Anda di halaman 1dari 5

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/272173478

Three-phase Three Legs Power Transformers Asymmetrical Modes Study for


Zigzag Windings Connection

Conference Paper · May 2014

CITATION READS

1 273

2 authors, including:

Valeriu Bosneaga
Academy of Sciences of Moldova
7 PUBLICATIONS   5 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Flexible Alternating Current Link View project

Transformer modelling View project

All content following this page was uploaded by Valeriu Bosneaga on 13 February 2015.

The user has requested enhancement of the downloaded file.


Three-phase Three Legs Power Transformers
Asymmetrical Modes Study for Zigzag Windings
Connection.
Bosneaga V., Suslov V.
Power Engineering institute, Academy of sciences, Chisinau, Moldova
valeriu.bosneaga@gmail.com
for the case of isolated neutral on the medium voltage side and
Abstract. Based on the previously proposed model the simulations grounded neutral on the low voltage side. For calculations let
were made and characteristic features of steady asymmetric use the catalogue data of Minsk (Belorussia) transformer plant
modes of three-phase core type (three leg) transformer were (http://metz.by/) for distribution transformers for direct
investigated for zigzag winding connection, taking into
sequence. For the transformer type TMG, rated power 100 kVA,
consideration the electromagnetic coupling of windings, located on
different legs. Calculations and analysis were conducted based on rated voltages 10/0.4 kV we have the following data: no load
distribution transformer 100 kVA, 10/0.4 kV and include the most (excitation) current I0 =2,6%, short-circuit voltage Usc= 4,7 %,
typical steady unbalanced conditions, arising at various short no load active power losses Р0=270 W, short circuit losses
circuits, including those, accompanied by the presence of zero Рsc=2270 W.
sequence magnetic flux. For the considered modes vector In addition, for this transformer the manufacturer provided
diagrams of currents and voltages, as well as the relative values of measured from the high voltage (HV) side zero sequence
the magnetic flux were constructed, which provide a clear visual impedance (for the scheme Y/y0) Z0 = 1.3 Ohm, and active
representation of their features. It was demonstrated, that if the power losses at no load conditions P = 2 kW. Based on these
0
numbers of secondary windings turns are unequal, zigzag scheme
data, in accordance with known formulas (see for example [22,
no longer has advantages in asymmetric modes. These advantages
also disappear at single-phase short-circuit of one secondary pp. 185-190]), one can calculate effective (RMS) values of the
winding. Additional measures should be taken for the reliable windings rated currents for HV and low voltage (LV) sides: IHV
protection against such short-circuits and prevention of = 5.8 A and ILV = 152 A, excitation current on HV side I0 =
transformer damage. 0.15 A, rated windings voltages on HV and LV sides UHV=5.77
kV and ULV = 127 V, resistances and winding’s pairs short-
Index Terms- Power Transformer, core type, three limbs, circuit reactance, as well as all other variables, needed to
asymmetric modes, zigzag, zero sequence, magnetic flux. elaborate the model.
A similar version of the transformer is considered, for
I. INTRODUCTION example, in [11], [12]. In [12] it is presented some data on the
values of short-circuit currents for different windings
Investigations and calculations of power transformers connections of distribution transformers with highest voltage of
asymmetrical modes were conducted in many publications, the 6 kV, including for zigzag diagram, but for a correct comparison
basics were laid in the classic books by Petrov G.N., Voldek with results, obtained here, it is necessary to have more detailed
A.I., Vasiutynski S.B., [1]-[4], etc., then the study was data on transformers parameters, used in [12]. For greater
continued in [5]-[10], etc. (the list is not exhaustive). clarity, let us present the results of calculations not in the form
Nevertheless, the publications, developing various aspects of the of tables with values, but rather in the form of vector diagrams
problem, including the creation of new models of three-phase (VD), and numerical values – only as needed. On Fig. 1, 2 are
transformers continue to appear, including in the recent years shown the voltages of the primary and secondary windings of
[13]-[20]. However, there is no publication where it is discussed transformer with zigzag diagram in initial symmetric mode (for
in detail asymmetric modes for the scheme with zigzag windings the case, when the turns numbers of both secondary windings,
connection. To perform this work a three-phase model for three connected in zigzag, are the same). The windings, located on the
limb core transformer, proposed by the authors and described in same limb and belonging to one of the phases are designated by
[21] was used. the letters A, B, C, the numbers 1, 2, 3 refer to the primary and
secondary windings. Accordingly, the loads voltages include the
II. CALCULATION ANS ANALASYS OF ASYMMETRIC MODES notation of windings, which are connected together to obtain the
corresponding load voltage (wherein the first is recorded the
Let us consider with the help of elaborated model typical winding, connected to the neutral point, for example, a load
features of steady asymmetrical modes of three phase, core type voltage U
A2B3).
distribution transformer with zigzag windings connection Y/z0

