Anda di halaman 1dari 64

1 2 3 4 5 6 7 8

A
ABB Manufacturing Sdn. Bhd. A

(Company Number : 12651-M)


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

Lot 608, Jalan SS13/1K, 47500 Subang Jaya, Selangor Darul Ehsan, Malaysia.
Tel : +60 (3) 5628 4888, Telefax : +60 (3) 5631 2920

B B

Project Title : PLN WEST JAVA

Project No. : MY-04511274.A


C C

Customer : PT ABB SAKTI INDUSTRI

D D

E E
FOR APPROVAL
(Company Number: 210262-T)
KINDLY TICK THE FOLLOWING BOX:-
APPROVED

APPROVED WITH NOTES


NOTES TO BE MARKED IN RED
NOT APPROVED
Drawing No. : E12070JS ALL COMMENTS / CORRECTIONS TO BE MARKED IN RED
F ONE SET OF DRAWING TO BE STAMPED AND RETURNED F
WITHIN 2 WORKING WEEKS. NO MANUFACTURING
Substation : 24kV SWITCHGEAR SUBSTATION WORK WILL START BEFORE APPROVAL

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TABLE OF CONTENTS
PAGE NAME DRAWING NO. SHEET NO. REVISION
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A GENERAL DRAWINGS E12070JS ==SWG1=J00/A00 A0 A1 A


COVER SHEET
GENERAL DRAWINGS E12070JS ==SWG1=J00/B01 A0 A1
TABLE OF CONTENTS
GENERAL DRAWINGS E12070JS ==SWG1=J00/C01 A0 A1
TECHNICAL DATA
GENERAL DRAWINGS E12070JS ==SWG1=J00/C02 A0 A1
TECHNICAL DATA
GENERAL DRAWINGS E12070JS ==SWG1=J00/C03 A0 A1
ACCESSORIES STANDARD GUIDELINES
B GENERAL DRAWINGS E12070JS ==SWG1=J00+SLD/A01 A0 A1 B
SLD CUBICLES
GENERAL DRAWINGS E12070JS ==SWG1=J00+SLD/A02 A0 A1
SLD CUBICLES
GENERAL DRAWINGS E12070JS ==SWG1=J00+SLD/A03 A0 A1
SLD CUBICLES
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/D01 A0 A1
GENERAL ARRANGEMENT
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/D02 A0 A1
GENERAL ARRANGEMENT
C C
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/D03 A0 A1
GENERAL ARRANGEMENT
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/D04 A0 A1
PLAN VIEW
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/D06 A0 A1
DETAIL OF SWITCHGEAR INSTALLATION
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/D07 A0 A1
SECTIONAL VIEW
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/D09 A0 A1
D LV COMPARTMENT DOOR ARRANGEMENT D
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/E01 A0 A1
PANEL RATING LABEL
GENERAL DRAWINGS E12070JS ==SWG1=J00+GA/E02 A0 A1
NAME PLATE DETAILS

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA TABLE OF CONTENTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00/B01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. CATEGORY DESCRIPTION NO. CATEGORY DESCRIPTION


1 Switchgear Type: UniGear ZS1 7 Power cable Entry : Bottom
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A Application: Standard Maximum cable size : According to single line diagram A


Packing: Plywood Case with Vacuum Pack Terminating facility : Undrilled aluminium gland plate only,
3mm thickness
2 Switchgear Rated voltage: 24kV
system Service voltage: 20kV 8 Control cable Entry: Bottom front
Rated frequency: 50Hz
Rated power frequency withstand voltage: 50kV 9 Auxiliary circuit Voltage supply:
Rated lightning impulse withstand voltage: 125kV - Circuit breaker spring charge motor 110VDC
Rated short-time withstand current: 25kA 3sec - Protection, control & signaling 110VDC
Rated peak withstand current: 63kA - Panel heater & cubicle lighting 230VAC 50Hz
B B
Internal arc withstand current: 25kA 0.5sec
Internal arc classified: IAC AFLR 10 Wiring and Type: Standard
Loss of service classified: LSC2B terminal Rated voltage: 600/1000V
Partition class: PM specification Maximum service temperature: 70°C
Wire size:
3 Earthing switch Rated short time withstand current: 25kA 3sec - Auxiliary circuits of AC (single-phase) 1.5mm²
system Short circuit making capacity: 63kA - Auxiliary circuits of DC 1.5mm²
- Current circuits 4.0mm²
4 Busbar Main busbar rated current: 2000A Size: 2 x 80 x 10mm² Cu - Voltage circuits 2.5mm²
C Branch connection rated current: 2000A Size: 2 x 80 x 10mm² Cu - Earthing circuits 2.5/6mm² C
630A Size: 1 x 60 x 10mm² Cu Wire colour:
- Auxiliary circuits of AC (single-phase) Brown (L) & Blue (N)
Earth bar size: 1 x 30 x 8mm² Cu - Auxiliary circuits of DC Grey (+Ve) & Blue (-Ve)
Insulation (except earth bar): Raychem BPTM - Current circuits Red (L1), Yellow (L2), Black (L3) & Blue
Finishing: Bare copper (N)
Partitioning: None - Voltage circuits Red (L1), Yellow (L2), Black (L3) & Blue
(N)
5 Construction Standard: IEC 62271-200 - Earthing circuits Green/yellow
Type: Indoor, Metal Enclosed Terminal block: ABB Entrelec M4/6
D Material: Aluminium-zinc steel sheets Test terminal block: ABB Entrelec M6/8.ST1 D
Access location: Front access Cable termination: Blade
Switching device type: Withdrawable vacuum circuit breaker Cable marker: Hot marker
Cable tray: Self-extinguishing, warp proof PVC
Degree of protection - outer cover (IEC 60529): IP41
Degree of protection - inner partitions (IEC 60529): IP20 11 Serial Protocol: REF615 - IEC 103
Ambient temperature: -5°C to +40°C communication DPM - MODBUS RTU
Switchgear room height: 3.5<=H<4 Connection media: RS485
Gasduct: Compact Duct with Top Chimney
E Low voltage compartment internal support: Grid 12 Main label Colour: Black letter on white background E
Material: PVC traffolyte
6 Paint finish Doors and end covers colour: RAL7035 "light grey" Fixing: Internal - Self adhesive
Treatment: Standard External - Self adhesive

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA TECHNICAL DATA DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00/C01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

NO. CATEGORY DESCRIPTION NO. CATEGORY DESCRIPTION


13 Locks and Low voltage compartment doors closing version: Central lock
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A interlock Feeder compartment doors closing version: Central handle A


Apparatus compartment doors closing version: Central handle
Interlock between feeder compartment door and
earthing switch position: Mechanical
Interlock between apparatus compartment door and
apparatus position: Mechanical
Apparatus mechanical operating mechanism: Off
Lock on shutters: Padlockable
Lock on insertion of the apparatus racking in/out lever: Padlockable
Lock on insertion of the earthing switch lever: Padlockable
B B
Electromechanical lock on de-energisation (-RL3):
- Voltage supply 110VDC
- For panel with earthing switch All panels

14 Additional Mimic diagram: Yes


request Fault limiting device: None
Floor fixing: Expansion Bolts
Fail safe (lockable shutters): None
Feeder compartment inspection window: None
C Feeder compartment wire mesh: None C

15 Note Accessories standard guidelines refer to next sheet.

D D

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA TECHNICAL DATA DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00/C02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

ACCESSORIES STANDARD GUIDELINES


TYPE OF PART NO. OF PANELS/CB/VC OPTIONS FOR STANDARD SUPPLY OPTIONS FOR NON STD. SUPPLY
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
LOW VOLTAGE COMPARTMENT DOOR KEYS 3 AND BELOW 2 PCS PCS
4 AND ABOVE 3 PCS 5 PCS
CIRCUIT BREAKER RACKING HANDLE 3 AND BELOW 1 PC PCS
4 AND ABOVE 3 PCS 5 PCS
CHARGING HANDLE (CLASSIC DESIGN CIRCUIT BREAKER 3 AND BELOW 1 PC PCS
FROM ABB CALOR EMAG) 4 AND ABOVE 2 PCS PCS
VACUUM CONTACTOR FUSE PULLER 3 AND BELOW 1 PC PCS
4 AND ABOVE 3 PCS PCS
B B
VACUUM CONTACTOR EMERGENCY OPERATION LEVER 3 AND BELOW 1 PC PCS
4 AND ABOVE 3 PCS PCS
LOAD BREAK SWITCH HANDLE 3 AND BELOW 1 PC PCS
4 AND ABOVE 3 PCS PCS
INSTALLATION, SERVICE AND MAINTENANCE INSTRUCTION 3 AND BELOW 1 PC PCS
MANUAL (SWITCHGEAR AND SWITCHING DEVICES) 4 AND ABOVE 3 PCS 5 PCS
ISOFLEX LUBRICANT 1 SUBSTATION 1 TUB TUB
EARTH SWITCH HANDLE 1 SUBSTATION 1 PC 5 PCS
C C
CIRCUIT BREAKER SERVICE TROLLEY 1 SUBSTATION 1 UNIT FOR EACH SIZE OF BREAKER EA
CURRENT TEST PLUG 1 SUBSTATION 1 PC 5 PCS
VOLTAGE TEST PLUG 1 SUBSTATION 1 PC PCS
PROTECTION RELAY PROGRAMMING CABLE 1 SUBSTATION 2 PCS FOR EACH TYPE OF RELAY PCS
PROTECTION RELAY CONTROL KEYS 1 SUBSTATION 2 PCS PCS
PROTECTION RELAY PROTECTION KEYS 1 SUBSTATION 2 PCS PCS
UNIGEAR SINGLE END COVER 1 SUBSTATION 5 SET (LEFT & RIGHT) LEFT 5 RIGHT
TOUCH UP PAINT 1 SUBSTATION 100GM
D D
ARC DUCT & IP ROOF FOLLOW PROJECT ACCORDING TO GA & TDS
JUNCTION POINT SCREW FOR COUPLING FOLLOW PROJECT ACCORDING TO GA
BUSBARS FOLLOW PROJECT ACCORDING TO SL & TDS
POWER FUSE FOR LOAD BREAK SWITCH FOLLOW PROJECT ACCORDING TO SL
PT FUSE 3.15A (FIXED TYPE PT) FOLLOW PROJECT ACCORDING TO SL

OTHERS ACCESSORIES GUIDELINES


1) PROVISION FOR CONNECTION TO EXISTING PANEL MAIN BUSBAR ON LEFT SIDE. EXISTING PANEL WIDTH 1000MM
E E

GA : GENERAL ARRANGEMENT
SL : SINGLE LINE
TDS : TECHNICAL DATA SHEET

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA ACCESSORIES STANDARD GUIDELINES DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00/C03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: +SLD/A01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
3ph.AC, 50Hz, 20kV, 2000A, 25kA/3s BOGOR BARU SUBSTATION

=JA01 =JA02 =JA03 =JA04 =JA05


-QB -QB -QB -QB -QB
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25
A M M M M M A
24kV 24kV 24kV 24kV 24kV
630A 630A 630A 630A 630A
25kA/3s 25kA/3s 25kA/3s 25kA/3s 25kA/3s

3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1
REF615 REF615 REF615 REF615 REF615
CORE 1 CORE 1 CORE 1 CORE 1 CORE 1
50 51 50 51 50 51 50 51 50 51
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
15VA 15VA 15VA 15VA 15VA
(W) (W) (W) (W) (W)

INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A
B CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A B
CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5
15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A
(W) P2 (W) P2 (W) P2 (W) P2 (W) P2

-BU1,2,3 -BU1,2,3 -BU1,2,3 -BU1,2,3 -BU1,2,3


-QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10
EK6 WITH EK6 WITH EK6 WITH EK6 WITH EK6 WITH
BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION
MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS)
C OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER
C
NO.1 NO.2 NO.3 NO.4 NO.5

NOTE: ITEMS DENOTED WITH AN ASTERISK (*) WILL BE FREE ISSUED BY IDABB

3ph.AC, 50Hz, 20kV, 2000A, 25kA/3s TELUK JAMBE SUBSTATION

=JB01 =JB02 =JB03 =JB04 =JB05


-QB -QB -QB -QB -QB
VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.20.25
M 24kV M 24kV M 24kV M 24kV M 24kV
630A 630A 630A 630A 2000A
D 25kA/3s 25kA/3s 25kA/3s 25kA/3s 25kA/3s D

3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x2000/5/5A
P1
REF615 REF615 REF615 REF615 REF615
CORE 1 CORE 1 CORE 1 CORE 1 CORE 1
50 51 50 51 50 51 50 51 50 51
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
15VA 15VA 15VA 15VA 15VA
(W) (W) (W) (W) (W)

INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA


CORE 2 CORE 2 CORE 2 CORE 2 CORE 2 0-2000A/4000A
*EDMI 1630 0-800A/1600A *EDMI 1630 0-800A/1600A *EDMI 1630 0-800A/1600A *EDMI 1630 0-800A/1600A 1630
CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5
15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA DPM A A A
(W) P2 (W) P2 (W) P2 (W) P2 (W) P2
E E

-BU1,2,3 -BU1,2,3 -BU1,2,3 -BU1,2,3 -BU1,2,3


-QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10
EK6 WITH EK6 WITH EK6 WITH EK6 WITH EK6 WITH
BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION
MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS)
OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER
BUS SECTION
NO.1 NO.2 NO.3 NO.4

F NOTE: ITEMS DENOTED WITH AN ASTERISK (*) WILL BE FREE ISSUED BY IDABB F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SLD CUBICLES DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+SLD/A01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: A02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
3ph.AC, 50Hz, 20kV, 2000A, 25kA/3s GARUT SUBSTATION

=JC01 =JC02 =JC03 =JC04 =JC05


-QB -QB -QB -QB -QB
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.20.25
A M M M M M A
24kV 24kV 24kV 24kV 24kV
630A 630A 630A 630A 2000A
25kA/3s 25kA/3s 25kA/3s 25kA/3s 25kA/3s

3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x2000/5/5A
P1
REF615 REF615 REF615 REF615 REF615
CORE 1 CORE 1 CORE 1 CORE 1 CORE 1
50 51 50 51 50 51 50 51 50 51
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
15VA 15VA 15VA 15VA 15VA
(W) (W) (W) (W) (W)

INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-2000A/4000A
B CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A CORE 2 1630 B
CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5
15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA DPM A A A
(W) P2 (W) P2 (W) P2 (W) P2 (W) P2

-BU1,2,3 -BU1,2,3 -BU1,2,3 -BU1,2,3 -BU1,2,3


-QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10
EK6 WITH EK6 WITH EK6 WITH EK6 WITH EK6 WITH
BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION
MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS)
C OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER
C
BUS SECTION
NO.1 NO.2 NO.3 NO.4

NOTE: ITEMS DENOTED WITH AN ASTERISK (*) WILL BE FREE ISSUED BY IDABB

3ph.AC, 50Hz, 20kV, 2000A, 25kA/3s CIAMIS SUBSTATION

=JD01 =JD02 =JD03 =JD04


-QB -QB -QB -QB
VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.20.25
M 24kV M 24kV M 24kV M 24kV
630A 630A 630A 2000A
D 25kA/3s 25kA/3s 25kA/3s 25kA/3s D

3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x2000/5/5A
P1
REF615 REF615 REF615 REF615
CORE 1 CORE 1 CORE 1 CORE 1
50 51 50 51 50 51 50 51
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
15VA 15VA 15VA 15VA
(W) (W) (W) (W)

INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA


CORE 2 CORE 2 CORE 2 CORE 2 0-2000A/4000A
*EDMI 1630 0-800A/1600A *EDMI 1630 0-800A/1600A *EDMI 1630 0-800A/1600A 1630
CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5
15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA DPM A A A
(W) P2 (W) P2 (W) P2 (W) P2
E E

-BU1,2,3 -BU1,2,3 -BU1,2,3 -BU1,2,3


-QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10
EK6 WITH EK6 WITH EK6 WITH EK6 WITH
BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION
MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS)
OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER
BUS SECTION
NO.1 NO.2 NO.3

F NOTE: ITEMS DENOTED WITH AN ASTERISK (*) WILL BE FREE ISSUED BY IDABB F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SLD CUBICLES DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+SLD/A02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: A03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
3ph.AC, 50Hz, 20kV, 2000A, 25kA/3s PAMEUNGPEUK SUBSTATION

=JE01 =JE02 =JE03 =JE04


-QB -QB -QB -QB
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.06.25 VD4/P 24.20.25


A M M M M A
24kV 24kV 24kV 24kV
630A 630A 630A 2000A
25kA/3s 25kA/3s 25kA/3s 25kA/3s

3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x400-800/5/5A
P1 3x2000/5/5A
P1
REF615 REF615 REF615 REF615
CORE 1 CORE 1 CORE 1 CORE 1
50 51 50 51 50 51 50 51
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
CL.5P20 TTA 79
15VA 15VA 15VA 15VA
(W) (W) (W) (W)

INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-400A/800A INTEGRA 0-2000A/4000A


B CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A CORE 2 *EDMI 1630 0-800A/1600A CORE 2 1630 B
CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5 CL 0.5, Fs5
15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA kWH DPM A A A 15VA
TTA DPM A A A
(W) P2 (W) P2 (W) P2 (W) P2

