 137013R7-E 137013R7 23Z\x 14 39Z\, 6M\, 21Z\, 18 35 23Z\, 25B\, 101 128 AEG(HKL)
Upright, or
Triangular
Upright Counter- 14.4 17.0 110 600 40 000 137212R3-E 137212R3 19B\, 10 34 4C\v 18Z\x 13 30 20Z\, 21B\, 84 98 AEGHK(L)
clockwise 25 27 150 600 40 000 137213R7-E 137213R7 23Z\x 14 39Z\, 6M\, 21Z\x 18 35 23Z\, 25B\, 101 128 AEG(HKL)
Dimensions in inches
Rating
Catalog Number Net Wt., per Pole, Lbs.
kV Amperes, RMS Applications
Mounting Opening
(see pages
Configuration Direction
Cypoxy Porcelain Cypoxy Porcelain 4 and 5)
Mom.
Nom. Max BIL Cont. (Asym.) Station Post Station Post Station Post Station Post
Insulators Insulators Insulators Insulators
Clockwise 34.5 38 200 600 40 000 138114R1-E 138114R1 120 158 AEGHKL
Upright
Counter-
34.5 38 200 600 40 000 138314R1-E 138314R1 120 158 AEGHKL
clockwise
Dimensions in inches
14.4 kV
Rating
Catalog Number Net Wt., per Pole, Lbs.
Mounting Mounting kV Amperes, RMS Applications
Opening
Configu- Arrange- (see pages
Direction Cypoxy Porcelain Cypoxy Porcelain
ration ments Mom. 4 and 5)
Nom. Max BIL Cont. Station Post Station Post Station Post Station Post
(Asym.)
Insulators Insulators Insulators Insulators
Dimensions in inches
³⁄₄ ³⁄₈
78¹⁄₂
⁵⁄₈ 1³⁄₄
4¹⁄₁₆ 1³⁄₄ 1³⁄₄ ⁵⁄₈
8¹⁄₈
3 2
8¹⁄₂ ⁵⁄₈
⁹⁄₁₆ DIA. ⁹⁄₁₆ DIA. HOLES (2)
³⁄₄ DIA. HOLES (2) ³⁄₄ DIA. HOLES (2) HOLES (4)
1200 Ampere 600 Ampere
34.5 38 200 600 40 000 20 000 135714R2-E 135714R2 451 565 AEGHKL
Pedestal ED-151R1
34.5 38 200 1200 40 000 30 000 135914R2-E 135914R2 451 565 AE(G)HKL
Dimensions in inches
34.5 38 200 600 40 000 20 000 135724R2-E 135724R2 446 560 AEGHKL
Pole-Top ED-152R3
34.5 38 200 1200 40 000 30 000 135924R2-E 135924R2 446 560 AE(G)HKL
Dimensions in inches
34.5 38 200 600 40 000 20 000 135734R2-E 135734R2 496 610 AEGHKL
Upright ED-153R5
34.5 38 200 1200 40 000 30 000 135934R2-E 135934R2 496 610 AE(G)HKL
Dimensions in inches
34.5 38 200 600 40 000 20 000 135744R2-E 135744R2 461 575 AEGHKL
Vertical ED-154R5
34.5 38 200 1200 40 000 30 000 135944R2-E 135944R2 461 575 AE(G)HKL
Dimensions in inches
Tiered 34.5 38 200 600 40 000 20 000 135754R2-E 135754R2 476 590 AEGHKL
ED-155R6
Outboard 34.5 38 200 1200 40 000 30 000 135954R2-E 135954R2 476 590 AE(G)HKL
Dimensions in inches
Triangular ED-156R5 34.5 38 200 600 40 000 20 000 135764R2-E 135764R2 496 610 AEGHKL
Dimensions in inches
Rating
Net Wt., per
Catalog Number Dimensions in Inches (to nearest Z\,0)
Pole., Lbs.
kV Amperes, RMS
Applications
Mounting
Cypoxy Porcelain (see pages
Configuration
Cypoxy Porcelain Station Station 4 and 5)
Nom. Max BIL Cont. Mom. Station Post Station Post A1 A2 B F H K L M R Post Post
(Asym.) Insulators Insulators Insula- Insula-
tors tors
14.4 17.0 110 600 40 000 135012R4-E 135012R4 15B\, 16Z\v 10 18Z\x 13C\v 2 4Z\x 38C\, 26B\, 120 141 AEGHK(L)
Vertical or
14.4 17.0 110 1200 61 000 320222R9-E 320222R9 15Z\x 16M\, 10 19C\, 11 2Z\v 4M\, 39C\v 25Z\x 163 184 AEGHK(L)
Upright
25 27 150 600 40 000 135013R5-E 135013R5 19M\, 20Z\x 14 22Z\x 13C\v 2Z\v 4Z\x 47Z\v 31 161 201 AEG(HKL)
Dimensions in inches
Vertical 34.5 38 200 600 40 000 135794R2-E 135794R2 29Z\v 18 61 32B\, 43 132 170 AEGHKL
34.5 38 200 1200 40 000 135994R2-E 135994R2 29Z\v 18 61 32B\, 43 132 170 AE(G)HKL
25/34.5 38 150 1200 40 000 135874R2-E 135874R2 25Z\v 14 57 28B\, 39 123 150 AE(G)HKL
Upright 34.5 38 200 600 40 000 135774R2-E 135774R2 29Z\v 18 61 32B\, 43 132 170 AEGHKL
34.5 38 200 1200 40 000 135974R2-E 135974R2 29Z\v 18 61 32B\, 43 132 170 AE(G)HKL
Dimensions in inches
R
10
Dimensions in inches (mm) A
2Z\v
1Z\x B
8Z\v
[ >\zn
HOLES (20)
ON 10
CTRS.