978-1-4673-6487-4/14/$31.00 ©2014 IEEE


On subsequent figures the obtained results are given in the this mode is shown in Fig.4, from which it is seen, that the sum
form of vector diagrams for various asymmetrical modes of limbs fluxes is close to zero, and hence the zero sequence flux
calculations. Fig. 3 shows the voltages of LV windings and in the air under these conditions is missing, which, as is known,
loads for the single-phase short circuit to ground (shorted load is is a significant advantage of the zigzag connection. In addition,
A2B3), as initial mode is taken the symmetrical loading the calculations fulfilled confirm that the star of HV windings
according to Fig. 1, 2. As it can be seen from VD on Fig. 3, voltages remains symmetrical, and no displacement of the
voltages of "healthy" loads UB2C3 and UC2B3 (shown in dashed neutral is observed. It should be noted, that these beneficial
lines) are somewhat less than the nominal voltage, and the phase
angle is more than conventional of 120°. Voltages system of
secondary windings, forming zigzag (voltage of primary
windings A1,B1,C1 look very similar, so are not shown) is
distorted, wherein the voltages on the shorted windings A2,B3
(as expected ) are equal and much less, than nominal value. The
voltages of remaining windings A3,B2, forming “healthy loads”,
are much lower than the nominal value of 127 V and have a
phase shift much less than normal of 120°, and the voltages of
windings C2, C3 are also equal, and their value is close to 1 r.u.
nominal value. Current of one load phase short-circuit, obtained
here by calculation, is equal to 113 A, this value is
approximately consistent with the result (102 A), presented in
[12], taking into account that in [12] the voltage was equal to 6
kV. Pattern of magnetic fluxes in the limbs of magnetic core for

Fig.4. Relative values of limb’s magnetic fluxes at one phase short-circuit.

properties of zigzag connection only take place in case of the


equal numbers or turns of windings, constituting zigzag (see Fig.
2, voltages UA2=UB3 and so on.). At Fig.5, 6 are presented VD
for the considered mode of short-circuit in one phase of load,
corresponding to the ratio of secondary windings turns of 2:1 (in
this case the angle between load and respective winding voltages
Fig 1. VD of Y-connected prima- Fig.2. VD of loads and secondary will be less than 30°, and will be close to 15°). From Fig.5,
ry windings voltages for windings voltages for zigzag con- which shows the relative values of fluxes in the core limbs, it
symmetric load conditions. nection at symmetrical conditions. follows the appearance in this case of significant zero sequence
flux. Besides, the displacement of neutral point appears at HV
side of the transformer. Dramatically changes not only the
200 V picture of magnetic fluxes in the limbs, but also the VD of
windings voltages and load voltages (see Fig.6).

300 V

Fig. 5. Relative values of fluxes Fig.6. LV windings and loads


in the core limbs at one phase of voltages at one phase of load short-
Fig. 3. VD of loads and secondary windings voltages at short-circuit in one load short-circuit and the ratio of circuit and the ratio of secondary
phase of load. secondary windings turns of 2:1. windings turns of 2:1.
Thus, at different numbers of secondary windings turns, forming The largest short-circuit current in this mode is reached in the
"shoulders" of zigzag connection, the beneficial properties, phase B of the power supply source and is equal to 150 A.
inherent to this scheme in asymmetric modes of operation, Next, let consider short-circuit of two phases of load to
practically are lost. ground. In this case two voltages of load “shoulders” are equal
Let consider next the less likely, but also possible mode of to zero (UА2В3=UВ2С3 =0). At Fig.9, 10 are presented VD,
short-circuit on the LV side between the two arms of load obtained for the considered case. At Fig .9 are presented the LV
without earth. At such fault, obviously, respective voltages will side windings voltages, it is obvious, that at such fault windings
have the same value (UА2В3=UВ2С3). Fig. 7 shows VD for the voltages are decreased further in comparison with previous case,
windings and loads voltages on the LV side at short-circuit but the power source currents still remain balanced and become
between the two arms of loads without earth. The voltage on even more symmetrical, although the largest value of the fault
short-circuited loads sharply decreases and three phase voltages current (see Fig. 10) remains practically the same, as in previous
system on the loads is greatly distorted. case. Power source currents in this mode are more symmetrical,
than at short-circuit of two phases of load without ground, and
also are balanced.
Let consider further for completeness specific unbalanced
mode, associated with possible internal fault in transformer -
namely, short-circuit to ground of one secondary winding on LV
side, adjacent to the neutral (in this case, in phase A). At Fig.11
- 14 are presented VD, obtained as a result of calculations, made
for the considered case. As follows from Fig.11, this shows