-BU1,2,3 -BU1,2,3 -BU1,2,3 -BU1,2,3


-QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10 -QE F10-CI-10
EK6 WITH EK6 WITH EK6 WITH EK6 WITH
BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION BLOCKING CABLE TERMINATION
MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS) MAGNET (BY OTHERS)
C OUTGOING FEEDER OUTGOING FEEDER OUTGOING FEEDER
C
BUS SECTION
NO.1 NO.2 NO.3

NOTE: ITEMS DENOTED WITH AN ASTERISK (*) WILL BE FREE ISSUED BY IDABB

D D

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SLD CUBICLES DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+SLD/A03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: +GA/D01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

4056 mm 4256 mm

B B

NP1 NP1 NP1 NP1 NP1 NP1 NP1 NP1 NP1 NP1
2530 mm

2530 mm
2325 mm

2325 mm
W W W W W W W W W W

11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 13
11 11 12

C C

28 mm 800 mm 800 mm 800 mm 800 mm 800 mm 28 mm 28 mm 800 mm 800 mm 800 mm 800 mm 1000 mm 28 mm

PANEL NO. =JA01 =JA02 =JA03 =JA04 =JA05 PANEL NO. =JB01 =JB02 =JB03 =JB04 =JB05

PANEL NAME OUTGOING OUTGOING OUTGOING OUTGOING OUTGOING PANEL NAME OUTGOING OUTGOING OUTGOING OUTGOING BUS
FEEDER NO.1 FEEDER NO.2 FEEDER NO.3 FEEDER NO.4 FEEDER NO.5 FEEDER NO.1 FEEDER NO.2 FEEDER NO.3 FEEDER NO.4 SECTION
CIRCUIT 630A 630A 630A 630A 630A CIRCUIT 630A 630A 630A 630A 2000A
BREAKER 25kA VD4 25kA VD4 25kA VD4 25kA VD4 25kA VD4 BREAKER 25kA VD4 25kA VD4 25kA VD4 25kA VD4 25kA VD4
D D

FRONT FRONT
PANEL DEPTH : 1700mm PANEL DEPTH : 1700mm

BOGOR BARU SUBSTATION TELUK JAMBE SUBSTATION

E E
LEGEND:
11 GUIDING HOLE FOR CB
12 OPENING FOR EARTH SWITCH AND INDICATOR
13 OPENING FOR RACKING IN & RACKING OUT OF CIRCUIT BREAKER
NP1 NAME PLATE
W VIEWING WINDOW

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 30
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA GENERAL ARRANGEMENT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/D01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: D02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

4256 mm 3456 mm

B B

NP1 NP1 NP1 NP1 NP1 NP1 NP1 NP1 NP1


2530 mm

2530 mm
2325 mm

2325 mm
W W W W W W W W W

11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12 11 13 11 12
13 13
11 11 12 11 11 12

C C

28 mm 800 mm 800 mm 800 mm 800 mm 1000 mm 28 mm 28 mm 800 mm 800 mm 800 mm 1000 mm 28 mm

PANEL NO. =JC01 =JC02 =JC03 =JC04 =JC05 PANEL NO. =JD01 =JD02 =JD03 =JD04

PANEL NAME OUTGOING OUTGOING OUTGOING OUTGOING BUS PANEL NAME OUTGOING OUTGOING OUTGOING BUS
FEEDER NO.1 FEEDER NO.2 FEEDER NO.3 FEEDER NO.4 SECTION FEEDER NO.1 FEEDER NO.2 FEEDER NO.3 SECTION
CIRCUIT 630A 630A 630A 630A 2000A CIRCUIT 630A 630A 630A 2000A
BREAKER 25kA VD4 25kA VD4 25kA VD4 25kA VD4 25kA VD4 BREAKER 25kA VD4 25kA VD4 25kA VD4 25kA VD4
D D

FRONT FRONT
PANEL DEPTH : 1700mm PANEL DEPTH : 1700mm
GARUT SUBSTATION CIAMIS SUBSTATION

E E
LEGEND:
11 GUIDING HOLE FOR CB
12 OPENING FOR EARTH SWITCH AND INDICATOR
13 OPENING FOR RACKING IN & RACKING OUT OF CIRCUIT BREAKER
NP1 NAME PLATE
W VIEWING WINDOW

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 30
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA GENERAL ARRANGEMENT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/D02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: D03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

3456 mm

B B

NP1 NP1 NP1 NP1


2530 mm

2325 mm

2325 mm
W W W W

11 13 11 12 11 13 11 12 11 13 11 12 13
11 11 12

C C

28 mm 800 mm 800 mm 800 mm 1000 mm 28 mm 28 mm 28 mm

PANEL NO. =JE01 =JE02 =JE03 =JE04

PANEL NAME OUTGOING OUTGOING OUTGOING BUS


FEEDER NO.1 FEEDER NO.2 FEEDER NO.3 SECTION
CIRCUIT 630A 630A 630A 2000A
BREAKER 25kA VD4 25kA VD4 25kA VD4 25kA VD4
D D

FRONT FRONT
PANEL DEPTH : 1700mm PANEL DEPTH : 1700mm
(END COVER)
PAMEUNGPEUK SUBSTATION

E E
LEGEND:
11 GUIDING HOLE FOR CB
12 OPENING FOR EARTH SWITCH AND INDICATOR
13 OPENING FOR RACKING IN & RACKING OUT OF CIRCUIT BREAKER
NP1 NAME PLATE
W VIEWING WINDOW

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 30
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA GENERAL ARRANGEMENT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/D03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: D04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
1700

1700
800 800 800 800 800 800 800 800 800 1000
B B
=JA01 =JA02 =JA03 =JA04 =JA05 =JB01 =JB02 =JB03 =JB04 =JB05

BOGOR BARU SUBSTATION PLAN VIEW TELUK JAMBE SUBSTATION PLAN VIEW

C C
1700

1700
800 800 800 800 1000 800 800 800 1000

=JC01 =JC02 =JC03 =JC04 =JC05 =JD01 =JD02 =JD03 =JD04


D D
GARUT SUBSTATION PLAN VIEW CIAMIS SUBSTATION PLAN VIEW

105 790 105 105 590 105

40
40

150
150

430
430
100 800 100 100 600 100
1700

680
680

1590
1590

1700
1700

E E

1400
1400
opening for power cables opening for power cables

80 200 200
80 200 200

65
65
opening for control cables opening for control cables

4-mounting hole (36X20) 4-mounting hole (36X20)

800 800 800 1000

70
70

40
40
105 790 105 105 590 105
=JE01 =JE02 =JE03 =JE04 1000 800

PAMEUNGPEUK SUBSTATION PLAN VIEW DIMENSION


F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 30
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA PLAN VIEW DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/D04
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: D06
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

105 590 105 105 790 105 105 590 105 105 790 105
A A

40

40

40

40
150

150

150

150
430

430

430

430
100 800 100 100 800 100 100 800 100 100 800 100

680

680

680

680
1590

1590

1590

1590
1700

1700

1700

1700
1400

1400

1400

1400
opening for power cables opening for power cables opening for power cables opening for power cables

B B
65 65 65 65
200

200

200

200
opening for control cables opening for control cables opening for control cables opening for control cables
80 200

80 200

80 200

80 200
4-mounting hole (36X20) 4-mounting hole (36X20) 4-mounting hole (36X20) 4-mounting hole (36X20)
70

70

70

70
40

40

40

40
105 590 105 105 790 105 105 590 105 105 790 105

800 1000 800 1000

24kV - 800&1000mm WIDE UNITS - ANCHORING BOLT FIXING SYSTEM 24kV - 800&1000mm WIDE UNITS - BASE IRON FIXING SYSTEM
C C

ANCHORING BOLT FIXING SYSTEM BASE IRON FIXING SYSTEM

>0,5
D D
80

80
Ø16
Ø16

ANCHORING BOLTS ON CONCRETE FLOOR BASE IRONS ON CONCRETE FLOOR

E E

M12
M12

THROUGH HOLE ON METAL STRUCTURE THREADED HOLE ON METAL STRUCTURE

NOTE: 1. FLOOR TOLARANCE ±1mm/METRE IN ALL DIRECTION UNDER SWITCHBOARD AND INCLUDING 1 METER IN FRONT
OF BOARD WITH A MAXIMUM ±3mm OVER ENTIRE SWITCHBOARD LENGTH.

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 25
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA DETAIL OF SWITCHGEAR INSTALLATION DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/D06
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: D07
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
LEGEND :
1 LV COMPARTMENT 7 HEATER Shutter painted "Signal Red" color 537 in BS381C,
2 CB COMPARTMENT 8 INSULATOR Labelled " BUSBAR" with white letters.
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

3 CABLE COMPARTMENT 9 -
CAPACITIVE INSULATOR
A A BUSBAR A
4 CIRCUIT BREAKER 10 CABLE TERMINATION
5 EARTHING SWITCH 11 EARTHING BAR 30X8
6 CURRENT TRANSFORMER B CIRCUIT

Shutter painted "Lemon Yellow" color 355 in BS381C,


Labelled " CIRCUIT" with white letters.

B B
400

400
FLAP FLAP FLAP FLAP FLAP FLAP

1 1

705

705
C C

2 2
A A 4

7
7

B
4
B
2200

D D

2200
1620

1620
6 6

5 5
3

8 9 8 9

3
10
10
E E
7
7

462
412

11 11

40 100 100 100 589 70 40 110 110 617 70


1700 1700

TYPICAL BUS SECTION PANEL TYPICAL OUTGOING FEEDER


F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 15
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SECTIONAL VIEW DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/D07
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: D09
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

EDMI Mk6

6
B B
10
10 EDMI

ABB
Ready Start Trip
REM 615
A A A ABB
Ready Start Trip
REM 615
A A A
4 4
8 9 HL
l
8 9 HL
ESC Clear l ESC Clear

O R
L ?
5 O R
L ?
5
ESSAILEC CABLE VOLTAGE INDICATOR ESSAILEC CABLE VOLTAGE INDICATOR

TTA entrelec H571


AUTO
RECLOSE

OFF ON
TRIP NEUTRAL CLOSE

TRIP
NEUTRAL
CLOSE
LOCAL
REMOTE
HEATER

OFF
ON
TTA entrelec H571
LOAD
SHEDDING

1 2
AUTO
RECLOSE

OFF ON
TRIP NEUTRAL CLOSE

TRIP
NEUTRAL
CLOSE
LOCAL
REMOTE
HEATER

OFF
ON

OFF 3
ESSAILEC ESSAILEC

7 7
4

TTA TTA
SALZER SALZER SALZER sälzer SALZER SALZER sälzer
SALZER

entrelec

1 2 3 HS
entrelec

11 1 2 3 HS
C C
1000 800
TYPICAL BUS SECTION TYPICAL OUTGOING FEEDER

LEGEND LEGEND
1 ON/OFF AUTO RECLOSE SELECTOR SWITCH HL HEATER ON I/L (W)
2 TRIP NEUTRAL CLOSE SELECTOR SWITCH HS HEATER SELECTOR SWITCH
D D
3 LOCAL REMOTE SELECTOR SWITCH A ANALOG AMMETER
4 FEEDER PROTECTION RELAY (REF615) AS AMMETER SELECTOR SWITCH
5 DIGITAL POWER METER (CROMPTON INTEGRA 1630)
6 ENERGY METER - EDMI
7 CAPACITIVE PHASE INDICATOR
8 CB ON I/L (RED)
9 CB OFF I/L (GREEN)
10 6 WINDOW ANNUNCIATOR
11 OFF/1/2/3/4 LOAD SHEDDING SELECTOR SWITCH
E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 10
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA LV COMPARTMENT DOOR ARRANGEMENT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/D09
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: E01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

B B
TYPE UniGear ZS1 TYPE UniGear ZS1

ASEA BROWN BOVERI ASEA BROWN BOVERI


WORKS ORDER NO. : MY-04511274.A E12070JS WORKS ORDER NO. : MY-04511274.A E12070JS

RATED NORMAL CURRENT 2000A RATED VOLTAGE 24kV RATED NORMAL CURRENT 630A RATED VOLTAGE 24kV

RATED MAIN BUSBAR RATED MAIN BUSBAR


CURRENT
2000A SYSTEM VOLTAGE 20kV CURRENT
2000A SYSTEM VOLTAGE 20kV

RATED SHORT TIME RATED INSULATION RATED SHORT TIME RATED INSULATION
C WITHSTAND CURRENT
25kA 3sec LEVEL
24/50/125kV WITHSTAND CURRENT
25kA 3sec LEVEL
24/50/125kV C
RATED PEAK WITHSTAND RATED PEAK WITHSTAND
CURRENT
63kA RATED FREQUENCY 50Hz CURRENT
63kA RATED FREQUENCY 50Hz

IEC STANDARD IEC 62271-200 MADE IN MALAYSIA IEC STANDARD IEC 62271-200 MADE IN MALAYSIA

PANEL RATING FOR ALL TYPICAL BUS SECTION PANELS PANEL RATING FOR ALL TYPICAL OUTGOING FEEDERS

D D

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA PANEL RATING LABEL DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/E01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: E02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

ENGRAVING TEXT LABEL SIZE - A


LABEL (NP1)
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

PANEL TYPE

10 mm
A FIRST LINE SECOND LINE THIRD LINE SIZE A
(FONT SIZE: 14mm) (FONT SIZE: 10mm) (FONT SIZE: 10mm)
FIRST LINE

8 mm
=JA01 NP1 =JA01 BOGOR BARU OUTGOING FEEDER A

70 mm
SECOND LINE

8 mm
=JA02 NP1 =JA02 BOGOR BARU OUTGOING FEEDER A

=JA03 NP1 =JA03 BOGOR BARU OUTGOING FEEDER A THIRD LINE

10 mm
=JA04 NP1 =JA04 BOGOR BARU OUTGOING FEEDER A
147 mm
=JA05 NP1 =JA05 BOGOR BARU OUTGOING FEEDER A
B MATERIAL: PVC TRAFFOLYTE B
=JB01 NP1 =JB01 TELUK JAMBE OUTGOING FEEDER A FIXING: SELF ADHESIVE
COLOUR: BLACK LETTER ON WHITE BACKGROUND
=JB02 NP1 =JB02 TELUK JAMBE OUTGOING FEEDER A

=JB03 NP1 =JB03 TELUK JAMBE OUTGOING FEEDER A

=JB04 NP1 =JB04 TELUK JAMBE OUTGOING FEEDER A

=JB05 NP1 =JB05 TELUK JAMBE BUS SECTION A

=JC01 NP1 =JC01 GARUT OUTGOING FEEDER A


C C
=JC02 NP1 =JC02 GARUT OUTGOING FEEDER A

=JC03 NP1 =JC03 GARUT OUTGOING FEEDER A

=JC04 NP1 =JC04 GARUT OUTGOING FEEDER A

=JC05 NP1 =JC05 GARUT BUS SECTION A

=JD01 NP1 =JD01 CIAMIS OUTGOING FEEDER A

=JD02 NP1 =JD02 CIAMIS OUTGOING FEEDER A


D D
=JD03 NP1 =JD03 CIAMIS OUTGOING FEEDER A

=JD04 NP1 =JD04 CIAMIS BUS SECTION A

=JE01 NP1 =J01 PAMEUNGPEUK OUTGOING FEEDER A

=JE02 NP1 =J02 PAMEUNGPEUK OUTGOING FEEDER A

=JE03 NP1 =J03 PAMEUNGPEUK OUTGOING FEEDER A

=JE04 NP1 =J04 PAMEUNGPEUK OUTGOING FEEDER A


E E
=JE05 NP1 =J05 PAMEUNGPEUK BUS SECTION A

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI GENERAL DRAWINGS SCALE (A3): 1 : 2
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA NAME PLATE DETAILS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J00+GA/E02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: =J01+/B01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TABLE OF CONTENTS
PAGE NAME DRAWING NO. SHEET NO. REVISION
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01/B01 A0 A1 A


TABLE OF CONTENTS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01/C01 A0 A1
BILL OF MATERIALS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01/C02 A0 A1
BILL OF MATERIALS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01/C03 A0 A1
BILL OF MATERIALS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01/C04 A0 A1
BILL OF MATERIALS
B TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/A01 A0 A1 B
POWER CIRCUIT
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/A02 A0 A1
POWER CIRCUIT
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/G01 A0 A1
DC VOLTAGE SUPPLY CIRCUITS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/G02 A0 A1
AC VOLTAGE SUPPLY CIRCUITS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/M01 A0 A1
VD4 C.B. INTERNAL WIRING
C C
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/M02 A0 A1
E.S. - INTERNAL WIRING
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/M03 A0 A1
CLOSING & TRIPPING CIRCUITS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/M04 A0 A1
INDICATION CIRCUIT
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/M05 A0 A1
MBAS0600 ANNUNCIATOR - SIGNAL INPUTS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/N01 A0 A1
D REF615 - A/I + BINARY I/O BOARD D
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/N02 A0 A1
REF615 - A/I + BINARY I/O BOARD
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/N03 A0 A1
RELAY INPUT SIGNALS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/N04 A0 A1
RELAY INPUT SIGNALS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/N05 A0 A1
RELAY INPUT SIGNALS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/N99 A0 A1
E CROSS REFERENCE E
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/N100 A0 A1
CROSS REFERENCE
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/X01 A0 A1
SPARE CONTACTS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/X02 A0 A1
SPARE CONTACTS
TYPICAL OUTGOING FEEDER E12070JS ==SWG1=J01+WLV/X03 A0 A1
SPARE CONTACTS
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA TABLE OF CONTENTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01/B01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF MATERIALS
DESIGNATION PART NUMBER MATERIAL DESCRIPTION MODEL MANUFACTURER MATERIAL TECHNICAL DATA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +CB-BT4 GCE7109399R0106 POSITION SWITCHES ON -BT4 ABB Located at Fix Part of UniGear Switchgear, 5 Auxiliary Contacts A
+WLV/N04/4.B SWITCHGEAR SIGNALLING
TRUCK IN SERVICE POSITION
+CB-BT5 GCE7109399R0106 POSITION SWITCHES ON -BT5 ABB Located at Fix Part of UniGear Switchgear, 5 Auxiliary Contacts
+WLV/N04/4.B SWITCHGEAR SIGNALLING
TRUCK IN TEST POSITION
+CB-EH2 SB-1B-50W ANTI-CONDENSATION HEATER SB-1B-50W CHANGSA 50W, 220VAC, 50Hz, Slim Type
+WLV/G02/3.E

