Instruction Leaflet IL032049EN Effective May 2015

115E-2 Ethernet networking I/O and gateway


installation guide

 WARNING - EXPLOSION HAZARD


Do not disconnect the device while the circuit is live unless the area
is known to be non-hazardous.

Connecting to the module for configuration


The default settings for the 115E-2 are as follows:
• IP Address: 192.168.0.1XX, where “XX” is the last two digits
of the serial number shown on the printed label on the side of
the module
• Subnet Mask: 255.255.255.0
• Default Gateway: 192.168.0.1
• Username: user
• Password: user
1. Connect a straight-through Ethernet cable between the
module’s Ethernet port and a PC.
2. Open Internet Explorer on the PC.
3. Type “http://” followed by the IP address of the module and
press Enter.
The configuration Web page is displayed. If this Web page
does not appear, see the user manual.
Instruction Leaflet IL032049EN 115E-2 Ethernet networking I/O and gateway installation guide
Effective May 2015 

NOTE Configuration switches
All connections must be SELV <50 Vac and <120 Vdc. Use the DIP switches in the
side access panel to select
The following illustrations show the ports on the 115E 2. analog input voltage and Side
current, external boot, and Access
default configuration settings. Panel
PWR

LED Indicator
LAN
232
DIP DESCRIPTION
485
Lights Factory Boot
1 AI3 current/voltage
Switch
2 AI3 current/voltage USB Host
3 AI4 current/voltage
Configuration
I/O Connectors 4 AI4 current/voltage
Switches
5 Unused
6 Enables default configuration

Input and output connections


The digital input/output channels can be wired as inputs or outputs.
USB Port RS-232 Port Digital input Digital output
D1 D2 D3 D4 D5 D6 D7 D8 GND +24V D1 D2 D3 D4 D5 D6 D7 D8 GND +24V

GND BAT SUP SUP


B A - + + - +

ETHERNET USB RS232 SUPPLY

Transistor
Switch
RJ-45 Ethernet Port Device
(connects to hub or switch) DC Load

Power supply wiring GND BAT SUP SUP


Voltage-free Contact
+ - + + –
The ground (GND) and “SUP –“
TTL CMOS
terminals are connected Output
internally to the ground terminal. USB RS232 SUPPLY

Differential current inputs (Al1, Al2) Single-ended current input (Al3, Al4)
Connect the screw terminal on
the end plate to ground for surge AI1 AI1
D7 D8 GND +24V +
_ AI2
+
AI2
_
AO1 AO2
AI3 AI4 + + GND +24V
AI1 AI1
GND +24V +
_ AI2
+
AI2
_
AO1 AO2
AI3 AI4 + + GND +24V
protection. Optional –
10.8–15 Vdc 3A Fuse
Lead Acid
Battery +

mA mA
15-30 Vdc Externally
Supply Exernally Powered
Powered Loop-Powered Loop-Powered Sensor
Sensor Sensor Sensor
Power Supply ON
Power Supply

Expanson I/O power and RS‑485 serial connection 1 2 3 4 5 6

DIP Switch Setting


for Current IP
An on-board RS‑485
B A - +
terminating resistor provides Analog output Single-ended voltage input
line attenuation for long runs.
AI1 AI1 AI2 AI2 AO1 AO2 AI1 AI1 AI2 AI2 AO1 AO2
+ _ + _
AI3 AI4 + + GND +24V + _ + _
AI3 AI4 + + GND +24V
Place terminating resisters B A ETHERNET USB RS232
+24V

at each end of the RS‑485 RS-485

cable.

115S-xx 115S-xx
0–5 Vdc
Sensor
B A - + B A - +

V
0–25V
AI COM Sensor
V
ON
Eaton
1000 Eaton Boulevard PLC
1 2 3 4 5 6
Cleveland, OH 44122
United States
DIP Switch Setting
© 2015 Eaton for Voltage IP
Eaton.com
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Eaton’s wireless business Publication No. IL032049EN All other trademarks are property
www.eaton.com/wireless May 2015 of their respective owners.