250 V

Рис.7. Windings and loads Fig . 8. VD for the source currents


voltages on LV side at short- on HV side at short-circuit between
circuit between two arms of loads the two arms of loads without earth.
without ground.

It is also seen on the VD, that the voltages on B2 and B3


windings coincide and are almost invisible because of their
relatively small value. Besides, the voltages on all LV side
windings are much lower, than the nominal one. As it could be
seen from Fig.8, the sum of source phase currents is zero, which Fig.11. Fault currents from the Fig.12. LV side windings and
power source at short-circuit of loads voltages and currents at
is understandable, since the HV side has no way for the flow of phase A secondary winding short-circuit to ground of phase A
zero sequence current. Due to calculations performed, the (connected to neutral). secondary winding.
neutral current on the LV side is also zero, and, respectively, the fault currents from the power source, they are relatively
there is no zero sequence current in the secondary windings and small in comparison with usual short-circuit currents
no zero sequence flux. (approximately twice bigger than rated current), so, at such fault

Fig. 9. LV side windings voltages at Fig. 10. Source currents on HV Fig.13. HV side windings Fig.14. Relative values of limbs
short-circuit of two phases of load side at short-circuit between two voltages at short-circuit to magnetic fluxes and total zero
to ground. “arms” of loads with ground. ground of phase A secondary sequence air flux at short-circuit to
winding. ground of phase A secondary winding.
the usual protection will not work, but the transformer will be parameters for the positive sequence, also their measured values
overloaded with these currents and could be damaged. So, it for the zero sequence, due to the fact that the latter are difficult
would be desirable to provide protection against this regime. to obtain by calculation.
Loads currents and voltages (see Fig. 12) in this mode are close REFERENCES
to symmetric; the voltages of short-circuited phase A are close
to zero (so, they are not shown on VD), but the voltages of [1] G.N. Petrov. Transformers. Fundamentals of theory. Vol.1, GEI, 1934,
445 pp. (In Russian).
"healthy" windings B2, B3 and C2, C3 are strongly shifted by
[2] G.N. Petrov. Electrical machines. In 3 parts. Part 1. Introduction.
phase relative to their normal positions. From Fig. 13, which Transformers. M. , Energia, 1974, 240 pp.(In Russian). [3] A.I. Voldek.
shows the voltages of the primary star connected windings with Electrical machines. – L.: Energia, 1978, 832 pp.(In Russian).
isolated neutral, it is seen, that the system of primary windings [4] S.B. Vasyutinsky. Problems of theory and design of transformers. L.,
Energia, 1970, 432 pages. (In Russian).
voltages is sufficiently asymmetrical, has essential shift of the
[5] B.N. Sergeenkov. Electrical machines. Transformers. Edited by Kopylov
neutral point and is similar to the VD of secondary voltages. I.P., M. Vishaia shkola, 1989, 352 pp. (In Russian). [6] E.I. Zabudski. Electrical
Furthermore, in this mode, due to calculations made, (see VD machines. Part 1. Transformers. M , 2002, 168 pp.(In Russian).
with results on Fig.14) significant zero sequence flux, caused by [7] S.B. Losev, A.B. Chernin. Calculation of electrical values in asymmetric
modes of electrical systems. M., Energoatomizdat, 1983, 527 pp. (In Russian).
unbalanced windings currents, appeared.
[8] A.P. Berman. Calculation of asymmetric modes of electrical systems
using phase coordinates. Elektrichestvo, 1985, number 12 , pp. 6-12. (In
III. CONCLUSIONS Russian). [9] A.M Guseynov. Calculation of asymmetric steady-state
1. Based on elaborated model the calculation of modules and modes in complex systems using phase coordinates. Elektrichestvo, 1989, Nr.
3.(In Russian). [10] D.D. Karasev, E.D. Karasev. Calculation of electrical
angles of windings currents and voltages in three-phase three
