CURRENT IN MULTIPLES OF Ir (Ir = LONG-TIME SETTING x In)

100
1.5

10

15

20

30

40

50

60
70
80
90
.5

.6
.7
.8
.9
1

6
7
8
9
10000 10000
9000 9000 MICROLOGIC® 5.0/6.0 A/P/H TRIP UNIT
8000
7000
8000
7000
CHARACTERISTIC TRIP CURVE NO. 613-5
6000 6000
Short-time Pickup and I2t ON Delay
5000 5000

4000 4000 The time-current curve information is to be used


for application and coordination purposes only.
3000 3000
Curves apply from -30°C to +60°C ambient
2000 2000 temperature.
1500 1500 Notes:
1. There is a thermal-imaging effect that can act
1000
1000
900 900
to shorten the long-time delay. The thermal-
800 800 imaging effect comes into play if a current
700 700
600 600
above the long-time delay pickup value exists
500 500 for a time and then is cleared by the tripping of
400 400
a downstream device or the circuit breaker
itself. A subsequent overload will cause the
300 300
circuit breaker to trip in a shorter time than
normal. The amount of time delay reduction is
200 200
inverse to the amount of time that has elapsed
150 150 since the previous overload. Approximately 20
minutes is required between overloads to
SHORT-TIME
100 PICKUP 100 completely reset thermal-imaging.
90 x Ir 90
80
70
1.5 2 2.5 6 8 10
80
70
2. The end of the curve is determined by the
60 60 interrupting rating of the circuit breaker.
50 50
3. With zone-selective interlocking on, short-time
40 40
delay utilized and no restraining signal, the
3 4 5
30 30 maximum unrestrained short-time delay time
band applies regardless of the setting.
20 20
4. Total clearing times shown include the
15 15 response times of the trip unit, the circuit
breaker opening, and the extinction of the
10 10 current.
9 9
8 8 5. For a withstand circuit breaker, instantaneous
7 7
6 6
can be turned OFF. See 613-7 for
TIME IN SECONDS

instantaneous trip curve. See 613-10 for


0.4

5 5
ON

4 4
instantaneous override values.
3 3
6. See 613-4 for long-time pickup and delay trip
0.2

curve.
ON

2 2
0.1

1.5 1.5
0.3
ON

ON

1 1
.9 .9
.8 .8
.7 .7
.6 .6

.5 .5

.4 0.4 ON .4
SHORT-TIME
.3
DELAY I2t ON .3
SECONDS AT 10 x Ir 0.3 ON
MAXIMUM
.2 .2
UNRESTRAINED
SHORT-TIME 0.2 ON
.15 DELAY .15

.1 0.1 ON .1
.09 .09
.08 .08
.07 .07
.06 .06

.05 .05

.04 .04

.03 .03

.02 .02

1 CYCLE
.015 .015

.01 .01
.009 .009
1
.008 2 CYCLE .008
.007 .007
.006 .006

.005 .005
1

1.5

6
7
8
9
10
.5

.6
.7
.8
.9

15

20

30

40

50

60
70
80
90
100

CURRENT IN MULTIPLES OF Ir
(Ir = LONG-TIME SETTING x In)

Curve No. 0613TC0005


December 2000
Schneider Electric Brands © 2000 Schneider Electric all rights reserved Drawing No. B48095-613-05