Description
ER22005/S & ER11010/S rectifiers, using the advanced power technology and
process, is designed for the DC systems in various transformer substations,
hydropower plants, power plants and other DC power supply applications,
especially for user transformer substation. It features high efficiency, high power
density, high reliability, intelligent control and aesthetic appearance.
The rectifiers are fitted with fans, feature high power density, and are space-saving.
Built-in blocking diode simplifies the system design.
The rectifiers are perfectly used with the specified subrack. You just connect the
subrack input and output cables, easy to use.
300
Output voltage(V)
1200
1000
800
600
400
200
0
-10 0 10 20 30 40 50
Ambient temperature(°C)
UtilitySureTM ER22005/S & ER11010/S DC Power
for Business-Critical Continuity™
Modular Switched Mode Rectifier
Technical Specifications
OUPTUT CHARACTERISTIC FUNCTION
ER22005/S ER11010/S Input Protection ā ā
Output Voltage Over-voltage: No output, self-recoverable
Nominal: 220Vdc 110Vdc Under-voltage: No output, self-recoverable
Rated: 234Vdc 117Vdc Over-current: Built-in fuse
Maximum: 286Vdc 143Vdc Output Protection ā ā
Minimum: 175Vdc 98Vdc Over-voltage: No output, manually recoverable
Output Current Alarm, output available, self-recoverable, through
Low-voltage:
Rated: 5A 10A software
Maximum: 5.5A 11A Hot swappable: Built-in blocking diode
Output power: Max 1430W Short current limit: 110% rated current, self-recoverable
Efficiency: ≥ 91% Over-temperature protection: No output, self-recoverable
Load regulation: ≤ Ġ0.5% Cooling: Forced air
Voltage stabilizing accuracy: ≤ Ġ0.5% Ambient temperature and output current combine
Fan control:
Current stabilizing accuracy: ≤ Ġ1% to control the fan speed
Output current limiting point: 10% to 110%Ir Communication protocol: RS485
Soft start time: 3 to 8 seconds ENVIRONMENTAL
Ripple factor: ≤ 0.1% rms Rated operating temperature: -10ŃC to 40ŃC
Load sharing imbalance: ≤ Ġ5% for 50% to 100% rated load Lowest start temperature: -10ŃC
Audible noise: ≤ 55dB Highest work temperature: 40ŃC
INPUT CHARACTERISTIC Relative humidity: ≤ 95%
Input Voltage Rated air pressure: 70 kPa to 106 kPa
Rated: 220Vac Transp. & stge., temperature: -25ŃC to +65ŃC
Maximum: 286Vac Transp. & stge., RH: ≤ 95%
Minimum: 85Vac (Power limiting for 85Vac to SAFETY
180Vac) Standard: EN 60950-1(CE marked)
Input phases: Single phase Protection level: IP20
Power factor: ≥ 0.99 EMC
Harmonic current: ≤ 5% Emission: GB9254-1998 (CE&RE Class A)
MECHANICAL Immunity: GB/T 17626-1998, IEC61000-4
Width: 72mm RELIABILITY
Height: 145mm MTBF: 250,000 hours (Bellcore TR332)
Depth: 280mm RoHS R5
Weight: ≤ 3kg
280 72
7.3
6
145
124.6
78.6
62
8
29.6
2.5
7
2.2
67.6