+CB-QB VD4/P24.06.25P210 VACUUM CIRCUIT BREAKER VD4/P24.06.25P210 ABB XIAMEN 630A, 24kV, 25kA, 3sec, Poles Distance: 210mm.
+WLV/M01/1.A
B +CB-QB PART OF VD4 VCB VD4 ACCESSORY -BB1, -BB2 & -BB3 ABB XIAMEN 14 Auxiliary Contacts, -BB1, -BB2 & -BB3 B
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -MO1 ABB XIAMEN Standard Shunt Opening Release -MO1 - 110VDC
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -RL1 ABB XIAMEN Locking Magnet on Operating Mechanism -RL1 - 110VDC
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -RL2 ABB XIAMEN Locking Magnet on Truck -RL2 - 110VDC
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -MS ABB XIAMEN Motor Operator Closing Spring Charging -MS - 110VDC
+WLV/M01/1.A
C C
+CB-QB PART OF VD4 VCB VD4 ACCESSORY -MC ABB XIAMEN Shunt Closing Release -MC - 110VDC
+WLV/M01/1.A

+CCB-BC1R ORDER ACCORDING TO WOUND TYPE CURRENT LZZB9-24/178/382b DYH Ratio: 400-800/5/5A
+WLV/A01/2.B DESCRIPTION TRANSFORMER Core 1: CL5P20, 7.5VA on 400A; 15VA on 800A
Core 2: CL0.5, 7.5VA on 400A; 15VA on 800A
Frequency: 50Hz
Insulation level: 24/50/125kV
Ith: 25kA/1sec
Secondary at P2
D +CCB-BC2R ORDER ACCORDING TO WOUND TYPE CURRENT LZZB9-24/178/382b DYH Ratio: 400-800/5/5A D
+WLV/A01/2.B DESCRIPTION TRANSFORMER Core 1: CL5P20, 7.5VA on 400A; 15VA on 800A
Core 2: CL0.5, 7.5VA on 400A; 15VA on 800A
Frequency: 50Hz
Insulation level: 24/50/125kV
Ith: 25kA/1sec
Secondary at P2
+CCB-BC3R ORDER ACCORDING TO WOUND TYPE CURRENT LZZB9-24/178/382b DYH Ratio: 400-800/5/5A
+WLV/A01/3.B DESCRIPTION TRANSFORMER Core 1: CL5P20, 7.5VA on 400A; 15VA on 800A
Core 2: CL0.5, 7.5VA on 400A; 15VA on 800A
Frequency: 50Hz
E E
Insulation level: 24/50/125kV
Ith: 25kA/1sec
Secondary at P2
+CCB-BU1 DIK-24-KXST030007 CAPACITIVE DETECTION KXST030007 MOTIC ELECTRIC Rated Voltage: 24kV
+WLV/A02/2.D INSULATOR Height: 225mm
+CCB-BU2 DIK-24-KXST030007 CAPACITIVE DETECTION KXST030007 MOTIC ELECTRIC Rated Voltage: 24kV
+WLV/A02/2.D INSULATOR Height: 225mm

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA BILL OF MATERIALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01/C01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF MATERIALS
DESIGNATION PART NUMBER MATERIAL DESCRIPTION MODEL MANUFACTURER MATERIAL TECHNICAL DATA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +CCB-BU3 DIK-24-KXST030007 CAPACITIVE DETECTION KXST030007 MOTIC ELECTRIC Rated Voltage: 24kV A
+WLV/A02/3.D INSULATOR Height: 225mm
+CCB-QE GCE7169312R0119 EARTH SWITCH EK6-2406-210 XIAMEN 24kV, 25kA, 3sec, Poles Distance: 210mm
+WLV/M02/3.A XINGJITAI
ELECTRICAL
+CCB-QE GCE7109399R0101 EARTH SWITCH AUXILIARY -BE1 ABB 5 Auxiliary Contacts, -BE1
+WLV/M02/3.A CONTACTS
+CCB-QE GCE7109399R0101 EARTH SWITCH AUXILIARY -BE2 ABB 5 Auxiliary Contacts, -BE2
+WLV/M02/3.A CONTACTS
+CCB-QE GCE9401766P0105 EARTH SWITCH BLOCKING -RL3 ABB Locking Magnet on Operating Mechanism -RL3 - 110VDC
B +WLV/M02/3.A MAGNET B
+CCF-EH1 SB-1B-100W ANTI-CONDENSATION HEATER SB-1B-100W CHANGSA 100W, 220VAC, 50Hz, Slim Type
+WLV/G02/3.E

+LVD-AR30.1 HBFDACADAND1AAN1XD FEEDER PROTECTION AND REF615 ABB REF615EA02D REF615 base unit for feeder protection
+WLV/N01/1.A CONTROL RELAY DISB01B Display Module LHMI IEC-variant, size 64*128
AIMB01A Analog input module 4 pcs (1/5A) CT inputs
Digital inputs 4
Threshold voltage for binary inputs Configurable between 18 - 176 VDC
COMB03A Communication module RS485
BIOB03A Additional Binary Inputs 8
C Additional Binary Outputs 4 C
Threshold voltage Configurable between 18 -176 VDC
PSMB02B Power Supply
Input voltage, AC 100-249 VAC
Input voltage, DC 48-250 VDC
Nominal frequency 50/60 HZ
Binary Outputs 6
CSEB01B Case
ACNB04A Functional Application "D" Non-directional O/C, non-directional E/F and CB condition
monitoring
SWFB01A Addtional Software Function for Auto-reclosure
D SWCB63A Communication protocol (s) IEC 103 D

+LVD-AR30.2 REFER TO -AR30.1 FEEDER PROTECTION AND REF615 ABB Refer to -AR30.1
+WLV/N02/1.A CONTROL RELAY
+LVD-EL PHI-11W/84-EHS ENERGY SAVING BULB GENIE E27 PHILIPS 11W, 220-240VAC, 50/60Hz, c/w Porcelain Holder
+WLV/G02/5.E

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA BILL OF MATERIALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01/C02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF MATERIALS
DESIGNATION PART NUMBER MATERIAL DESCRIPTION MODEL MANUFACTURER MATERIAL TECHNICAL DATA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +LVD-PA1 M-10B6SP3-NF ALARM ANNUNCIATOR MBAS0600 MINILEC Supply Voltage : 90-270V AC/DC A
+WLV/N100/4.A Windows : 6 small windows
Windows Sizes : 30x30mm
Display Device : Super bright high efficiencly low power consuming LED's
Facia Type : Individual windows Front Replaceable
Window/LED Colours : Yellow
Flash Rate : Fast - 60 flashes/min. Slow - 30 flashes/min.
Response Time : 25msec. ± 10 msec.
Input Signal : Potential free contacts (NO or NC site selectable)
Interrogation Voltage : + 12 V DC
Output Contacts : 1NO
B Architecture : Integrated B
Operational Sequences : S1
Operational Temp. : 0-60 degrees C
Power Consumption : 1.5 Watts per Window (Max)
C/W built in control modulr pushbutton (Test, Silence, Acknowledge and Reset)
+LVD-PG1 APW199DEG PILOT LIGHT APW199DEG DEMEX Lens: Green, 22mm Diameter Cutout, 6-240V
+WLV/M04/2.D

+LVD-PG1 A-BA9S-LED-110-W LED BA9S ATEC Colour: White, 110VAC/DC


+WLV/M04/2.D

+LVD-PM INT-1630-L-5-M-010 INTEGRA DIGITAL POWER INTEGRA 1630 CROMPTON Current Inputs: 5A
C +WLV/N100/1.D SYSTEM INSTRUMENTS Voltage Inputs: 57.7-139V L–N (100-240V L-L), 3-phase 3/4-wire C
Frequency: 45-66Hz
Auxiliary Power Supply: 100-250V AC/DC
Communication: 1 x RS485 Port Modbus Protocol
+LVD-PR1 APW199DER PILOT LIGHT APW199DER DEMEX Lens: Red, 22mm Diameter Cutout, 6-240V
+WLV/M04/2.D
+LVD-PR1 A-BA9S-LED-110-W LED BA9S ATEC Colour: White, 110VAC/DC
+WLV/M04/2.D

+LVD-PU DXN-T-22kV CAPACITIVE VOLTAGE DXN-T LEELEN For 22kV system, LED Indicator with Key-press, Rated Frequency: 50/60Hz, Threshold Voltage:
+WLV/A02/4.C INDICATOR 15%...40%Un
D D
+LVD-S20 M220-61001-003M1 2-POSITION SELECTOR SWITCH M220 TYPE SALZER 1 Pole, Ith: 20A, Size: 48x48mm²
+WLV/G02/3.D Legend: HEATER, Label: OFF/ON
+LVD-SS1 M220-61040-003V1 2-POSITION PADLOCKABLE M220 TYPE SALZER 4 Poles, Ith: 20A, Size: 48x48mm²
+WLV/N99/2.A SELECTOR SWITCH Legend: LOCAL REMOTE, Label: LOCAL/REMOTE
+LVD-SS2 M220-61362-003V1 3-POSITION PADLOCKABLE M220 TYPE SALZER 2 Poles, Ith: 20A, Size: 48x48mm²
+WLV/N99/2.D SPRING RETURN SELECTOR Legend: CIRCUIT BREAKER, Label: TRIP/NEUTRAL/CLOSE
SWITCH
+LVD-SS3 M220-61038-003V1 2-POSITION PADLOCKABLE M220 TYPE SALZER 2 Poles, Ith: 20A, Size: 48x48mm²
+WLV/N99/6.A SELECTOR SWITCH Legend: AUTO RECLOSE, Label: OFF/ON
E +LVD-SS4 M220-61651-003V1/01 5-POSITION PADLOCKABLE M220 TYPE SALZER 1 Pole, Ith: 20A, Size: 48x48mm² E
+WLV/N99/5.D SELECTOR SWITCH Legend: LOAD SHEDDING, Label: OFF/1/2/3/4
+LVD-XM1 1SNA166625R2000 CURRENT TEST BLOCK ESSAILEC ABB 4 Poles, Flush Mounted, with Lid and Coding 6.6
+WLV/A01/4.B CC-E-VA-6.6
+LVD-XM1 1SNA166502R2600 CURRENT TEST PLUG ESSAILEC 166502.26 ABB Plug with 8x2.5mm² 8x14 AWG Pins
+WLV/A01/4.B
+LVD-XM2 1SNA166625R2000 CURRENT TEST BLOCK ESSAILEC ABB 4 Poles, Flush Mounted, with Lid and Coding 6.6
+WLV/A01/4.D CC-E-VA-6.6

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA BILL OF MATERIALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01/C03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF MATERIALS
DESIGNATION PART NUMBER MATERIAL DESCRIPTION MODEL MANUFACTURER MATERIAL TECHNICAL DATA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +LVD-XM2 1SNA166502R2600 CURRENT TEST PLUG ESSAILEC 166502.26 ABB Plug with 8x2.5mm² 8x14 AWG Pins A
+WLV/A01/4.D

+WLV-B1 R-EC96-400/800/52 AMMETER R-EC96 RUDOLF CT Ratio: 400-800/5A, Scale: 0-400/800A & 0-800/1600A Dual Scale (2X Overscale), 90 Degree
+WLV/A02/7.D Deflection, 96x96mm²
+WLV-B2 R-EC96-400/800/52 AMMETER R-EC96 RUDOLF CT Ratio: 400-800/5A, Scale: 0-400/800A & 0-800/1600A Dual Scale (2X Overscale), 90 Degree
+WLV/A02/7.D Deflection, 96x96mm²
+WLV-B3 R-EC96-400/800/52 AMMETER R-EC96 RUDOLF CT Ratio: 400-800/5A, Scale: 0-400/800A & 0-800/1600A Dual Scale (2X Overscale), 90 Degree
+WLV/A02/8.D Deflection, 96x96mm²
+WLV-BH GWTB-110 THERMOSTAT GWTB-110 SHIMATEC Setting: 0 - 110 Celcius, 1x Change-over contact
+WLV/G02/3.E
B +WLV-FB1 2CDS252001R0064 MINIATURE CIRCUIT BREAKER S202-C6 ABB 2 Poles, 440VAC/125VDC Max., 6A, 6kA, Tripping Characteristic C B
+WLV/G01/1.D

+WLV-FB1 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
+WLV/G01/1.D

+WLV-FB2 2CDS252001R0064 MINIATURE CIRCUIT BREAKER S202-C6 ABB 2 Poles, 440VAC/125VDC Max., 6A, 6kA, Tripping Characteristic C
+WLV/G01/3.D

+WLV-FB2 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
+WLV/G01/3.D

+WLV-FB3 2CDS252001R0064 MINIATURE CIRCUIT BREAKER S202-C6 ABB 2 Poles, 440VAC/125VDC Max., 6A, 6kA, Tripping Characteristic C
+WLV/G01/5.D
C C
+WLV-FB3 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
+WLV/G01/5.D

+WLV-FB4 2CDS252001R0974 MINIATURE CIRCUIT BREAKER S202-C1.6 ABB 2 Poles, 440VAC/125VDC Max., 1.6A, 6kA, Tripping Characteristic C
+WLV/G01/7.D
+WLV-FB4 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
+WLV/G01/7.D

+WLV-FB5 2CDS252001R0064 MINIATURE CIRCUIT BREAKER S202-C6 ABB 2 Poles, 440VAC/125VDC Max., 6A, 6kA, Tripping Characteristic C
+WLV/G02/2.C

+WLV-FB5 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
D +WLV/G02/2.C D
+WLV-H20 APW199DEW PILOT LIGHT APW199DEW DEMEX Lens: White, 22mm Diameter Cutout, 6-240V
+WLV/G02/4.E
+WLV-H20 A-BA9S-LED-110-W LED BA9S ATEC Colour: White, 110VAC/DC
+WLV/G02/4.E

+WLV-R1 RF022K00005WC RESISTOR RESISTOR - 22k ohm 5W Carbon Film


+WLV/M03/2.D

+WLV-S101 Z15G1307 LIMIT SWITCH Z15G1307 HIGHLY Contacts: 1 Change-over


+WLV/G02/5.D

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA BILL OF MATERIALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01/C04
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: +WLV/A01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

R 3ph.AC, 50Hz, 20kV, 2000A, 25kA/3s


Y
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B
A A
+CB
-QB1 VD4/P 24.06.25 CURRENT METERING INPUTS (In=1/5A)
+LVD
24kV REF615
630A -AR30.1
25kA /N01/1.A

IL1 IL2 IL3 Io


L1 COM L2 COM L3 COM N COM
-X120 7 8 9 10 11 12 13 14
CURRENT TEST (A71)
+CCB +CCB +CCB BLOCK
-BC1R P1 -BC2R P1 -BC3R P1 +LVD
B -XM1 B
(A110) -XA1 1 (A113) 2 L1 L1 02 (A114)
(A130) -XA1 2 (A133) 3 L2 L2 03 (A134)

(A150) -XA1 3 (A153) 4 L3 L3 04 (A154)

(A111) -XA1 4
1 N N 01 (A170)
(A131) -XA1 5

(A151) -XA1 6

-GND
(A190) -XA1 7
C C
3xCT(W) 1S1 1S1 1S1
3x400-800/5/5A
C1:CL 5P20 1S2 1S2 1S2
15VA 1S3 1S3 1S3
(A112) -XA1 8

(A132) -XA1 9
CURRENT TEST
(A152) -XA1 10 BLOCK
+LVD
-XM2
(A210) -XA2 1 (A213) 2 L1 L1 02
D D
(A230) -XA2 2 (A233) 3 L2 L2 03
(A250) -XA2 3 (A253) 4 L3 L3 04

(A211) -XA2 4
1 N N 01
(A231) -XA2 5

(A251) -XA2 6

-GND

(A214)

(A234)

(A254)

(A270)
(A290) -XA2 7
2S1 2S1 2S1
E C2:CL 0.5,Fs5
2S2
E
15VA 2S2 2S2
2S3 2S3 2S3
(A212) -XA2 8
(A232) -XA2 9

-BC1R.1

-BC2R.1

BC3R.1

-BCN.1
A02/3.A

A02/3.A

A02/3.A

A02/3.A
(A252) -XA2 10

P2 P2 P2

-E1 -R1 -Y1 -B1


A02/1.A A02/2.A A02/2.A A02/3.A
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA POWER CIRCUIT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/A01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: A02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

