Anda di halaman 1dari 14

TECHNICAL SPECIFICATIONS

Parameters Specification
Model ALM 36

Number of Channels 4U/4I

Voltage (TRMS AC + DC) per Phase-Phase 2V to 2000V

Voltage (TRMS AC + DC) per Phase-Neutral 2V to 1000V

Voltage Ratio Up to 500kV

Current (TRMS AC + DC) 5mA to 10,000Aac / 50mA to 5,000Adc (depending on Clamp)

Current Ratio Up to 60kA

Frequency 40 to 69Hz

Power values W, VA, VAr, VAD, PF, DPF, cosφ, tanφ

Energy values Wh, VArh, Vah, Dh

Harmonics, THD on V, U, I, VA & In up to 50th order

Transients 210

Flicker (Pst & Plt) Pst & Plt

Inrush mode > 10 Min

Alarms 10,000 Events

Min/Max Recording Yes


st
Storage Capacity for a selection of parameters at 1 Interval 2 Weeks to Several Years

Phasor Diagram Yes on Instrument & on PC

Vectorial representation Automatic

Display Colour ¼ VGA TFT screen, 320 x 240, diagonal 148mm

Capture of screen snapshots 50

Electrical safety IEC 61010 - 1000V CAT III / 600V CAT IV

Protection IP 53 / IK 08

Communication Interface USB

Battery life Up to 13 Hours

Power supply 9.6V Ni-Mh Re-Chargeable battery or external mains charger

Dimensions 240 x 180 x 55 mm

Weight 1.9kg

21
Ampflex A193 Ampflex A193 Mini Ampflex
Specification/ Model MN 93
450mm 800mm MA193

Internal Dia (mm) 140mm 250mm 70mm 20mm

Maximum Current 10,000Aac 10,000Aac 10,000Aac 240Aac

Measurement Range 100mA to 10,000Aac (measures from 10A when used on ALM 10) 1A to 200Aac

0.5A to 10A :
10A to 100A : ±3% 10A to 100A : ±3% 10A to 100A : ±3%
±(3% + 1A)

10A to 100A :
100 to 10,000A : ±2% 100 to 10,000A : ±2% 100 to 10,000A : ±2%
±(2.5% + 1A)
Accuracy
100A to 240A :
±(1% + 1A)

CAT IV 600V/ CAT IV 600V/ CAT III CAT IV 600V/ CAT IV 300V/
Safety
CAT III 1000V 1000V CAT III 1000V CAT III 600V
145

140

135
V

130

125

120

12/03/2014 19.878 (s) 12/03/2014


16:02:52.214 3 s/Div 16:03:12.092

Anda mungkin juga menyukai