Anda di halaman 1dari 12

PERSYARATAN PENEMPATAN

APAR MENURUT NFPA


(NATIONAL FIRE PROTECTION
ASSOCIATION) disertai CONTOH
SOAL DAN JAWABANNYA

Ach. Lukman Chakim, ST

FIRE PROTECTION EQUIPMENT


Refilling & Testing
Ref. : Peraturan Menteri Tenaga Kerja
No. Per 04/Men/1980

Jenis Refilling Testing

Water 5 th 5 th

Mechanical Foam 3 th 5 th

Chemical Foam 2 th 5 th

Dry powder 5 th 5 th
Halogen 5 th 5 th

CO2 5-10 th 10-5-5 th


TABEL-1
PERSYARATAN UKURAN DAN
PENEMPATAN UTK BAHAYA KLAS A
URAIAN HUNIAN BAHAYA HUNIAN BAHAYA HUNIAN
RINGAN SEDANG BAHAYA
BERAT
APAR tunggal rating 2A 2A 4A
minimal
Luas lantai maksimum per 300 m2 150 m2 100 m2
unit APAR

Luas lantai maks per unit 1050 m2 1050 m2 1050 m2


APAR

Jarak tempuh maks ke APAR 22,5 m 22,5 m 22,5 m


Table 3.2.1.
Fire Extinguisher Size and Placement for Class A Hazards
Table 3.3.1
Fire Extinguisher Size and Placement for Class B Hazards
TABEL-2 LUAS AREA MAKSIMUM YG
DIPROTEKSI PER UNIT APAR (M2)
RATING KLAS A BAHAYA RINGAN BAHAYA SEDANG BAHAYA BERAT

1A 300 150 100


2A 600 300 200
3A 900 450 300
4A 1050 550 400
6A 1050 900 550
10A 1050 1050 1000
20A 1050 1050 1050
30A 1050 1050 1050
40A 1050 1050 1050
TABEL-3 PERSYARATAN UKURAN DAN
PENEMPATAN UNTUK BAHAYA KLAS B
JENIS BAHAYA RATING PEMADAM JARAK TEMPUH
MIN SBG DASAR MAX KE APAR
RINGAN 5B 9,15 m
10B 15,25 m
SEDANG 10B 9,15 m
20B 15,25 m
BERAT 40B 9,15 m
80B 15,25 m
TABEL-4 PERSYARATAN UNTUK
KLAS C DAN D

KLAS C / listrik KLAS D / combustible


bermuatan metal
CO2
Dry-chemical Dry chemical
Halon
TABEL-5 PEMADAM EFEKTIF
KLAS A KLAS B KLAS C KLAS D KLAS K

Basis air Busa CO2 Dry chemical Kimia basah

Busa / foam CO2 Dry Dry Dry


chemical chemical(multi chemical
(multi purpose) purpose) (multi purpose)

CO2 Dry hemical Halon

Dry
chemical
Halon
TABEL-6 HYDROSTATIC TEST
TIPE APAR INTERVAL UJI (Tahun)
APAR basis air 5
Bahan basah (wet agent) 5
Busa (AFFF, FFFF) 5
Dry chemical (stainless steel sheet) 5
CO2 5
Kimia basah 5
Dry chemical (stored pressure) 12
Dry chemical (cartridge) 12
Halogen/ halon 12
Dry powder (stored, cartridge) 12
CONTOH CONTOH SOAL
1. Suatu ruangan berukuran 6271 m2 2. Dengan ukuran ruangan
(67.500 ft2) Dinding penutupnya tersebut tentukan jumlah
berukuran 45,7 x 137,2 m (150 x
450 ft). Tentukan jumlah minimal minimum APAR Klas A
APAR yang harus dipasang utk apabila APAR dengan luas
bahaya kebakaran Klas A jangkauan 550 m2 yang
digunakan.
Jawab : Menurut Tabel-1 luas lantai
maks per unit APAR adalah 1050 Jawab : Jml APAR = luas total
m2. Maka luas lantai total : luas lantai /luas jangkau per unit
lantai maks per APAR = 6271 / 1050 APAR = 6271 / 550 = 12 unit
= 6 APAR. Mengacu ke Tabel-2 ,
APAR. Dari Tabel-2 maka
maka diperlukan min rating 4A untuk
bahaya ringan, rating 10A untuk jangkauan 550 m2 dipenuhi
bahaya sedang dan rating 20A untuk oleh minimal APAR rating 2A
bahaya berat. untuk baha-ya ringan, rating
Namun penempatan pada dinding ku- 4A untuk bahaya sedang dan
rang pas karena jarak jangkau ada rating 6A untuk bahaya berat.
yg melebihi 22,5 m  hrs ditambah Penempatan pd dinding meme
nuhi distribusi & jarak jangkau
PENEMPATAN APAR

Konfigurasi soal no-1

Konfigurasi soal no-2

Anda mungkin juga menyukai