TECHNICAL SPECIFICATION & FEATURE: TAVR‐30
VOLTAGE 240V AC ± 10%
INPUT POWER
FREQUENCY 50/60 Hz
VOLTAGE 95V DC ± 5Vat 240V AC
OUTPUT POWER 6 Amps continuous
CURRENT
8Amps for 30sec
VOLTAGE
SENSING INPUT 3 Phase: 415V AC line to line rms.
BUILD‐UP VOLTAGE From a residual of ≤2V at power
VOLTAGE
input terminals of AVR
VOLTAGE REGULATION % REGULATION ≤ ±0.8% at AVR terminals
Adjustment to get steady state stability and good
STABILITY STABILITY
transient response.
ADJUSTMENT
VOLTAGE ±12% of rated voltage
VOLTAGE VARIATION
RESPONSE TIME TIME ≤ 50milli seconds.
CLOSED
LOOPED Typically 0.5 secs to recover 98% of the set
TIME
RESPONSE voltage for a field forcing ratio of 1:2.
THERMAL DRIFT
VOLTAGE ≤ ±1% 30ºC change in Ambient
OPERATING ‐20ºC to + 70ºC
TEMERATURE
TEMPERATURE
FUSE PROTECTION
6A,240V AC
Adjustable between ≤40 Hz to ≥60 Hz for 50 Hz
FREQUENCY ROLL OFF Operation when50/60 Hz link short.
WITH LED INDICATION
Adjustable between ≤40 Hz to ≥70 Hz for 60 Hz
Operation when50/60 Hz link Open.
www.sanelec.in Confidential 1
TECHNICAL SPECIFICATION & FEATURE: TAVR‐30 AUGUST 2010
OVER EXCITATION LIMIT
WITH LED INDICATION Settable between 10V to 85V DC
SENSE LOSS PROTECTION Generator voltage goes to low level when sensing
WITH LED PROTECTION
open.
DROOP ADJUSTMENT
Adjustable to get 4% droop for 5A from ‘W’ phase.
ACCESSORY INPUT
To Change the terminal voltage by ±10% for ± 4.5V
DC (Isolated supply)
OVERALL 135 X 110 X 48 in mm
DIMENSIONS (in mm) MOUNTING 115 X 90 in mm
MOUNTING HOLE DIA 9mm
WEIGHT 320 gm(approximately)