-BC1R.1

-BC2R.1

BC3R.1

-BCN.1
GENIUS ENERGY METER MULTIFUNCTION INTEGRA 1630

A01/5.E

A01/5.E

A01/6.E

A01/6.E
+LVD-PM1 +LVD-PM
A01/1.F A01/2.F A01/2.F A01/3.F EDMI MK6 /N100/1.D DIGITAL METERING SYSTEM
E1 R1 Y1 B1 CURRENT INPUTS
VOLTAGE INPUTS
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

Ia Ib Ic CURRENT INPUTS VOLTAGE INPUTS


A S1 S2 S1 S2 S1 S2 Va Vb Vc Vn IL1 IL2 IL3 A
-TB1 1 3 4 6 8 10 2 5 9 13 S1 S2 S1 S2 S1 S2 L1 L2 L3 N
1 3 4 6 7 9 2 5 8 11
(A213)
(A233)

(A253)

B B
(A270)

(V110)

(V130)

(V150)

(V170)
-XV2 1 2 3 4

PT

C C
CAPACITIVE VOLTAGE INDICATOR
+LVD
+CCB -PU
-BU1
1 (L1) 1 1 1
L1
-B1 A -B2 A -B3 A
+CCB 0-400/800A 0-400/800A 0-400/800A
0-800/1600A 3 0-800/1600A 3 0-800/1600A 3
-BU2
1 (L2)
L2
D D
+CCB
-BU3 -SH
1 (L3)
L3

GND

+CCB
-QE
E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA POWER CIRCUIT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/A02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: G01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PREVIOUS MCB - 110V DC MCB - 110V DC MCB - 110V DC MCB - 110V DC


NEXT PANEL
PANEL CONTROL INDICATION PROTECTION RELAY SPRING CHARGE MOTOR
VOLTAGE SUPPLY VOLTAGE SUPPLY VOLTAGE SUPPLY VOLTAGE SUPPLY
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

-XJ 1 -XJ 1
A A
-XJ 3 -XJ 3

(J1)

(J2)
-XJ 1 3

B -XJ 2 4 B
(J1)

(J2)

C C

1 3 L13 L21 1 3 L13 L21 1 3 L13 L21 1 3 L13 L21


-FB1 -FB2 -FB3 -FB4
S202-C6 2 4 L14 L22 S202-C6 2 4 L14 L22 S202-C6 2 4 L14 L22 S202-C1.6 2 4 L14 L22
6A 6A 6A 1.6A
/M05/1.C

/M05/2.C

/M05/2.C

/M05/3.C
-XM 1 -XM 2
D D

(M1)

(M2)
/M01/1.A
(K101)

(K102)

(K201)

(K202)
(K1)

(K2)

+CB -XB 25
-QB
2
-BS1
1

E E
-MS M
-DC110_L1+
/M03/1.A
-DC110_L2+ -DC110_L3+
-DC110_L1- /M04/1.A /N03/1.A
-XB 35
/M03/1.F /M01/1.D
-DC110_L2- -DC110_L3-
/M04/1.F /N03/1.F

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA DC VOLTAGE SUPPLY CIRCUITS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/G01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: G02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PREVIOUS HEATER HEATER HEATER ON PANEL NEXT PANEL


PANEL CABLE CB I/L (WHITE) LIGHTING
COMPARTMENT COMPARTMENT
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

230VAC 230VAC
A A
50Hz 50Hz

-XH 1 -XH 2

-XH 3 -XH 4

(H1)

(H2)
-XH 1 3

B -XH 2 4
B

(H1)

(H2)

1 3 L13 L21
-FB5
S202-C6 2 4 L14 L22
6A
C /M05/3.C C
(H3)

(H4)

-XH 5 -XH 6
(H3)

COM
1
+LVD 1 2
-S101
-S20 2
NC
D ON/OFF D
(H5)

(H7)
HEATER
SWITCH
-XH 7 -XH 14
(H5)

X1
1
-BH T +LVD
C -EL
(H6)

(H6) 220-240VAC
X2
11W

-XH 8 9
(H6)

(H6)

E E
1 1 X1
+CCF +CB
-H20
-EH1 -EH2 WHITE X2
100W 2 50W 2
(H4)

(H4)

(H4)

-XH 10 11 12 13

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA AC VOLTAGE SUPPLY CIRCUITS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/G02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

-VD4 CN
DOC. No: 1YH8122104 -GND
(QB90) (QB91)

/M03/2.C
/M04/2.B
/G01/7.D

/M03/4.E

/M03/7.E

/M03/2.E

/M03/2.E

/M03/6.E

/M03/6.E
/N04/2.B

/N03/5.B

/N03/6.B

/X01/2.B

/X01/2.B

/X02/3.B

/X02/1.B

/X02/2.B

/X02/3.B

/X02/6.B

/X02/5.B

/X02/4.B
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
-XB
+CB 24 26 25 45 4 5 32 27 2 31 41 23 8 11 6 29 28 9 7 1 40 52 12 49 10 57 55
-QB

CB DISCHARGED

CB CHARGED

CB OPENED

CB CLOSED
B -BS2 -BS1 B
4 2 2
-BT2
3 1 1 0 I 13 23 33 43 53

-BB1 -BB2 -BB3 14 24 34 44 54


-MS 13 21 31 43 53 13 21 31 41 53 13 21 31 41 53
M P
14 22 32 44 54 14 22 32 42 54 14 22 32 42 54

POSITION
SERVICE
-BT1 13 23 33 43 53

C 14 24 34 44 54 C

TEST
POSITION
-RL2 -RL1 -MC -MO1

D 34 36 35 46 20 14 15 42 13 37 3 30 33 18 22 21 16 39 38 19 17 50 51 53 54 47 48 58 56 D
-XB
/N04/2.C

/G01/7.E

/M03/4.F

/M03/6.F

/M03/7.F

/N03/5.C

/N03/6.C

/M04/2.C

/X01/2.B

/M04/2.C

/M03/2.F

/X01/2.B

/M03/2.D

/X02/3.C

/X02/1.C

/X02/2.C

/X02/3.C

/X02/6.C

/X02/6.C

/X02/5.C

/X02/4.C
DESIGNATION FIGURE DESCRIPTION DESIGNATION FIGURE DESCRIPTION
CIRCUIT BREAKER SWITCHED OFF
-MS Fig.1 MOTOR FOR SPRING CHARGING -BB1 Fig.32 AUXILIARY SWITCH C.B. SHAFT
SPRING NOT CHARGED -MC Fig.2 CLOSING RELEASE -BB2 Fig.32 AUXILIARY SWITCH C.B. SHAFT
E
TRUCK IN THE SERVICE POSITION -MO1 Fig.7 FIRST SHUNT OPENING RELEASE -BB3 Fig.32 AUXILIARY SWITCH C.B. SHAFT E
-RL1 Fig.3 ELECTROMECHANICAL LOCK C.B. CLOSING -BT1 Fig.51 C.B. TRUCK IN SERVICE (CONNECTED) POSITION
-RL2 Fig.8 ELEKTROMECHANICAL LOCK C.B. TRUCK -BT2 Fig.51 C.B. TRUCK IN TEST (ISOLATED) POSITION
-BS1 Fig.1 CONTACT FOR CHARGER MECHANISM -XB 58-POLE PLUG FOR AUXILIARY CIRCUITS
-BS2 Fig.26 SIGNALLING - SPRING CHAR./DISCHAR. -XG GROUND TERMINALS

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA VD4 C.B. INTERNAL WIRING DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/M01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EARTH SWITCH OFF AND


CRANK NOT INSERTED
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
L1 L2 L3

+CCB-QE

/N04/6.B

/X03/1.E

/X03/2.E
40 42 44 46 48
-BE1

/M03/8.E
41 43 45 47 49

/N04/5.B

/X03/3.E

/X03/4.E
B B
G
-RL3 40 42 44 46 48
H -BE2
41 43 45 47 49

/X01/6.B

/X01/7.B
20 22 24 26 28
-BE3
21 23 25 27 29
C C

D D

DESIGNATION DESCRIPTION
-BE1 EARTH SWITCH OPENED
-BE2 EARTH SWITCH CLOSED
-RL3 EARTH SWITCH CLOSING BLOCKING COIL

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA E.S. - INTERNAL WIRING DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/M02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SHUNT RELEASE CB TRUCK BLOCKING


REF615 CB CLOSING
OPEN MAGNET
PROTECTION TRIP BLOCKING MAGNET CB CLOSING RELEASE ES BLOCKING
TCS COIL
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A SPARE A
-DC110_L1+
/G01/1.E
-XK 1 -XK 2 -XK 3 -XK 4

(K1)
(K1)

(K1)
(K1)

(K1)
(K1)
-XR 1
-X100 16 15
+LVD -XR 3 -XR 5
-AR30.1 -XK 5

Rint
/N01/1.A PO3
-X100 6
-JUMPER 1
B REMOVE JUMPER -JUMPER 2 +LVD B
-X100 17 LINK IF CONNECTED
REMOVE JUMPER -AR30.1 PO1
TO INTERLOCK -XR 7
LINK IF CONNECTED /N01/1.A

(K6)
TO INTERLOCK
-X100 7
-XR 4 -XR 6
-X100 19
+LVD
-XR -AR30.1

TCS1
2
PO3 -XR 9
/N01/1.A -XR 8

(K9)
-JUMPER 3
-X100 18
(K3)
C -XR 10 REMOVE JUMPER C
-XK 10 LINK IF CONNECTED
(K3) TO INTERLOCK
/M01/5.A -XK 15 -XK 16
+CB -XB 8
-QB
31
-BB2

(K8)

(K9)

(K10)
(K3)

(K7)
32

D -XB 18 D
/M01/5.D
-XK 14
(K5)

-R1
(K4)

x2 -XK
13

(K1)
x1
-XK 11 (K5)
-XK 12 22kohm 5W /M01/8.A /M01/8.A
/M01/4.A /M01/4.A
+CB -XB 10 -XB 49
+CB -XB 31 -XB 41
-QB
-QB 43 43
13 /M01/2.A /M01/3.A
-BT1 -BT2
-BB2 +CB -XB 45 +CB -XB 4 (RL3:G)
44 44
14
-QB -QB +CCB
E G E
-QE -RL3
/M02/3.A H
-RL2 -RL1 -MC
-MO1
(RL3:H)

-XB 46 -XB 20 -XB 14


-XB 30
/M01/2.D /M01/2.D /M01/3.D
(K2)

(K2)

(K2)
/M01/4.D

-XK 6 -XK 7 -XK 8 -XK 9


(K2)
-DC110_L1-
/G01/2.E
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA CLOSING & TRIPPING CIRCUITS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/M03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A CB CLOSED CB OPENED ANNUNCIATOR ANNUNCIATOR EDMI MK6 AUX A


POWER SUPPLY STANDBY POWER POWER SUPPLY
SUPPLY
(K101)
DC110_L2+
G01/3.E
-XK1 1 -XK1 2 -XK1 3 -XK1 4

/M01/4.A

(K101)

(K101)

(K101)
+CB -XB 2
B B
-QB
53 31
-BB1 -BB1
54 32

(PM90)
-XB 3 -XB 13 -GND
/M01/4.D /M01/3.D

E +VE1 +VE2 -TB1 7


+LVD +LVD +LVD L/+
C C
-PA1 -PA1 -PM1
(K103)

(K104)

/N100/4.A /N100/4.A
-PS

(AC/DC)
N/-
-XK1 7 -XK1 8 -VE1 -VE2 -TB1 11
(K103)

(K104)

D D
X1 X1
+LVD +LVD
-PR1 X2
-PG1 X2
RED GREEN
(K102)

(K102)

(K102)

(K102)
E E

-XK1 5 -XK1 6 -XK1 7 -XK1 8

DC110_L2-
G01/3.E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA INDICATION CIRCUIT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/M04
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M05
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

ANNUNCIATOR SIGNAL INPUTS

AC/DC SUPPLY OC & EF AUTO RECLOSE AUTO RECLOSE CB DRAWN OUT SPARE
FAIL PROTECTION FAIL OPERATED
TRIP
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
(C1)
-XC 1 -XC 3 -XC 5 -XC 7 -XC 9 -XC 11 -XC 13

(C1)

(C1)

(C1)

(C1)

(C1)
B B

-X100 10 -X110 14 -X100 13


L21 L21 L21 L21 L21 +LVD +LVD +LVD 26

(C1)
-AR30.1 SO1 -AR30.1 SO1 -AR30.1 SO2 +CB
-FB1 -FB2 -FB3 -FB4 -FB5
/G01/1.D L22 /G01/3.D L22 /G01/5.D L22 /G01/7.D L22 /G02/2.C L22 /N01/1.A /N01/1.A /N01/1.A -BT5
27
-X100 11 12 -X110 16 15 -X100 14
C C
(C2)

(C3)

(C4)

(C5)

(C6)
D D

-XC 2 -XC 4 -XC 6 -XC 8 -XC 10 -XC 12


(C2)

(C3)

(C4)

(C5)

(C6)

(C7)
F1 F2 F3 F4 F5 F6 C
+LVD
-PA1 +
/N100/4.A
CH1 CH2 CH3 CH4 CH5 CH6
E E
-

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA MBAS0600 ANNUNCIATOR - SIGNAL INPUTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/M05
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N01
1 2 3 4 5 6 7 8
F
E
B

C
A

D
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A0
A1

REV.
1
1

FIRST ISSUE
FEEDER PROTECTION RELAY
+LVD-AR30.1

DESCRIPTION
REF615

REVISED AS PER COMMENTS


ANALOG INPUT AND BI MODULE
BINARY INPUT 1 (+) /N03/4.D -X120 1
BINARY INPUT 1, 2 & 3 (-) /N03/4.E 2
BI1
BINARY INPUT 2 (+) /N03/4.D 3
BI2

2
2

BINARY INPUT 3 (+) /N03/5.D 4

DATE
BI3

01/06/12
06/06/12
BINARY INPUT 4 (+) 5
(-) 6
BI4
INPUT FOR PHASE CURRENT (L1) /A01/6.B 7
COM /A01/6.B 8
IL1
INPUT FOR PHASE CURRENT (L2) /A01/6.B 9
COM /A01/6.B 10
IL2

PROJECT TITLE:
INPUT FOR PHASE CURRENT (L3) /A01/7.B 11
COM /A01/7.B 12
IL3

PLN WEST JAVA


INPUT FOR RESIDUAL CURRENT (N) /A01/7.B 13
COM /A01/7.B 14
Io

3
3

PROJECT NO.: MY-04511274.A


MAIN MODULE +
AUXILIARY VOLTAGE SUPPLY (+) INPUT /N03/2.D -X100 1
- Uaux
(-) INPUT /N03/2.E 2
IRF, COMMON /X01/2.E 3
CLOSED; IRF, OR Uaux DISCONNECTED /X01/2.E 4 IRF
CLOSED; NO IRF, AND Uaux CONNECTED /X01/2.E 5
POWER OUTPUT CONTACT 1, NO /M03/7.B 6 PO1
/M03/7.B 7
POWER OUTPUT CONTACT 2, NO /X02/4.E 8 PO2

DESIGNED:
APPROVED:
/X02/4.E 9

4
4

SIGNAL OUTPUT CONTACT 1, COMMON /M05/4.C 10


NC /M05/4.C 11
SO1
NO /M05/4.C 12
SIGNAL OUTPUT CONTACT 2, NO /M05/6.C 13
/M05/6.C 14
SO2

DRAWING NO.: E12070JS


POWER OUTPUT CONTACT 3, NO /M03/3.B 16

CUSTOMER: PT ABB SAKTI

NISHANTH
LEE ML
/M03/3.B 17
PO3
(TCS RESISTOR) /M03/3.B 15
POWER OUTPUT CONTACT 3, NO (TCS1 INPUT) /M03/3.B 19
/M03/3.C 18 TCS1

DRAWN:
CHECKED:
INDUSTRI
(TCS RESISTOR) 20
22
POWER OUTPUT CONTACT 4, NO 21
PO4

5
5

POWER OUTPUT CONTACT 4, NO (TCS2 INPUT) 23


24 TCS2

NISHANTH
CHEE MENG
BIO MODULE
BINARY INPUT 1 (+) /N03/7.D -X110 1
(-) /N03/7.E 2
BI1
BINARY INPUT 2 (+) /N05/2.D 3
(-) /N05/2.E 4
BI2
BINARY INPUT 3 (+) /N04/2.D 5
BI3
DRAWING TITLE:
BINARY INPUT 3 & 4 (-) /N04/2.E 6

BINARY INPUT 4 (+) /N04/2.D 7


BI4

6
6

BINARY INPUT 5 (+) /N04/4.D 8


BINARY INPUT 5 & 6 (-) /N04/4.E 9
BI5

BINARY INPUT 6 (+) /N04/4.D 10


BI6
TYPICAL OUTGOING FEEDER

BINARY INPUT 7 (+) /N04/5.D 11


BINARY INPUT 7 & 8 (-) /N04/5.E 12
BI7
REF615 - A/I + BINARY I/O BOARD

BINARY INPUT 8 (+) /N04/6.D 13


BI8
SIGNAL OUTPUT CONTACT 1, COMMON /M05/5.C 14
NC /M05/5.C 16 SO1
NO /M05/5.C 15
SIGNAL OUTPUT CONTACT 2, COMMON /X02/3.E 17
SO2
7
7

