Group / Parameter IED Value PC Value Unit Min Max


Name
GOPPDOP: 1
General
IBase 2062 A 1 99999
UBase 10.50 kV 0.05 2000.00
Mode L1L2
Setting Group1
Operation On
k 0.00 0.00 0.99
IAmpComp5 0.000 % -10.000 10.000
IAmpComp30 0.000 % -10.000 10.000
IAmpComp100 0.000 % -10.000 10.000
UAmpComp5 0.000 % -10.000 10.000
UAmpComp30 0.000 % -10.000 10.000
UAmpComp100 0.000 % -10.000 10.000
IAngComp5 0.000 Deg -10.000 10.000
IAngComp30 0.000 Deg -10.000 10.000
IAngComp100 0.000 Deg -10.000 10.000
Step 1
Setting Group1
OpMode1 OverPower
Power1 20.0 %SB 0.0 500.0
Angle1 0.0 Deg -180.0 180.0
TripDelay1 5.000 s 0.010 6000.000
DropDelay1 2.000 s 0.010 6000.000
Hysteresis1 0.5 pu 0.2 5.0
Step 2
Setting Group1
OpMode2 Off
Power2 2.0 %SB 0.0 500.0
Angle2 0.0 Deg -180.0 180.0
TripDelay2 2.000 s 0.010 6000.000
DropDelay2 1.000 s 0.010 6000.000
Hysteresis2 0.5 pu 0.2 5.0

Project Responsible department Technical ref... Document kind Doc. designation

PLTU GORONTALO UNIT 2 N... ABB Ltd. AA1J1Q01A1


Repla... Created by Title Document id.
REG670
PLTU GORONTALO UNIT 2
Approved by Rev. Rel. date Lan
NEW USE.Substation.Voltage
Re Rel. Created Based 1/1
v.
Modification
date by on Level.Bay 0 11/12/2018 en