networks with “FAZAN” software. Editor A.I. Artemov. Moscow: Moscow
limb core transformer with "zigzag" connection of secondary Power Engineering Institute, 1989.(In Russian).
windings at various short-circuit modes was performed. [11] B. Fishman, A. Fedorovskaia. Power transformers 10 (6 ) / 0.4 kV. Areas
Electromagnetic coupling between windings on different limbs, of application of different connection schemes. Novosti Elektrotehniki, Nr.5,
2006. (In Russian). [12] B. Fishman, A. Fedorovskaia. Power
based on zero sequence parameters, was considered. Obtained
transformers 10 (6 ) / 0.4 kV. Areas of application of different connection
vector diagrams for windings voltages and currents and relative schemes . Novosti Elektrotehniki, Nr.6 (60), 2009. (In Russian). [13]
values of magnetic fluxes give clear visual representation of G.A. Evdokunin, M.V. Dmitriev. Transformers in the electrical network.
different asymmetric modes peculiarities. Simulation of transient processes taking into account the configuration of
magnetic system. Novosti Elektrotehnik" Nr. 5 (53), 2008. (In Russian). [14]
2. At usual single-phase and two-phase short-circuits the
V.P Zakaryukin, A.V. Kriukov. Complicated asymmetric modes of
"zigzag" connection (at equal secondary windings turns number) electrical systems. Publisher Irkutsk State University, 2005 - 274 p. (Transformer
ensures absence of zero-sequence current and flux and, model – at page 45.), (In Russian). [15] A.S. Gusev, S.V. Svechkarev, I.L.
accordingly, less distortion of voltages and currents (in Plodisty. Universal mathematical model of three-phase transformers and auto-
transformers. Bulletin of the Tomsk Polytechnic University. 2007. Vol. 311. – Nr.
comparison with Y/y and D/y connections) at asymmetric short-
4, pp.77-81. (In Russian).
circuits and loads. However, if the numbers of secondary [16] V.A. Martynov. Unbalanced modes of power transformers with windings
windings turns are unequal, this scheme no longer has connection Y/y0. Bulletin of Irkutsk State Power University, issue 2, 2009, pp. 1-
mentioned advantages. Furthermore, these advantages also 5.(In Russian). [17] M. Iu. Pustovetov. Mathematical model of three-phase
transformer, Proceedings of Tomsk Polytechnic University. 2012. Vol. 321. Nr.4.
disappear at single-phase short-circuit of one secondary
(In Russian).
winding, that, in turn, seemingly means, that a similar effect will [18] Three-Phase Transformer Inductance Matrix Type (Two Windings). 2012.
also occur at internal short-circuits between loops in the URL:http://www.mathworks.com/help/toolbox/physmod/powersys/ref/threephas
windings. etransformerinductancematrixtypetwowindings.html (date of access:
06.04.2012).
3. The currents, arising from short-circuit of one secondary
[19] Three-Phase Transformer 12 Terminals. 2012. URL:http://www.-
winding, are approximately twice bigger than rated load currents mathworks.com/help/toolbox/physmod/powersys/ref/threephasetransformer12ter
and are significantly smaller, than usual short-circuit currents. minals.html (date accessed: 06.04.2012).
Due to this, they are insufficient for the reliable operation of [20] URL:http://www.mathworks.com/help/physmod/powersys/ref/threephase-
transformer-inductancematrixtypethreewindings.html (date of access:
protection against short-circuits, so this may require additional
20.09.2013).
measures to protect against such faults and prevent transformer [21] V.A. Bosneaga, V.M. Suslov. Investigation of asymmetrical modes of
damage. three-phase three leg transformer with windings connection in zigzag.(In
4. To enable more accurate accounting of asymmetric modes Russian) (http://journal.ie.asm.md/en/contents/elektronnyij-zhurnal-n-323-
2013). [22]Electrical Engineering Handbook: In 3 volumes, Vol. 2. M,
processes associated with the appearance of zero sequence
Energoatomizdat , 1986, 712 pp.(In Russian).
current and magnetic flux, transformer manufacturers should
present in the catalogue data sheets of transformers, along with

View publication stats

Anda mungkin juga menyukai