NC /X02/3.E 19
NO /X02/3.E 18
SIGNAL OUTPUT CONTACT 3, COMMON /X02/1.E 20
(COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920

SO3
ABB MANUFACTURING SDN BHD

NC /X02/1.E 22
NO /X02/1.E 21
SIGNAL OUTPUT CONTACT 4, NO /X02/2.E 23
/X02/2.E 24
SO4
CONT.:
SHEET:

8
8

LANGUAGE:

N02
==SWG1=J01+WLV/N01
DATE: 13/04/2009
SCALE (A3): 1 : 1
ENG
F
E
B

C
A

D
F
E
B

C
A

D
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A0
A1

REV.
1
1

FIRST ISSUE
FEEDER PROTECTION RELAY
+LVD-AR30.2

DESCRIPTION
REF615

REVISED AS PER COMMENTS


OPTIONAL BIO MODULE
BINARY INPUT 1 (+) -X130 1
BINARY INPUT 1 & 2 (-) 2
BI1

BI2

2
2

BINARY INPUT 2 (+) 3


BINARY INPUT 3 (+) 4

DATE
BINARY INPUT 3 & 4 (-) 5
BI3

01/06/12
06/06/12
BINARY INPUT 4 (+) 6
BI4
BINARY INPUT 5 (+) 7
BINARY INPUT 5 & 6 (-) 8
BI5

BINARY INPUT 6 (+) 9


BI6

PROJECT TITLE:
SIGNAL OUTPUT CONTACT 1, COMMON 10
NC 12 SO1

PLN WEST JAVA


NO 11
SIGNAL OUTPUT CONTACT 2, COMMON 13

3
3

NC 15 SO2
NO 14

PROJECT NO.: MY-04511274.A


SIGNAL OUTPUT CONTACT 3, COMMON 16
NC 18 SO3
NO 17

COMMUNICATION MODULE
GND (CASE) /X03/1.B -X5 1
GNDC (CASE VIA CAPASITOR) /X03/2.B 2
RESERVED 3

DESIGNED:
APPROVED:
IRIG-B (-) /X03/2.B 4

4
4

IRIG-B (+) /X03/2.B 5


AGND (ISOLATED GROUND) /X03/3.B 6
COM2 (B-) / TX (-) /X03/3.B 7
COM2 (A+) / TX (+) /X03/4.B 8
COM1 (B-) / RX (-) /X03/4.B 9

DRAWING NO.: E12070JS


COM1 (A+) / RX (+) /X03/4.B 10

CUSTOMER: PT ABB SAKTI

NISHANTH
LEE ML
DRAWN:
CHECKED:
INDUSTRI

5
5

NISHANTH
CHEE MENG
DRAWING TITLE:

6
6

TYPICAL OUTGOING FEEDER


REF615 - A/I + BINARY I/O BOARD

7
7

(COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920
CONT.:
SHEET:
ABB MANUFACTURING SDN BHD
8
8

LANGUAGE:

N03
==SWG1=J01+WLV/N02
DATE: 13/04/2009
SCALE (A3): 1 : 1
ENG
F
E
B

C
A

D
1 2 3 4 5 6 7 8
REF615 PROTECTION RELAY

PROTECTION RELAY DIGITAL POWER METER CB SHUNT OPENING CB ON CB OFF CB SHUNT CLOSING
POWER SUPPLY AUXILIARY SUPPLY LOCAL REMOTE STATUS STATUS LOCAL REMOTE
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
DC110_L3+ -A1+ / N04/1.A
G01/5.E
-XK2 1 -XK2 2 -XK2 3 -XK2 4 -XK2 5 -XK2 6

(K201)

(K201)
(K201)

(K201)
(K201) (K201)

1 3 5 7
+LVD 1 2
+LVD 1 2
+LVD 1 2
+LVD 1 2

-SS1 2
-SS1 4
/M01/3.A /M01/3.A -SS1 6
-SS1 8
LOCAL REMOTE +CB -XB 5 +CB -XB 32 LOCAL REMOTE
B /N99/3.B /N99/3.B /N99/3.B /N99/3.B B
-QB -QB

(K204)

(K209)
(K207)

(K211)
13 21
1 -BB1 -BB1 3
+LVD 123
14 22
+LVD 123

-SS2 -XR 11 -SS2 -XR 13


2 4
/N99/3.D /N99/3.D
(K201)

(K201)
TRIP -XB 15 -XB 42 TRIP
-XK2 19 -XR 12
/M01/3.D /M01/3.D -XK2 23 -XR 14

C C

(K208)
(K205)

(K206)

(K210)
-XK2 18 -XK2 20 -XK2 21 -XK2 22
(AR90)

(K205)

(K206)

(K208)

(K210)
-GND

D -GND -X100 1 14 D
L/+
-X120 1 -X120 3 -X120 4 -X110 1
+LVD +LVD
-AR30.1 -PM (AC/DC) +LVD +LVD
/N01/1.A /N100/1.D -AR30.1 -AR30.1
+

+
/N01/1.A
-PS BI1 BI2 BI3 /N01/1.A
BI1
- - - -

N/-
2 13 -X120 2 2
-X100 -X110

E E
(K202)
(K202)

(K202)

(K202)

-XK2 14 -XK2 15 -XK2 16

DC110_L3- -A1- / N04/1.F


G01/5.E
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA RELAY INPUT SIGNALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/N03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB. POS. STATUS ES STATUS SIGNAL

CB SPRING CHARGED CB IN
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

CB IN TEST ES ON ES OFF
A AUTO RECLOSE SERVICE A
ON POSITION
POSITION

-A1+
N03/7.A

-XK2 7 -XK2 8 -XK2 9 -XK2 10 -XK2 11 -XK2 12

(K201)

(K201)

(K201)

(K201)

(K201)

(K201)
B B

22 22 +CCB 42 +CCB 42
/M01/1.A +CB +CB -QE -QE
-BE2 -BE1
+CB -XB 24 -BT4 -BT5 /M02/3.A /M02/3.A
3 23 23 43 43
+LVD 1 2
-QB
-SS3 4
ON 4
/N99/7.B -BS2
3
C C
(K212)

(K214)

(K215)

(K216)

(K217)
-XB 34
/M01/1.D

-XK2 24 -XK2 25 -XK2 26 -XK2 27 -XK2 28 -XK2 29


(K212)

(K213)

(K214)

(K215)

(K216)

(K217)
D D

-X110 5 -X110 7 -X110 8 -X110 10 -X110 11 -X110 13

+LVD +LVD +LVD


-AR30.1 -AR30.1 -AR30.1
+

+
+

/N01/1.A /N01/1.A /N01/1.A


BI3 BI4 BI5 BI6 BI7 BI8
- - - - - -

6 -X110 9 -X110 12
E -X110 E

(K202) (K202)
(K202)

-XK2 17

-A1-
N03/7.F
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA RELAY INPUT SIGNALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/N04
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N05
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A LOAD SHEDDING CIRCUIT A

=EXT L-
L+

B B

-XR2 1 2 3 4 5
(R201)

(R202)

(R203)

(R204)
3 5 7 9
+LVD 12345
+LVD 12345
+LVD 12345
+LVD 12345

-SS4 4
-SS4 6
-SS4 8
-SS4 10
1 2 3 4
/N99/6.D /N99/7.D /N99/7.D /N99/7.D
C C
(R205)

(R205)

(R205)

-XR2 6 (R205)
D D
(R205)

-X110 3 (R206)
+LVD
-AR30.1
+

/N01/1.A
BI2
-

E -X110 4 E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA RELAY INPUT SIGNALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/N05
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N99
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

+LVD-SS1 +LVD-SS3
CONTROL AUTO RECLOSE

1 2 1 2
1 3 5 7 9 11 13 15 1 3 5 7

2 4 6 8 10 12 14 16 2 4 6 8
B B

/N03/4.B

/N03/4.B

/N03/7.B

/N03/7.B

/X01/3.B

/X01/3.E

/N04/2.C
PADLOCKABLE HANDLE SZ-61040-003V1/1 PADLOCKABLE HANDLE SZ-61038-003V1/6

1 LOCAL 1 OFF
2 REMOTE 2 ON

C C

+LVD-SS4
+LVD-SS2 LOAD SHEDDING
CIRCUIT BREAKER

2 2 3
D 1 3 1 3 5 7
1 3 5 7 9 D
1 4
2 4 6 8 10
2 4 6 8 5

/X01/3.E

/N05/2.C

/N05/2.C

/N05/3.C

/N05/4.C
/N03/4.B

/N03/7.B

SPRING-RETURN HANDLE PADLOCKABLE HANDLE


SZ-61362-003V1/1
WITH PADLOCKABLE
1 OFF
1 TRIP
2 1
2 NEUTRAL
3 2
3 CLOSE
E 4 3 E

5 4

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA CROSS REFERENCE DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/N99
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N100
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

+LVD MINILEC MBAS0600 ALARM ANNUNCIATOR WINDOW FACIAS

/M04/6.D
/M04/6.C
-PA1

/X03/7.B

/X03/8.B

/X03/7.B

/X03/8.B

/X03/8.B
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

/M04/3.D

/M04/4.D
/M04/3.C

/M04/3.C

/M04/4.C
-TB1 7 11 -TB10 1 2 3 4 5
+LVD L/+ N/- GND RX- TX+ RX+ TX- CH1 CH2
-PM1 POWER RS485 COMM. PORT
SUPPLY E +VE1 -VE1 +VE2 -VE2
EDMI MK6 GENIUS ENERGY METER
NORMAL STANDBY
CURRENT INPUTS SUPPLY SUPPLY
VOLTAGE INPUTS
Ia Ib Ic CH3 CH4
S1 S2 S1 S2 S1 S2 Va Vb Vc Vn
AUX. SUPPLY
-TB1 1 3 4 6 8 10 2 5 9 13
B B
/A02/4.A

/A02/4.A

/A02/4.A

/A02/5.A

/A02/5.A

/A02/5.A

/A02/5.A

/A02/6.A

/A02/6.A

/A02/6.A

/M05/1.E

/M05/4.E

/M05/5.E

/M05/6.E

/M05/6.E

/M05/7.E

/M05/7.E
CH5 CH6

F1 F2 F3 F4 F5 F6 C
COM

CH 1-8 SIGNAL INPUTS


C C

/N03/3.D
/N03/3.E
/X03/5.B

/X03/5.B

/X03/6.B

B A GND 13 14
+LVD RS485 N/- L/+
-PM COMMUNICATION PORT POWER SUPPLY
(AC/DC SUPPLY)

INTEGRA 1630
D D
CURRENT INPUTS
VOLTAGE INPUTS
IL1 IL2 IL3
S1 S2 S1 S2 S1 S2 L1 L2 L3 N
1 3 4 6 7 9 2 5 8 11
/A02/6.A

/A02/7.A

/A02/7.A

/A02/7.A

/A02/7.A

/A02/8.A

/A02/8.A

/A02/8.A

/A02/8.A

/A02/8.A

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA CROSS REFERENCE DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/N100
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: X01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

ES AUXILIARY
SPARE CONTACTS
COMMON CB ON CB OFF LOCAL MODE EARTH SWITCH INTERLOCKING E.S. OPENED AND E.S. OPENED AND
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

TO METERING PANEL CRANK NOT CRANK NOT


A (SPARE) A
INSERTED INSERTED

-XU 1 -XU 2 -XU 4 -XU 6 -XR1 1 -XR1 3 -XR1 5

(R101)

(R107)

(R109)
(U2)

(U3)

(U4)
/M01/4.A /M01/4.A
-XB 27 -XB 23 20 +CCB 20 +CCB 22
+CB +CB 9 +CB
+LVD 1 2 -QE -BE3 -QE -BE3
-QB -QB -BT5
21 /M02/3.A 21 /M02/3.A 23
-SS1
B 43 21 LOCAL
10 B
-BB1 -BB2 /N99/3.B
44 22

(R102)

(R108)

(R110)
(U1)
-XB 37 -XB 33
/M01/4.D /M01/4.D
(U1)

(U1)

-XU 3 -XU 5 -XU 7 -XR1 2 -XR1 4 -XR1 6


C C

REF615
RELAY AUTO RECLOSE LOAD SHEDDING
FAULTY OFF OFF

D -XU1 6 -XU1 10 -XU1 10 D


(U104)

(U108)

(U108)

-X100 3
+LVD 1 1
-AR30.1 IRF +LVD 1 2
+LVD 1 2

/N01/1.A -SS3 2
-SS4 2
OFF OFF
-X100 4 5 /N99/6.B /N99/6.D
E E
(U101)

(U101)

(U101)

-XU1 5 -XU1 11 -XU1 11

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SPARE CONTACTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/X01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: X02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB SPARE CONTACTS

CB CLOSED CB CLOSED CB OPENED CB OPENED CB IN SERVICE CB IN TEST POSITION CB IN TEST POSITION CB IN SERVICE
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

POSITION POSITION
A A

-XU2 1 -XU2 3 -XU2 5 -XU2 7 -XU2 9 -XU2 11 -XU2 13


(U201)

(U203)

(U205)

(U207)

(U209)

(U211)

(U213)
/M01/5.A /M01/6.A /M01/6.A /M01/5.A /M01/8.A /M01/8.A /M01/7.A
+CB -XB 28 +CB -XB 9 +CB -XB 7 +CB -XB 6 +CB -XB 55 +CB -XB 57 +CB -XB 52
-QB -QB -QB -QB -QB -QB -QB
B B
31 41 53 13 53 53 23 23
-BB3 -BB3 -BB3 -BB3 -BT1 -BT2 -BT2 -BT1
32 42 54 14 54 54 24 24

-XB 38 -XB 19 -XB 17 -XB 16 -XB 56 -XB 58 -XB 53 -XB 54


/M01/5.D /M01/6.D /M01/6.D /M01/5.D /M01/8.D /M01/8.D /M01/7.D /M01/7.D
(U202)

(U204)

(U206)

(U208)

(U210)

(U212)

(U214)

(U215)
C -XU2 2 -XU2 4 -XU2 6 -XU2 8 -XU2 10 -XU2 12 -XU2 14 -XU2 15 C

REF615 SPARE CONTACTS

D -XU2 16 -XU2 18 -XU2 20 -XU2 22


D
(U216)

(U218)

(U220)

-X110 20 -X110 23 -X110 17 -X100 (U222) 8


+LVD +LVD +LVD +LVD
-AR30.1 SO3 -AR30.1 SO4 -AR30.1 SO2 -AR30.1 PO2
/N01/1.A /N01/1.A /N01/1.A /N01/1.A

-X110 22 21 -X110 24 -X110 19 18 -X100 9

E E
(U217)

(U219)

(U221)

(U223)

-XU2 17 -XU2 19 -XU2 21 -XU2 23

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SPARE CONTACTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/X02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: X03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DPM RS485 ENERGY METER RS485


REF615 PROT.RELAY RS485 COMMUNICATION PORT COMMUNICATION COMMUNICATION PORT
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

PORT
A A

-XU2 26 27 28 29 30 31 32 33 34 35
(U227)

-SH1
-SH2
-XU2 36 37 38 39 40 41 42 43 44 45 46 47
(U228)

(U229)

(U230)

(U231)

(U232)

(U233)

(U234)

(U235)
-GND

(U239)

(U240)

(U241)

(U242)

(U243)

(U244)

(U245)
(U236)

(U237)

(U238)
B B

-SH2
-SH1 -SH1 -GND -GND
-X5 1 2 4 5 6 7 8 9 10 B A GND -TB10 1 3 5 4 2
+LVD GND GNDC IRIG-B (-) IRIG-B (+) AGND *COM2 (B-) *COM2 *COM1 (B-) *COM1 +LVD RS485 +LVD GND TX+ TX- RX+ RX-
(CASE) (CASE VIA (ISOLATED / TX (-) (A+) / RX (-) (A+) COMMUNICATION PORT
-AR30.2 -PM -PM1 RS485 COMMUNICATION PORT
CAPASITOR) GROUND) / TX (+) / RX (+)
/N02/1.A /N100/1.D
RS485
C C

SERVICE & TEST SPARE CONTACTS

ES SPARE CONTACTS
CB IN SERVICE CB IN SERVICE CB IN TEST
POSITION POSITION POSITION
ES OFF ES OFF ES ON ES ON
D D
-XU3 1 -XU3 3 -XU3 5 -XU3 7 -XU3 9 -XU3 11 -XU3 13
(U301)

(U303)

(U305)

(U307)

(U309)

(U311)

(U313)
+CCB-QE 44 +CCB-QE 46 +CCB-QE 44 +CCB-QE 46
24 26 24
/M02/3.A -BE1 /M02/3.A -BE1 /M02/3.A -BE2 /M02/3.A
-BE2 +CB +CB +CB
45 47 45 47 -BT4 -BT4 -BT5
25 27 25

E E
(U302)

(U304)

(U306)

(U308)

(U310)

(U312)

(U314)
-XU3 2 -XU3 4 -XU3 6 -XU3 8 -XU3 10 -XU3 12 -XU3 14

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL OUTGOING FEEDER SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SPARE CONTACTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J01+WLV/X03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: =J02+/B01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

TABLE OF CONTENTS
PAGE NAME DRAWING NO. SHEET NO. REVISION
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A TYPICAL BUS SECTION E12070JS ==SWG1=J02/B01 A0 A1 A