F E 1B\,
C L
10
F
J
B\,
1C\v
6 5Z\v
B\,
[ >\zn 3 1>\zn 2
1Z\x SLOTS (4) >\zn DIA. HOLES (2)
BASE DETAIL TERMINAL PAD DETAIL
Dimensions in inches
178Z\x
148
60 24 48 54Z\x
23Z\v
6
22 38C\zn
[ 2Z\v 30C\zn
7Z\x
1
6
1Z\x
144 2Z\x M\, 15
M\, 18
2 1C\v
POLE SADDLE DETAIL 1 20
2
M\,
>\zn DIA. HOLES (2) B\,
10 10
TERMINAL PAD DRILLING
BASE DETAIL
Upright ED-160R1 46 48.3 250 600 40 000 18 000 320335-E 320335 1080 1080 AEG(KL)
Dimensions in inches
142Z\x
108
6 48 48
R 23Z\v
2
2C\zn
54Z\x
2
22
7Z\x
M\, 30C\zn
38C\zn
POLE SADDLE DETAIL 2Z\v
1
1C\v
M\, 2
>\zn DIA. HOLES (2)
10 10 B\,
BASE DETAIL
TERMINAL PAD DRILLING
Vertical ED-161 46 48.3 250 600 40 000 18 000 320345-E 320345 980 980 AEG(KL)
Dimensions in inches
3Z\x
ZC\zn
6 23Z\v
[ 2Z\v
54Z\x
20
POLE BAND
MOUNTING
BRACKETS (4)
38C\zn
120 22
66 30C\zn
90 148
144 7Z\x
178Z\x
5Z\v
Z\x
66 1C\v
2
12
Tiered
ED-162 46 48.3 250 600 40 000 18 000 320355-E 320355 1050 1050 AEG(KL)
Outboard
Dimensions in inches
142Z\x
112
48 48 54Z\x
23Z\v
38C\zn
22
12 30C\zn
2B\,
7Z\x
6
108 2Z\x
1C\v
C\v DIA.
HOLES (2)
5Z\v 2
10Z\x
Pole-Top ED-163R1 46 48.3 250 600 40 000 18 000 320365-E 320365 980 980 AEG(KL)
Dimensions in inches
142Z\x
112
48 48
54Z\x
23Z\v
12 22 38C\zn
30C\zn
2B\,
7Z\x
6 C\,
108
1C\v
C\v DIA. HOLES (4)
5Z\v
2
10Z\x
7 >\zn DIA.
B\,
HOLES (2)
14
Pedestal ED-164R1 46 48.3 250 600 40 000 18 000 320375-E 320375 970 970 AEG(KL)
Dimensions in inches
Rating
Net Wt., per
Catalog Number Dimensions in Inches (to nearest Z\,0)
Pole, Lbs.
kV Amperes, RMS
Mounting Applications
Configura- Cypoxy Porcelain (see pages
tion Cypoxy Porcelain Station Station 4 and 5)
Nom. Max BIL Cont. Mom. Station Post Station Post A B C D F G H L M R Post Post
(Asym.) Insulators Insulators Insula- Insula-
tors tors
14.4 17.0 110 600 40 000 136012-E 136012 12B\, 10 28 4C\v 18Z\x 15 — 25 40C\v 23C\v 62 76 AEGHK(L)
14.4 17.0 110 1200 61 000 320022R9-E 320022R9 13Z\v 10 28 4C\, 19C\, 19 11 25 43 23C\, 93 107 AEGHK(L)
Vertical
25 27 150 600 40 000 136013R1-E 136013R1 16B\, 14 30 4C\v 20Z\x 17 — 27 47 27M\, 74 101 AEG(HKL)
25 27 150 1200 61 000 320023R10-E 320023R10 17Z\v 14 32C\v 5B\, 21B\, 23C\v 13C\, 29C\v 50C\, 28B\, 104 131 AE(GHKL)
14.4 17.0 110 600 40 000 136112R5-E 136112R5 12B\, 10 28 4C\v 18Z\x 15 — 25 40C\v 23C\v 62 76 AEGHK(L)
14.4 17.0 110 1200 61 000 320122R9-E 320122R9 13Z\v 10 28 4C\, 19C\, 19 11 25 43 23C\, 93 107 AEGHK(L)
Inverted
25 27 150 600 40 000 136113R1-E 136113R1 16B\, 14 30 4C\v 20Z\x 17 — 27 47 27M\, 74 101 AEG(HKL)
25 27 150 1200 61 000 320123R10-E 320123R10 17Z\v 14 32C\v 5B\, 21B\, 23C\v 13C\, 29C\v 50C\, 28B\, 104 131 AE(GHKL)