PWM 10 & 20 CHECK LIST
THESE READINGS ARE FOR UNITS USING
A 7967-400-5010 OR 42210-4 HEATSINK ONLY

TRANSFORMER
AC INPUT 600 OR 480 OR 240 VAC 3 PHASE
AC OUTPUT TO PWM 186 VAC -5% NO + %
(BE SURE TAPS ARE SET FOR PROPER AC INPUT)

PWM CONTROL UNIT NORMAL


TB1 - 7 TO 8 181 TO 170 VAC
8 TO 9 181 TO 170 VAC
9 TO 7 181 TO 170 VAC

TB1 - 2 TO 4 SET DC OUTPUT AT 230 VDC (3630 = 200 VDC)


(SEE CALIBRATION PROCEDURE) 7040-220 VDC
TB1 - ON PC BOARD TO DRILLERS CONTROL
TB1 - 1 TO 2 10 OHM 8 TO 10 VAC
3 TO 4 OFF 60 OHM 14 TO 20 VAC
3 TO 4 ON 1 TO 5.8 VAC

VERIFY THAT YOU HAVE PROPER READINGS AT PC TB-1 1-2-3-4.


POSITIVE TO NEGATIVE HEATSINK 220 TO 270 VDC
7040 & 7838 UNDER 60 AMPS AC PER LEG AT-TB-1 7-8-9
3630 & 5032 & 6032 UNDER 30 AMPS AC PER LEG AT TB-1 7-8-9

(TB-2 PC BOARD, ALL READINGS ARE DC VOLTAGE)

PWM-20 PWM-10

TB-2 5 TO 10 OFF 220 TO 260* NOT USED


ON 210 TO 250* NOT USED
6 TO 10 220 TO 260* 220 TO 260*
7 TO 10 OFF 7.0 TO 9.0 7.0 TO 9.0
11 TO 10 19 TO 21 19 TO 21
12 TO 10 OFF 220 TO 260* 220 TO 260*
ON 210 TO 250* 210 TO 250*

* IF READINGS ARE OVER OR UNDER, CHECK YOUR METER AND THE AC VOLTAGE INPUT TO
TRANSFORMERS.
FULL ON ADJ. R-19 5.8 VDC OFF ADJ. R-21 15.8 VDC

FOR ALL PROBLEMS WITH SYSTEM SEE PWM MAINTENANCE SERVICE MANUAL
OR CALL (520) 432-4746 OR (800) 520-5423.