TABLE OF CONTENTS
TYPICAL BUS SECTION E12070JS ==SWG1=J02/C01 A0 A1
BILL OF MATERIALS
TYPICAL BUS SECTION E12070JS ==SWG1=J02/C02 A0 A1
BILL OF MATERIALS
TYPICAL BUS SECTION E12070JS ==SWG1=J02/C03 A0 A1
BILL OF MATERIALS
TYPICAL BUS SECTION E12070JS ==SWG1=J02/C04 A0 A1
BILL OF MATERIALS
B TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/A01 A0 A1 B
POWER CIRCUIT
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/A02 A0 A1
POWER CIRCUIT
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/G01 A0 A1
DC VOLTAGE SUPPLY CIRCUITS
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/G02 A0 A1
AC VOLTAGE SUPPLY CIRCUITS
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/M01 A0 A1
VD4 C.B. INTERNAL WIRING
C C
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/M02 A0 A1
E.S. - INTERNAL WIRING
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/M03 A0 A1
CLOSING & TRIPPING CIRCUITS
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/M04 A0 A1
INDICATION CIRCUIT
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/M05 A0 A1
MBAS0600 ANNUNCIATOR - SIGNAL INPUTS
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/N01 A0 A1
D REF615 - A/I + BINARY I/O BOARD D
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/N02 A0 A1
REF615 - A/I + BINARY I/O BOARD
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/N03 A0 A1
RELAY INPUT SIGNALS
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/N04 A0 A1
RELAY INPUT SIGNALS
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/N99 A0 A1
CROSS REFERENCE
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/N100 A0 A1
E CROSS REFERENCE E
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/X01 A0 A1
SPARE CONTACTS
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/X02 A0 A1
SPARE CONTACTS
TYPICAL BUS SECTION E12070JS ==SWG1=J02+WLV/X03 A0 A1
SPARE CONTACTS

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA TABLE OF CONTENTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02/B01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF MATERIALS
DESIGNATION PART NUMBER MATERIAL DESCRIPTION MODEL MANUFACTURER MATERIAL TECHNICAL DATA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +CB-BT4 GCE7109399R0106 POSITION SWITCHES ON -BT4 ABB Located at Fix Part of UniGear Switchgear, 5 Auxiliary Contacts A
+WLV/N04/4.B SWITCHGEAR SIGNALLING
TRUCK IN SERVICE POSITION
+CB-BT5 GCE7109399R0106 POSITION SWITCHES ON -BT5 ABB Located at Fix Part of UniGear Switchgear, 5 Auxiliary Contacts
+WLV/N04/4.B SWITCHGEAR SIGNALLING
TRUCK IN TEST POSITION
+CB-BX GCE7109399R0106 POSITION SWITCHES OF -BX ABB Located at Fix Part of UniGear Switchgear, 5 Auxiliary Contacts
+WLV/X03/7.E CIRCUIT BREAKER CONNECTOR
+CB-EH2 SB-1B-50W ANTI-CONDENSATION HEATER SB-1B-50W CHANGSA 50W, 220VAC, 50Hz, Slim Type
+WLV/G02/3.E
B +CB-QB VD4/P24.20.25P275 VACUUM CIRCUIT BREAKER VD4/P24.20.25P275 ABB XIAMEN 2000A, 24kV, 25kA, 3sec, Poles Distance: 275mm. B
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -BB1, -BB2 & -BB3 ABB XIAMEN 14 Auxiliary Contacts, -BB1, -BB2 & -BB3
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -MO1 ABB XIAMEN Standard Shunt Opening Release -MO1 - 110VDC
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -RL1 ABB XIAMEN Locking Magnet on Operating Mechanism -RL1 - 110VDC
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -RL2 ABB XIAMEN Locking Magnet on Truck -RL2 - 110VDC
+WLV/M01/1.A
C C
+CB-QB PART OF VD4 VCB VD4 ACCESSORY -MS ABB XIAMEN Motor Operator Closing Spring Charging -MS - 110VDC
+WLV/M01/1.A

+CB-QB PART OF VD4 VCB VD4 ACCESSORY -MC ABB XIAMEN Shunt Closing Release -MC - 110VDC
+WLV/M01/1.A

+CCB-BC1R ORDER ACCORDING TO WOUND TYPE CURRENT LZZB9-24/178/382b DYH Ratio: 400-800/5/5A
+WLV/A01/2.B DESCRIPTION TRANSFORMER Core 1: CL5P20, 7.5VA on 400A; 15VA on 800A
Core 2: CL0.5, 7.5VA on 400A; 15VA on 800A
Frequency: 50Hz
Insulation level: 24/50/125kV
Ith: 25kA/1sec
D D
Secondary at P2
+CCB-BC2R ORDER ACCORDING TO WOUND TYPE CURRENT LZZB9-24/178/382b DYH Ratio: 400-800/5/5A
+WLV/A01/2.B DESCRIPTION TRANSFORMER Core 1: CL5P20, 7.5VA on 400A; 15VA on 800A
Core 2: CL0.5, 7.5VA on 400A; 15VA on 800A
Frequency: 50Hz
Insulation level: 24/50/125kV
Ith: 25kA/1sec
Secondary at P2
+CCB-BC3R ORDER ACCORDING TO WOUND TYPE CURRENT LZZB9-24/178/382b DYH Ratio: 400-800/5/5A
E +WLV/A01/3.B DESCRIPTION TRANSFORMER Core 1: CL5P20, 7.5VA on 400A; 15VA on 800A E
Core 2: CL0.5, 7.5VA on 400A; 15VA on 800A
Frequency: 50Hz
Insulation level: 24/50/125kV
Ith: 25kA/1sec
Secondary at P2
+CCB-BU1 DIK-24-KXST030007 CAPACITIVE DETECTION KXST030007 MOTIC ELECTRIC Rated Voltage: 24kV
+WLV/A02/2.D INSULATOR Height: 225mm

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA BILL OF MATERIALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02/C01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF MATERIALS
DESIGNATION PART NUMBER MATERIAL DESCRIPTION MODEL MANUFACTURER MATERIAL TECHNICAL DATA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +CCB-BU2 DIK-24-KXST030007 CAPACITIVE DETECTION KXST030007 MOTIC ELECTRIC Rated Voltage: 24kV A
+WLV/A02/2.D INSULATOR Height: 225mm
+CCB-BU3 DIK-24-KXST030007 CAPACITIVE DETECTION KXST030007 MOTIC ELECTRIC Rated Voltage: 24kV
+WLV/A02/3.D INSULATOR Height: 225mm
+CCB-QE GCE7169312R0119 EARTH SWITCH EK6-2406-210 XIAMEN 24kV, 25kA, 3sec, Poles Distance: 210mm
+WLV/M02/3.A XINGJITAI
ELECTRICAL
+CCB-QE GCE7109399R0101 EARTH SWITCH AUXILIARY -BE1 ABB 5 Auxiliary Contacts, -BE1
+WLV/M02/3.A CONTACTS
+CCB-QE GCE7109399R0101 EARTH SWITCH AUXILIARY -BE2 ABB 5 Auxiliary Contacts, -BE2
B +WLV/M02/3.A CONTACTS B
+CCB-QE GCE9401766P0105 EARTH SWITCH BLOCKING -RL3 ABB Locking Magnet on Operating Mechanism -RL3 - 110VDC
+WLV/M02/3.A MAGNET
+CCF-EH1 SB-1B-100W ANTI-CONDENSATION HEATER SB-1B-100W CHANGSA 100W, 220VAC, 50Hz, Slim Type
+WLV/G02/3.E

+LVD-AR30.1 HBFDACADAND1AAN1XD FEEDER PROTECTION AND REF615 ABB REF615EA02D REF615 base unit for feeder protection
+WLV/N01/1.A CONTROL RELAY DISB01B Display Module LHMI IEC-variant, size 64*128
AIMB01A Analog input module 4 pcs (1/5A) CT inputs
Digital inputs 4
Threshold voltage for binary inputs Configurable between 18 - 176 VDC
C COMB03A Communication module RS485 C
BIOB03A Additional Binary Inputs 8
Additional Binary Outputs 4
Threshold voltage Configurable between 18 -176 VDC
PSMB02B Power Supply
Input voltage, AC 100-249 VAC
Input voltage, DC 48-250 VDC
Nominal frequency 50/60 HZ
Binary Outputs 6
CSEB01B Case
ACNB04A Functional Application "D" Non-directional O/C, non-directional E/F and CB condition
D monitoring D
SWFB01A Addtional Software Function for Auto-reclosure
SWCB63A Communication protocol (s) IEC 103
+LVD-AR30.2 REFER TO -AR30.1 FEEDER PROTECTION AND REF615 ABB Refer to -AR30.1
+WLV/N02/1.A CONTROL RELAY
+LVD-EL PHI-11W/84-EHS ENERGY SAVING BULB GENIE E27 PHILIPS 11W, 220-240VAC, 50/60Hz, c/w Porcelain Holder
+WLV/G02/5.E

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA BILL OF MATERIALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02/C02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF MATERIALS
DESIGNATION PART NUMBER MATERIAL DESCRIPTION MODEL MANUFACTURER MATERIAL TECHNICAL DATA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +LVD-PA1 M-10B6SP3-NF ALARM ANNUNCIATOR MBAS0600 MINILEC Supply Voltage : 90-270V AC/DC A
+WLV/N100/1.A Windows : 6 small windows
Windows Sizes : 30x30mm
Display Device : Super bright high efficiencly low power consuming LED's
Facia Type : Individual windows Front Replaceable
Window/LED Colours : Yellow
Flash Rate : Fast - 60 flashes/min. Slow - 30 flashes/min.
Response Time : 25msec. ± 10 msec.
Input Signal : Potential free contacts (NO or NC site selectable)
Interrogation Voltage : + 12 V DC
Output Contacts : 1NO
B Architecture : Integrated B
Operational Sequences : S1
Operational Temp. : 0-60 degrees C
Power Consumption : 1.5 Watts per Window (Max)
C/W built in control modulr pushbutton (Test, Silence, Acknowledge and Reset)
+LVD-PG1 APW199DEG PILOT LIGHT APW199DEG DEMEX Lens: Green, 22mm Diameter Cutout, 6-240V
+WLV/M04/2.D

+LVD-PG1 A-BA9S-LED-110-W LED BA9S ATEC Colour: White, 110VAC/DC


+WLV/M04/2.D

+LVD-PM INT-1630-L-5-M-010 INTEGRA DIGITAL POWER INTEGRA 1630 CROMPTON Current Inputs: 5A
C +WLV/N99/5.B SYSTEM INSTRUMENTS Voltage Inputs: 57.7-139V L–N (100-240V L-L), 3-phase 3/4-wire C
Frequency: 45-66Hz
Auxiliary Power Supply: 100-250V AC/DC
Communication: 1 x RS485 Port Modbus Protocol
+LVD-PR1 APW199DER PILOT LIGHT APW199DER DEMEX Lens: Red, 22mm Diameter Cutout, 6-240V
+WLV/M04/2.D
+LVD-PR1 A-BA9S-LED-110-W LED BA9S ATEC Colour: White, 110VAC/DC
+WLV/M04/2.D

+LVD-PU DXN-T-22kV CAPACITIVE VOLTAGE DXN-T LEELEN For 22kV system, LED Indicator with Key-press, Rated Frequency: 50/60Hz, Threshold Voltage:
+WLV/A02/4.C INDICATOR 15%...40%Un
D D
+LVD-S20 M220-61001-003M1 2-POSITION SELECTOR SWITCH M220 TYPE SALZER 1 Pole, Ith: 20A, Size: 48x48mm²
+WLV/G02/3.D Legend: HEATER, Label: OFF/ON
+LVD-SS1 M220-61040-003V1 2-POSITION PADLOCKABLE M220 TYPE SALZER 4 Poles, Ith: 20A, Size: 48x48mm²
+WLV/N99/2.A SELECTOR SWITCH Legend: LOCAL REMOTE, Label: LOCAL/REMOTE
+LVD-SS2 M220-61362-003V1 3-POSITION PADLOCKABLE M220 TYPE SALZER 2 Poles, Ith: 20A, Size: 48x48mm²
+WLV/N99/2.D SPRING RETURN SELECTOR Legend: CIRCUIT BREAKER, Label: TRIP/NEUTRAL/CLOSE
SWITCH
+LVD-SS3 M220-61038-003V1 2-POSITION PADLOCKABLE M220 TYPE SALZER 2 Poles, Ith: 20A, Size: 48x48mm²
+WLV/N99/7.D SELECTOR SWITCH Legend: AUTO RECLOSE, Label: OFF/ON
E +LVD-XM1 1SNA166625R2000 CURRENT TEST BLOCK ESSAILEC ABB 4 Poles, Flush Mounted, with Lid and Coding 6.6 E
+WLV/A01/5.B CC-E-VA-6.6
+LVD-XM1 1SNA166502R2600 CURRENT TEST PLUG ESSAILEC 166502.26 ABB Plug with 8x2.5mm² 8x14 AWG Pins
+WLV/A01/5.B

+LVD-XM2 1SNA166625R2000 CURRENT TEST BLOCK ESSAILEC ABB 4 Poles, Flush Mounted, with Lid and Coding 6.6
+WLV/A01/5.D CC-E-VA-6.6
+LVD-XM2 1SNA166502R2600 CURRENT TEST PLUG ESSAILEC 166502.26 ABB Plug with 8x2.5mm² 8x14 AWG Pins
+WLV/A01/5.D

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA BILL OF MATERIALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02/C03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: C04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

BILL OF MATERIALS
DESIGNATION PART NUMBER MATERIAL DESCRIPTION MODEL MANUFACTURER MATERIAL TECHNICAL DATA
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +WLV-B1 R-EC96-2000/52 AMMETER R-EC96 RUDOLF CT Ratio: 2000/5A, Scale: 0-2000/4000A (2X Overscale), 90 Degree Deflection, 96x96mm² A
+WLV/A01/6.E

+WLV-B2 R-EC96-2000/52 AMMETER R-EC96 RUDOLF CT Ratio: 2000/5A, Scale: 0-2000/4000A (2X Overscale), 90 Degree Deflection, 96x96mm²
+WLV/A01/6.E

+WLV-B3 R-EC96-2000/52 AMMETER R-EC96 RUDOLF CT Ratio: 2000/5A, Scale: 0-2000/4000A (2X Overscale), 90 Degree Deflection, 96x96mm²
+WLV/A01/7.E

+WLV-BH GWTB-110 THERMOSTAT GWTB-110 SHIMATEC Setting: 0 - 110 Celcius, 1x Change-over contact
+WLV/G02/3.E
+WLV-FB1 2CDS252001R0064 MINIATURE CIRCUIT BREAKER S202-C6 ABB 2 Poles, 440VAC/125VDC Max., 6A, 6kA, Tripping Characteristic C
+WLV/G01/1.D
B +WLV-FB1 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series B
+WLV/G01/1.D

+WLV-FB2 2CDS252001R0064 MINIATURE CIRCUIT BREAKER S202-C6 ABB 2 Poles, 440VAC/125VDC Max., 6A, 6kA, Tripping Characteristic C
+WLV/G01/3.D

+WLV-FB2 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
+WLV/G01/3.D

+WLV-FB3 2CDS252001R0064 MINIATURE CIRCUIT BREAKER S202-C6 ABB 2 Poles, 440VAC/125VDC Max., 6A, 6kA, Tripping Characteristic C
+WLV/G01/5.D

+WLV-FB3 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
+WLV/G01/5.D
C C
+WLV-FB4 2CDS252001R0974 MINIATURE CIRCUIT BREAKER S202-C1.6 ABB 2 Poles, 440VAC/125VDC Max., 1.6A, 6kA, Tripping Characteristic C
+WLV/G01/7.D

+WLV-FB4 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
+WLV/G01/7.D
+WLV-FB5 2CDS252001R0064 MINIATURE CIRCUIT BREAKER S202-C6 ABB 2 Poles, 440VAC/125VDC Max., 6A, 6kA, Tripping Characteristic C
+WLV/G02/2.C

+WLV-FB5 2CDS200936R0001 AUXILIARY CONTACTS S2C-H11L ABB Contacts: 1NO+1NC; Suitable for MCBs S200 series
+WLV/G02/2.C

+WLV-H20 APW199DEW PILOT LIGHT APW199DEW DEMEX Lens: White, 22mm Diameter Cutout, 6-240V
D +WLV/G02/4.E D
+WLV-H20 A-BA9S-LED-110-W LED BA9S ATEC Colour: White, 110VAC/DC
+WLV/G02/4.E
+WLV-R1 RF022K00005WC RESISTOR RESISTOR - 22k ohm 5W Carbon Film
+WLV/M03/2.D

+WLV-S101 Z15G1307 LIMIT SWITCH Z15G1307 HIGHLY Contacts: 1 Change-over


+WLV/G02/5.D

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA BILL OF MATERIALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02/C04
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: +WLV/A01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

R 3ph.AC, 50Hz, 20kV, 2000A, 25kA/3s


Y
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

B
A A
+CB
-QB1 VD4/P 24.20.25
24kV CURRENT METERING INPUTS (In=1/5A)
2000A
+LVD-AR30.1
/N01/1.A VOLTAGE METERING INPUTS (Un=60-210V)
25kA REF615
IL1 IL2 IL3 Io
L1 COM L2 COM L3 COM N COM
-X120 7 8 9 10 11 12 13 14
CURRENT TEST (A71)
+CCB +CCB +CCB BLOCK
-BC1R P1 -BC2R P1 -BC3R P1 +LVD
B -XM1 B
(A110) -XA1 1 (A113) 2 L1 L1 02
(A130) -XA1 2 (A133) 3 L2 L2 03
(A150) -XA1 3 (A153) 4 L3 L3 04
3xCT(W):
1S1 1S1 1S1
2000/5/5A
-GND
C1:CL 5P20 (A190) -XA1 7 (A170) 1 N N 01
15VA 1S2 1S2 1S2
(A111) -XA1 4
(A131) -XA1 5
C (A151) -XA1 6 C

+LVD-PM DIGITAL METERING SYSTEM


/N99/5.B CROMPTON INSTRUMENTS INTEGRA 1630
CURRENT INPUTS
VOLTAGE INPUTS
IL1 IL2 IL3
S1 S2 S1 S2 S1 S2 L1 L2 L3 N
1 3 4 6 7 9 2 5 8 11

(V110)

(V130)

(V150)

(V170)
CURRENT TEST
BLOCK
+LVD
D -XM2 -XV2 1 2 3 4
D
(A210) -XA2 1 (A213) 2 L1 L1 02 (A214)
PT
(A230) -XA2 2 (A233) 3 L2 L2 03 (A234)
(A250) -XA2 3 (A253) 4 L3 L3 04 (A254)

2S1 2S1 2S1


C2:CL 0.5,Fs5
-GND
15VA (A290) -XA2 7 (A270) 1 N N 01 (A270)
2S2 2S2 2S2
(A211) -XA2 4

(A231) -XA2 5
E (A251) -XA2 6 E
1 1 1

-B1 A -B2 A -B3 A


0-2000/4000A 0-2000/4000A 0-2000/4000A
3 3 3

P2 P2 P2

-E1 -R1 -Y1 -B1


A02/1.A A02/2.A A02/2.A A02/3.A
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA POWER CIRCUIT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/A01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: A02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

A01/1.F A01/2.F A01/2.F A01/3.F


E1 R1 Y1 B1
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

B B

C C
CAPACITIVE VOLTAGE INDICATOR
+LVD
+CCB -PU
-BU1
1 (L1)
L1

+CCB
-BU2
1 (L2)
L2
D D
+CCB
-BU3 -SH
1 (L3)
L3

GND

+CCB
-QE
E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA POWER CIRCUIT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/A02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: G01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PREVIOUS MCB - 110V DC MCB - 110V DC MCB - 110V DC MCB - 110V DC


NEXT PANEL
PANEL CONTROL INDICATION PROTECTION RELAY SPRING CHARGE MOTOR
VOLTAGE SUPPLY VOLTAGE SUPPLY VOLTAGE SUPPLY VOLTAGE SUPPLY
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

-XJ 1 -XJ 1
A A
-XJ 3 -XJ 3

(J1)

(J2)
-XJ 1 3

B -XJ 2 4 B
(J1)

(J2)

C C

1 3 L13 L21 1 3 L13 L21 1 3 L13 L21 1 3 L13 L21


-FB1 -FB2 -FB3 -FB4
S202-C6 2 4 L14 L22 S202-C6 2 4 L14 L22 S202-C6 2 4 L14 L22 S202-C1.6 2 4 L14 L22
6A 6A 6A 1.6A
/M05/1.C

/M05/2.C

/M05/2.C

/M05/3.C
-XM 1 -XM 2
D D

(M1)

(M2)
/M01/1.A
(K101)

(K102)

(K201)

(K202)
(K1)

(K2)

+CB -XB 25
-QB
2
-BS1
1

E E
-MS M
-DC110_L1+
/M03/1.A
-DC110_L2+ -DC110_L3+
-DC110_L1- /M04/1.A /N03/1.A
-XB 35
/M03/1.F /M01/1.D
-DC110_L2- -DC110_L3-
/M04/1.F /N03/1.F

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA DC VOLTAGE SUPPLY CIRCUITS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/G01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: G02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

PREVIOUS HEATER HEATER HEATER ON PANEL NEXT PANEL


PANEL CABLE CB I/L (WHITE) LIGHTING
COMPARTMENT COMPARTMENT
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

230VAC 230VAC
A A
50Hz 50Hz

-XH 1 -XH 2

-XH 3 -XH 4

(H1)

(H2)
-XH 1 3

B -XH 2 4
B

(H1)

(H2)

1 3 L13 L21
-FB5
S202-C6 2 4 L14 L22
6A
C /M05/3.C C
(H3)

(H4)

-XH 5 -XH 6
(H3)

COM
1
+LVD 1 2
-S101
-S20 2
NC
D /N99/5.D D
(H5)

(H7)
ON/OFF
HEATER
SWITCH -XH 7 -XH 14
(H5)

X1
1
-BH T +LVD
C -EL
(H6)

(H6) 220-240VAC
X2
11W

-XH 8 9
(H6)

(H6)

E E
1 1 X1
+CCF +CB
-H20
-EH1 -EH2 WHITE X2
100W 2 50W 2
(H4)

(H4)

(H4)

-XH 10 11 12 13

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA AC VOLTAGE SUPPLY CIRCUITS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/G02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

-VD4 CN
DOC. No: 1YH8122104 -GND
(QB90) (QB91)

/M03/2.C
/M04/2.B
/G01/7.D

/M03/4.E

/M03/7.E

/M03/2.E

/M03/2.E

/M03/6.E

/M03/6.E
/N04/2.B

/N03/5.B

/N03/6.B

/X01/2.B

/X01/2.B

/X02/3.B

/X02/1.B

/X02/2.B

/X02/3.B

/X02/6.B

/X02/5.B

/X02/4.B
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
-XB
+CB 24 26 25 45 4 5 32 27 2 31 41 23 8 11 6 29 28 9 7 1 40 52 12 49 10 57 55
-QB

CB DISCHARGED

CB CHARGED

CB OPENED

CB CLOSED
B -BS2 -BS1 B
4 2 2
-BT2
3 1 1 0 I 13 23 33 43 53

-BB1 -BB2 -BB3 14 24 34 44 54


-MS 13 21 31 43 53 13 21 31 41 53 13 21 31 41 53
M P
14 22 32 44 54 14 22 32 42 54 14 22 32 42 54

POSITION
SERVICE
-BT1 13 23 33 43 53

C 14 24 34 44 54 C

TEST
POSITION
-RL2 -RL1 -MC -MO1

D 34 36 35 46 20 14 15 42 13 37 3 30 33 18 22 21 16 39 38 19 17 50 51 53 54 47 48 58 56 D
-XB
/N04/2.C

/G01/7.E

/M03/4.F

/M03/6.F

/M03/7.F

/N03/5.C

/N03/6.C

/M04/2.C

/X01/2.B

/M04/2.C

/M03/2.F

/X01/2.B

/M03/2.D

/X02/3.C

/X02/1.C

/X02/2.C

/X02/3.C

/X02/6.C

/X02/6.C

/X02/5.C

/X02/4.C
DESIGNATION FIGURE DESCRIPTION DESIGNATION FIGURE DESCRIPTION
CIRCUIT BREAKER SWITCHED OFF
-MS Fig.1 MOTOR FOR SPRING CHARGING -BB1 Fig.32 AUXILIARY SWITCH C.B. SHAFT
SPRING NOT CHARGED -MC Fig.2 CLOSING RELEASE -BB2 Fig.32 AUXILIARY SWITCH C.B. SHAFT
E
TRUCK IN THE SERVICE POSITION -MO1 Fig.7 FIRST SHUNT OPENING RELEASE -BB3 Fig.32 AUXILIARY SWITCH C.B. SHAFT E
-RL1 Fig.3 ELECTROMECHANICAL LOCK C.B. CLOSING -BT1 Fig.51 C.B. TRUCK IN SERVICE (CONNECTED) POSITION
-RL2 Fig.8 ELEKTROMECHANICAL LOCK C.B. TRUCK -BT2 Fig.51 C.B. TRUCK IN TEST (ISOLATED) POSITION
-BS1 Fig.1 CONTACT FOR CHARGER MECHANISM -XB 58-POLE PLUG FOR AUXILIARY CIRCUITS
-BS2 Fig.26 SIGNALLING - SPRING CHAR./DISCHAR. -XG GROUND TERMINALS

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA VD4 C.B. INTERNAL WIRING DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/M01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

EARTH SWITCH OFF AND


CRANK NOT INSERTED
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
L1 L2 L3

+CCB-QE

/N04/6.B

/X03/1.E

/X03/2.E
40 42 44 46 48
-BE1

/M03/8.E
41 43 45 47 49

/N04/6.B

/X03/3.E

/X03/4.E
B B
G
-RL3 40 42 44 46 48
H -BE2
41 43 45 47 49

/X01/7.B

/X01/8.B
20 22 24 26 28
-BE3
21 23 25 27 29
C C

D D

DESIGNATION DESCRIPTION
-BE1 EARTH SWITCH OPENED
-BE2 EARTH SWITCH CLOSED
-BE3 EARTHING SWITCH OPENED AND CRANK NOT INSERTED
-RL3 EARTH SWITCH CLOSING BLOCKING COIL
E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA E.S. - INTERNAL WIRING DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/M02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

SHUNT RELEASE CB TRUCK BLOCKING


REF615 CB CLOSING
OPEN MAGNET
PROTECTION TRIP BLOCKING MAGNET CB CLOSING RELEASE ES BLOCKING
TCS COIL
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A SPARE A
-DC110_L1+
/G01/1.E
-XK 1 -XK 2 -XK 3 -XK 4

(K1)
(K1)

(K1)
(K1)

(K1)
(K1)
-XR 1
-X100 16 15
+LVD -XR 3 -XR 5
-AR30.1 -XK 5

Rint
/N01/1.A PO3
-X100 6
-JUMPER 1
B REMOVE JUMPER -JUMPER 2 +LVD B
-X100 17 LINK IF CONNECTED
REMOVE JUMPER -AR30.1 PO1
TO INTERLOCK -XR 7
LINK IF CONNECTED /N01/1.A

(K6)
TO INTERLOCK
-X100 7
-XR 4 -XR 6
-X100 19
+LVD
-XR -AR30.1

TCS1
2
PO3 -XR 9
/N01/1.A -XR 8

(K9)
-JUMPER 3
-X100 18
(K3)
C -XR 10 REMOVE JUMPER C
-XK 10 LINK IF CONNECTED
(K3) TO INTERLOCK
/M01/5.A -XK 15 -XK 16
+CB -XB 8
-QB
31
-BB2

(K8)

(K9)

(K10)
(K3)

(K7)
32

D -XB 18 D
/M01/5.D
-XK 14
(K5)

-R1
(K4)

x2 -XK
13

(K1)
x1
-XK 11 (K5)
-XK 12 22kohm 5W /M01/8.A /M01/8.A
/M01/4.A /M01/4.A
+CB -XB 10 -XB 49
+CB -XB 31 -XB 41
-QB
-QB 43 43
13 /M01/2.A /M01/3.A
-BT1 -BT2
-BB2 +CB -XB 45 +CB -XB 4 (RL3:G)
44 44
14
-QB -QB +CCB
E G E
-QE -RL3
/M02/3.A H
-RL2 -RL1 -MC
-MO1
(RL3:H)

-XB 46 -XB 20 -XB 14


-XB 30
/M01/2.D /M01/2.D /M01/3.D
(K2)

(K2)

(K2)
/M01/4.D

-XK 6 -XK 7 -XK 8 -XK 9


(K2)
-DC110_L1-
/G01/2.E
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA CLOSING & TRIPPING CIRCUITS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/M03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A CB CLOSED CB OPENED ANNUNCIATOR ANNUNCIATOR A


POWER SUPPLY STANDBY POWER
SUPPLY
(K101)
DC110_L2+
G01/3.E
-XK1 1 -XK1 2 -XK1 3

/M01/4.A
+CB -XB 2
B B
-QB
53 31
-BB1 -BB1
54 32

(PM90)
-XB 3 -XB 13 -GND
/M01/4.D /M01/3.D

E +VE1 +VE2
+LVD +LVD
C C
-PA1 -PA1
(K103)

(K104)

/N100/1.A /N100/1.A

-XK1 7 -XK1 8 -VE1 -VE2


(K103)

(K104)

D D
X1 X1
+LVD +LVD
-PR1 X2
-PG1 X2
RED GREEN
(K102)

E E

-XK1 4 -XK1 5 -XK1 6

DC110_L2-
G01/3.E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA INDICATION CIRCUIT DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/M04
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: M05
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

ANNUNCIATOR SIGNAL INPUTS

AC/DC SUPPLY OC & EF AUTO RECLOSE AUTO RECLOSE CB DRAWN OUT SPARE
FAIL PROTECTION FAIL OPERATED
TRIP
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A
(C1)
-XC 1 -XC 3 -XC 5 -XC 7 -XC 9 -XC 11 -XC 13

(C1)

(C1)

(C1)

(C1)

(C1)
B B

-X100 10 -X110 14 -X100 13


L21 L21 L21 L21 L21 +LVD +LVD +LVD 24

(C1)
-AR30.1 SO1 -AR30.1 SO1 -AR30.1 SO2 +CB
-FB1 -FB2 -FB3 -FB4 -FB5
/G01/1.D L22 /G01/3.D L22 /G01/5.D L22 /G01/7.D L22 /G02/2.C L22 /N01/1.A /N01/1.A /N01/1.A -BT5
25
-X100 11 12 -X110 16 15 -X100 14
C C
(C2)

(C3)

(C4)

(C5)

(C6)
D D

-XC 2 -XC 4 -XC 6 -XC 8 -XC 10 -XC 12


(C2)

(C3)

(C4)

(C5)

(C6)

(C7)
F1 F2 F3 F4 F5 F6 C
+LVD
-PA1 +
/N100/1.A
CH1 CH2 CH3 CH4 CH5 CH6
E E
-

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA MBAS0600 ANNUNCIATOR - SIGNAL INPUTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/M05
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N01
1 2 3 4 5 6 7 8
F
E
B

C
A

D
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A0
A1

REV.
1
1

FIRST ISSUE
FEEDER PROTECTION RELAY
+LVD-AR30.1

DESCRIPTION
REF615

REVISED AS PER COMMENTS


ANALOG INPUT AND BI MODULE
BINARY INPUT 1 (+) /N03/4.D -X120 1
BINARY INPUT 1, 2 & 3 (-) /N03/4.E 2
BI1
BINARY INPUT 2 (+) /N03/4.D 3
BI2

2
2

BINARY INPUT 3 (+) /N03/5.D 4

DATE
BI3

01/06/12
06/06/12
BINARY INPUT 4 (+) 5
(-) 6
BI4
INPUT FOR PHASE CURRENT (L1) /A01/5.B 7
COM /A01/6.B 8
IL1
INPUT FOR PHASE CURRENT (L2) /A01/6.B 9
COM /A01/6.B 10
IL2

PROJECT TITLE:
INPUT FOR PHASE CURRENT (L3) /A01/6.B 11
COM /A01/7.B 12
IL3

PLN WEST JAVA


INPUT FOR RESIDUAL CURRENT (N) /A01/7.B 13
COM /A01/7.B 14
Io

3
3

PROJECT NO.: MY-04511274.A


MAIN MODULE +
AUXILIARY VOLTAGE SUPPLY (+) INPUT /N03/2.D -X100 1
- Uaux
(-) INPUT /N03/2.E 2
IRF, COMMON /X01/2.E 3
CLOSED; IRF, OR Uaux DISCONNECTED /X01/2.E 4 IRF
CLOSED; NO IRF, AND Uaux CONNECTED /X01/2.E 5
POWER OUTPUT CONTACT 1, NO /M03/7.B 6 PO1
/M03/7.B 7
POWER OUTPUT CONTACT 2, NO /X02/4.E 8 PO2

DESIGNED:
APPROVED:
/X02/4.E 9

4
4

SIGNAL OUTPUT CONTACT 1, COMMON /M05/4.C 10


NC /M05/4.C 11
SO1
NO /M05/4.C 12
SIGNAL OUTPUT CONTACT 2, NO /M05/6.C 13
/M05/6.C 14
SO2

DRAWING NO.: E12070JS


POWER OUTPUT CONTACT 3, NO /M03/3.B 16

CUSTOMER: PT ABB SAKTI

NISHANTH
LEE ML
/M03/3.B 17
PO3
(TCS RESISTOR) /M03/3.B 15
POWER OUTPUT CONTACT 3, NO (TCS1 INPUT) /M03/3.B 19
/M03/3.C 18 TCS1

DRAWN:
CHECKED:
INDUSTRI
(TCS RESISTOR) 20
22
POWER OUTPUT CONTACT 4, NO 21
PO4

5
5

POWER OUTPUT CONTACT 4, NO (TCS2 INPUT) 23


24 TCS2

NISHANTH
CHEE MENG
BIO MODULE
BINARY INPUT 1 (+) /N03/7.D -X110 1
(-) /N03/7.E 2
BI1
BINARY INPUT 2 (+) /N04/8.D 3
(-) /N04/8.E 4
BI2
BINARY INPUT 3 (+) /N04/2.D 5
BI3
DRAWING TITLE:
BINARY INPUT 3 & 4 (-) /N04/2.E 6

BINARY INPUT 4 (+) /N04/2.D 7


BI4

6
6

BINARY INPUT 5 (+) /N04/4.D 8


BI5
TYPICAL BUS SECTION

BINARY INPUT 5 & 6 (-) /N04/4.E 9

BINARY INPUT 6 (+) /N04/4.D 10


BI6
BINARY INPUT 7 (+) /N04/6.D 11
BINARY INPUT 7 & 8 (-) /N04/6.E 12
BI7
REF615 - A/I + BINARY I/O BOARD

BINARY INPUT 8 (+) /N04/6.D 13


BI8
SIGNAL OUTPUT CONTACT 1, COMMON /M05/5.C 14
NC /M05/5.C 16 SO1
NO /M05/5.C 15
SIGNAL OUTPUT CONTACT 2, COMMON /X02/3.E 17
SO2
7
7

NC /X02/3.E 19
NO /X02/3.E 18
SIGNAL OUTPUT CONTACT 3, COMMON /X02/1.E 20
(COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920

SO3
ABB MANUFACTURING SDN BHD

NC /X02/1.E 22
NO /X02/1.E 21
SIGNAL OUTPUT CONTACT 4, NO /X02/2.E 23
/X02/2.E 24
SO4
CONT.:
SHEET:

8
8

LANGUAGE:

N02
==SWG1=J02+WLV/N01
DATE: 13/04/2009
SCALE (A3): 1 : 1
ENG
F
E
B

C
A

D
F
E
B

C
A

D
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A0
A1

REV.
1
1

FIRST ISSUE
FEEDER PROTECTION RELAY

DESCRIPTION
+LVD-AR30.2

REF615

REVISED AS PER COMMENTS


OPTIONAL BIO MODULE
BINARY INPUT 1 (+) -X130 1
BINARY INPUT 1 & 2 (-) 2
BI1

BI2

2
2

BINARY INPUT 2 (+) 3


BINARY INPUT 3 (+) 4

DATE
BINARY INPUT 3 & 4 (-) 5
BI3

01/06/12
06/06/12
BINARY INPUT 4 (+) 6
BI4
BINARY INPUT 5 (+) 7
BINARY INPUT 5 & 6 (-) 8
BI5

BINARY INPUT 6 (+) 9


BI6

PROJECT TITLE:
SIGNAL OUTPUT CONTACT 1, COMMON 10
NC 12 SO1

PLN WEST JAVA


NO 11
SIGNAL OUTPUT CONTACT 2, COMMON 13

3
3

NC 15 SO2
NO 14

PROJECT NO.: MY-04511274.A


SIGNAL OUTPUT CONTACT 3, COMMON 16
NC 18 SO3
NO 17

COMMUNICATION MODULE
GND (CASE) /X03/2.B -X5 1
GNDC (CASE VIA CAPASITOR) /X03/2.B 2
RESERVED 3

DESIGNED:
APPROVED:
IRIG-B (-) /X03/2.B 4

4
4

IRIG-B (+) /X03/3.B 5


AGND (ISOLATED GROUND) /X03/3.B 6
COM2 (B-) / TX (-) /X03/3.B 7
COM2 (A+) / TX (+) /X03/4.B 8
COM1 (B-) / RX (-) /X03/4.B 9

DRAWING NO.: E12070JS


COM1 (A+) / RX (+) /X03/5.B 10

CUSTOMER: PT ABB SAKTI

NISHANTH
LEE ML
DRAWN:
CHECKED:
INDUSTRI

5
5

NISHANTH
CHEE MENG
DRAWING TITLE:

6
6

TYPICAL BUS SECTION


REF615 - A/I + BINARY I/O BOARD

7
7

(COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920
CONT.:
SHEET:
ABB MANUFACTURING SDN BHD
8
8

LANGUAGE:

N03
==SWG1=J02+WLV/N02
DATE: 13/04/2009
SCALE (A3): 1 : 1
ENG
F
E
B

C
A

D
1 2 3 4 5 6 7 8
REF615 PROTECTION RELAY

DIGITAL POWER
PROTECTION RELAY CB SHUNT OPENING CB ON CB OFF CB SHUNT CLOSING
METER AUXILIARY
POWER SUPPLY LOCAL REMOTE STATUS STATUS LOCAL REMOTE
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

SUPPLY
A A
DC110_L3+ -A1+ / N04/1.A
G01/5.E
-XK2 1 -XK2 2 -XK2 3 -XK2 4 -XK2 5 -XK2 6

(K201)

(K201)
(K201)

(K201)
(K201) (K201)

1 3 5 7
+LVD 1 2
+LVD 1 2
+LVD 1 2
+LVD 1 2

-SS1 2
-SS1 4
/M01/3.A /M01/3.A -SS1 6
-SS1 8
LOCAL REMOTE +CB -XB 5 +CB -XB 32 LOCAL REMOTE
B /N99/3.B /N99/3.B /N99/3.B /N99/3.B B
-QB -QB

(K204)

(K209)
(K207)

(K211)
13 21
1 -BB1 -BB1 3
+LVD 123
14 22
+LVD 123

-SS2 -XR 11 -SS2 -XR 13


2 4
/N99/3.D /N99/3.D
(K201)

TRIP -XB 15 -XB 42 TRIP


-XK2 19 -XR 12
/M01/3.D /M01/3.D -XK2 23 -XR 14

C C

(K208)
(K205)

(K206)

(K210)
-XK2 18 -XK2 20 -XK2 21 -XK2 22
(AR90)

(K205)

(K206)

(K208)

(K210)
-GND

D -GND -X100 1 14 D
L/+
-X120 1 -X120 3 -X120 4 -X110 1
+LVD +LVD
-AR30.1 -PM +LVD +LVD
/N01/1.A /N99/5.B -AR30.1 -AR30.1
+

+
/N01/1.A
-PS BI1 BI2 BI3 /N01/1.A
BI1
- - - -
(AC/DC)
N/-
2 13 -X120 2 2
-X100 -X110

E E
(K202)
(K202)

(K202)

-XK2 14 -XK2 15 -XK2 16

DC110_L3- -A1- / N04/1.F


G01/5.E
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA RELAY INPUT SIGNALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/N03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N04
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB. POS. STATUS ES STATUS SIGNAL

AUTO RECLOSE CB SPRING CHARGED CB IN


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

CB IN TEST ES ON ES OFF
A ON A
SERVICE POSITION
POSITION

-A1+
N03/7.A

-XK2 7 -XK2 8 -XK2 9 -XK2 10 -XK2 11 -XK2 12 -XK2 13

(K201)

(K201)

(K201)

(K201)

(K201)

(K201)
B B

22 22 +CCB 42 +CCB 42
/M01/1.A +CB +CB -QE -QE
-BE2 -BE1
+CB -XB 24 -BT4 -BT5 /M02/3.A /M02/3.A
23 23 43 43
-QB
3
+LVD 1 2 4
-SS3 -BS2
4
ON 3
C /N99/8.D C

(K214)

(K215)

(K216)

(K217)
-XB 34
/M01/1.D

-XK2 24 -XK2 25 -XK2 26 -XK2 27 -XK2 28 -XK2 29 -XK2 30


(K212)

(K213)

(K214)

(K215)

(K216)

(K217)

(K218)
D D

-X110 5 -X110 7 -X110 8 -X110 10 -X110 11 -X110 13 -X110 3

+LVD +LVD +LVD +LVD


-AR30.1 -AR30.1 -AR30.1 -AR30.1
+

+
+

/N01/1.A /N01/1.A /N01/1.A /N01/1.A


BI3 BI4 BI5 BI6 BI7 BI8 BI2
- - - - - - -

6 -X110 9 -X110 12 -X110 4


E -X110 E

(K202) (K202)
(K202)

-XK2 17

-A1-
N03/7.F
F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA RELAY INPUT SIGNALS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/N04
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N99
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A A

/N03/3.D
/N03/3.E
/X03/6.C

/X03/6.C

/X03/6.C
+LVD-SS1
CONTROL
B A GND 13 14
+LVD RS485 N/- L/+
1 2
1 3 5 7 9 11 13 15 -PM COMM. PORT POWER SUPPLY
(AC/DC SUPPLY)
2 4 6 8 10 12 14 16 CROMPTON INSTRUMENTS INTEGRA 1630 DIGITAL METERING SYSTEM
B B

/N03/4.B

/N03/4.B

/N03/7.B

/N03/7.B

/X01/3.B
CURRENT INPUTS
VOLTAGE INPUTS
PADLOCKABLE HANDLE SZ-61040-003V1/1 IL1 IL2 IL3
S1 S2 S1 S2 S1 S2 L1 L2 L3 N
1 3 4 6 7 9 2 5 8 11
1 LOCAL

/A01/6.D

/A01/6.D

/A01/6.D

/A01/6.D

/A01/6.D

/A01/7.D

/A01/7.D

/A01/7.D

/A01/8.D

/A01/8.D
2 REMOTE

C C

+LVD-S20 +LVD-SS3
+LVD-SS2 HEATER
CIRCUIT BREAKER AUTO RECLOSE

2 0 1 1 2
D 1 3 1 3 5 7 D
1 3 5 7 1
2
2 4 6 8 2 4 6 8

/G02/3.D

/X01/3.E

/N04/2.C
/N03/4.B

/N03/7.B

SPRING-RETURN HANDLE SZ-61362-003V1/1 NORMAL HANDLE PADLOCKABLE HANDLE SZ-61038-003V1/6


WITH PADLOCKABLE
0 OFF 1 OFF
1 TRIP
1 ON 2 ON
2 NEUTRAL
3 CLOSE
E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA CROSS REFERENCE DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/N99
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: N100
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

A +LVD MINILEC MBAS0600 ALARM ANNUNCIATOR WINDOW FACIAS A


-PA1

/M04/3.D

/M04/4.D
/M04/3.C

/M04/3.C

/M04/4.C
CH1 CH2

E +VE1 -VE1 +VE2 -VE2

NORMAL STANDBY
SUPPLY SUPPLY
B CH3 CH4 B
AUX. SUPPLY
/M05/1.E

/M05/4.E

/M05/5.E

/M05/6.E

/M05/6.E

/M05/7.E

/M05/7.E
CH5 CH6

F1 F2 F3 F4 F5 F6 C
COM

C C
CH 1-8 SIGNAL INPUTS

D D

E E

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA CROSS REFERENCE DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/N100
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: X01
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

ES AUXILIARY
2 OUT OF 3 CB INTERLOCK
SPARE CONTACTS
(PROVISION FOR FUTURE)
COMMON CB ON CB OFF LOCAL MODE EARTH SWITCH INTERLOCKING E.S. OPENED AND E.S. OPENED AND
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

TO METERING PANEL CRANK NOT CRANK NOT


A (SPARE) A
TO INCOMER TO INCOMER INSERTED INSERTED
NO.2 NO.1
-XU 1 -XU 2 -XU 4 -XU 6 -XR1 1 -XR1 3 -XR1 7 -XR1 11 -XR1 13

-XR1 4 -XR1 8

(R101)

(R107)

(R109)
(U2)

(U3)

(U4)

(R103)

(R105)
(R103)
/M01/4.A /M01/4.A
-XB 27 -XB 23 20 26 24 28 26 +CCB 20 +CCB 22
+CB +CB 9 +CB +CB +CB +CB +CB
+LVD 1 2 -QE -BE3 -QE -BE3
-QB -QB -BT5 -BT5 -BX -BT5 -BX
21 27 25 29 27 /M02/3.A 21 /M02/3.A 23
-SS1
B 43 21 LOCAL
10 (R104) B
-BB1 -BB2 /N99/3.B
44 22

(R102)

(R104)

(R106)

(R108)

(R110)
(U1)
-XB 37 -XB 33
/M01/4.D /M01/4.D
-XR1 5 -XR1 9
(U1)

(U1)

-XU 3 -XU 5 -XU 7 -XR1 2 -XR1 6 -XR1 10 -XR1 12 -XR1 14


C C

REF615
RELAY
FAULTY

D -XU1 1 -XU1 3 D
(U101)

(U103)

-X100 3
+LVD 1
-AR30.1 IRF +LVD 1 2

/N01/1.A -SS3 2
OFF
-X100 4 5 /N99/8.D
E E
(U102)

(U104)

-XU1 2 -XU1 4

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SPARE CONTACTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/X01
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: X02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CB SPARE CONTACTS

CB CLOSED CB CLOSED CB OPENED CB OPENED CB IN SERVICE CB IN TEST POSITION CB IN TEST POSITION CB IN SERVICE
This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

POSITION POSITION
A A

-XU2 1 -XU2 3 -XU2 5 -XU2 7 -XU2 9 -XU2 11 -XU2 13


(U201)

(U203)

(U205)

(U207)

(U209)

(U211)

(U213)
/M01/5.A /M01/6.A /M01/6.A /M01/5.A /M01/8.A /M01/8.A /M01/7.A
+CB -XB 28 +CB -XB 9 +CB -XB 7 +CB -XB 6 +CB -XB 55 +CB -XB 57 +CB -XB 52
-QB -QB -QB -QB -QB -QB -QB
B B
31 41 53 13 53 53 23 23
-BB3 -BB3 -BB3 -BB3 -BT1 -BT2 -BT2 -BT1
32 42 54 14 54 54 24 24

-XB 38 -XB 19 -XB 17 -XB 16 -XB 56 -XB 58 -XB 53 -XB 54


/M01/5.D /M01/6.D /M01/6.D /M01/5.D /M01/8.D /M01/8.D /M01/7.D /M01/7.D
(U202)

(U204)

(U206)

(U208)

(U210)

(U212)

(U214)

(U215)
C -XU2 2 -XU2 4 -XU2 6 -XU2 8 -XU2 10 -XU2 12 -XU2 14 -XU2 15 C

REF615 SPARE CONTACTS

D -XU2 16 -XU2 18 -XU2 20 -XU2 22


D
(U216)

(U218)

(U220)

(U222)
-X110 20 -X110 23 -X110 17 -X100 8
+LVD +LVD +LVD +LVD
-AR30.1 SO3 -AR30.1 SO4 -AR30.1 SO2 -AR30.1 PO2
/N01/1.A /N01/1.A /N01/1.A /N01/1.A

-X110 22 21 -X110 24 -X110 19 18 -X100 9

E E
(U217)

(U219)

(U221)

(U223)

-XU2 17 -XU2 19 -XU2 21 -XU2 23

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SPARE CONTACTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/X02
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.: X03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

REF615 PROT.RELAY RS485 COMMUNICATION PORT DPM RS485


This document must not be copied without our written permission, and the contents thereof must not be imported to a third party not be used for any unauthorized purpose. Contravention will be prosecuted.

COMMUNICATION
A PORT A

-XU2(U227) 26 27 28 29 30 31 32 33 34 35

-SH1
-SH2

(U228)

(U229)

(U230)

(U231)

(U232)

(U233)

(U234)

(U235)
-GND -XU2 36 37 38 39 40

(U239)
B B

(U236)

(U237)

(U238)
-SH2
-SH1
-SH1 -GND
-X5 1 2 4 5 6 7 8 9 10
+LVD GND GNDC IRIG-B (-) IRIG-B (+) AGND *COM2 (B-) *COM2 *COM1 (B-) *COM1 B A GND
(CASE) (CASE VIA (ISOLATED / TX (-) (A+) / RX (-) (A+) +LVD
-AR30.2 RS485
CAPASITOR) GROUND) / TX (+) / RX (+) COMMUNICATION PORT
/N02/1.A -PM
RS485 /N99/5.B

C C

SERVICE & TEST SPARE CONTACTS CB PLUG SPARE CONTACTS

ES SPARE CONTACTS
CB IN SERVICE CB IN SERVICE C.B. PLUG NOT C.B. PLUG NOT
POSITION POSITION CONNECTED CONNECTED
ES OFF ES OFF ES ON ES ON
D D
-XU3 1 -XU3 3 -XU3 5 -XU3 7 -XU3 9 -XU3 11 -XU3 13 -XU3 15
(U301)

(U303)

(U305)

(U307)

(U309)

(U311)

(U313)

(U315)
+CCB-QE 44 +CCB-QE 46 +CCB-QE 44 +CCB-QE 46
24 26 20 22
/M02/3.A -BE1 /M02/3.A -BE1 /M02/3.A -BE2 /M02/3.A -BE2 +CB +CB +CB +CB
45 47 45 47 -BT4 -BT4 -BX -BX
25 27 21 23

E E
(U302)

(U304)

(U306)

(U308)

(U310)

(U312)

(U314)

(U316)
-XU3 2 -XU3 4 -XU3 6 -XU3 8 -XU3 10 -XU3 12 -XU3 14 -XU3 16

F F
PROJECT NO.: MY-04511274.A DRAWING NO.: E12070JS DRAWING TITLE: LANGUAGE: ENG
PROJECT TITLE: CUSTOMER: PT ABB SAKTI INDUSTRI TYPICAL BUS SECTION SCALE (A3): 1 : 1
A1 REVISED AS PER COMMENTS 06/06/12 PLN WEST JAVA SPARE CONTACTS DATE: 13/04/2009
A0 FIRST ISSUE 01/06/12 APPROVED: LEE ML CHECKED: CHEE MENG ABB MANUFACTURING SDN BHD SHEET: ==SWG1=J02+WLV/X03
REV. DESCRIPTION DATE DESIGNED: NISHANTH DRAWN: NISHANTH (COMPANY NUMBER: 12651-M), TEL: +60 (3) 5628 4888, TELEFAX: +60 (3) 5631 2920 CONT.:
1 2 3 4 5 6 7 8