Anda di halaman 1dari 5

 

Annexure ‐ I 
GUARANTEED TECHNICAL PARTICULARS FOR DISTRIBUTION TRANSFORMER 
 
Sl. 
Description  Offered 
No. 
1  Make  Shilchar Technologies Ltd. 
2  Name of Manufacturer  Shilchar Technologies Ltd. 
3  Place of Manufacture  Vadodara 
4  Reference standard  IS 1180 / IS 2026 / IS 335 
5  Service (indoor/outdoor)  Outdoor 
6  Voltage Ratio  11/0.433 kV 
7  Rating in kVA  252 kVA 
8  Rated Frequency (Hz)  50 Hz 
9  Number of phases  3 
10  Vector group  Dyn11 
11  a) Core Material used and Grade  M4 or better 
  b) Flux density  1.69 Tesla (Max) 
c) Over fluxing without saturation (Curve to be furnished by the 
  DDE 
manufacturer in support of his claim) 
12  Maximum temperature rise of:   
  a) Winding by resistance method (0C)  550C 
  b) Oil by thermometer (0C)  500C 
13  Magnetizing (No‐load) current at :   
  a) 90%  <2 % of FLRC 
  b) 100%  <3 % of FLRC 
  c) 110%  <5 % of FLRC 
14  Core loss in watts   
  a) Normal voltage  330 Watts * 
  b) Maximum voltage  330 Watts * 
15  Resistance of windings at 200C (with 5% tolerance)   
  a) HV Windings (ohms)  DDE 
  b) LV Windings (ohms)  DDE 
16  Full load losses (watt) at 750C  2360 Watts * 
17  Total losses at 100% load at 750C  2700 Watts (Max) 
18  Total losses at 50% load at 750C  920 Watts (Max) 
19  Current density used for : (Ampere/Sq.mm)   
  a) HV Winding   2.5 A/mm² (Max) 
  b)  LV winding  2.5 A/mm² (Max) 
20  a) Clearances : mm (in oil)   
  a) Core and LV  3 
  b) LV & HV  9 

REG. OFFIC:BIL ROAD, BIL,VADODARA - 391 410, GUJARAT,INDIA.


WORKS: NEAR MUVAL SUB STATION, PADRA JAMBUSAR HIGHWAY, GAVASAD, VADODARA – 391430
PHONE: 0265-2680466, 2680566 (BIL PLANT), 7624090901/2 (GAVASAD PLANT)
E-MAIL: info@shilchar.com WEBSITE: shilchar.com
CIN:L29308GJ1986PLC008387
  c) HV Phase to Phase  8 
  d) End insulation clearance to earth  10 
  e) Any point of winding to tank  35 
  ii) Clearances : mm (in air)   
a) HV ‐ Phase to Phase 
  As per CBIP 
        Phase to Earth 
b) LV ‐ Phase to Phase 
  As per CBIP 
       Phase to Earth 
21  Efficiency at 750C (@ Unity P.F. and0.8 P.F.)  Unity P.F.  0.8 P.F. 
  a) 125% load  98.73% 98.42%
  b) 100% load  98.94% 98.67%
  c)  75% load  99.12% 98.91%
  d)  50% load  99.27% 99.09%
  e)  25% load  99.24% 99.05%
22  Regulation at :   
  a) Unity P.F. and  1.04%
  b) 0.8 P.F. at 750C  3.44%
23  % Impedance at 750C  4.5% ( Sub. to IS Tol.) 
24  Tap changing gear:   
As per STL’s approved 
  a) Make 
Vendor List. 
  b) Type of tap changer  Off circuit 
  c) Step voltage  in steps of 2.5%
  d) Total tap range (+) percent to (‐) percent  +5% to -10%
  e) Tappings provided at  HV winding 
25  Permissible overloading  As per IS 6600 
Noise level when energized at normal voltage and normal frequency at no‐
26  As per NEMA 
load (db) 
27  Insulation level in kV   
  a) Nominal system voltage (NSV)  Class A 
  b) Highest system voltage (HSV)  Class A 
  c) Power frequency withstand voltage  HV : 28 kV & LV : 3 kV 
  d) Lightning impulse withstand voltage  HV : 75 kV & LV : NA 
28  Mass of : (kg)   
  a) Core lamination (minimum)  540 kg. (Approx) 
  b) Windings (minimum)  155 kg. (Approx) 
  c) Tank and fittings  460 kg. (Approx) 
  d) Oil  440 kg. (Approx)
  e) Oil quantity (minimum ) (litre)  530 Ltr. (Approx)
  f) Total weight  1925 kg. (Approx)
29  Oil Data:   
  1. Quantity for first filling (minimum) (litre)  530 Ltr. (Approx) 

REG. OFFIC:BIL ROAD, BIL,VADODARA - 391 410, GUJARAT,INDIA.


WORKS: NEAR MUVAL SUB STATION, PADRA JAMBUSAR HIGHWAY, GAVASAD, VADODARA – 391430
PHONE: 0265-2680466, 2680566 (BIL PLANT), 7624090901/2 (GAVASAD PLANT)
E-MAIL: info@shilchar.com WEBSITE: shilchar.com
CIN:L29308GJ1986PLC008387
  2. Grade of oil used  As per IS 335 
  3. Maker’s name  Apar / Savita 
  4. BDV at the time of filling (kV)  60 kV 
  5. Water content at the time of filling (in PPM)  As per IS 335 
30  Transformer:   
  a) Overall length x breadth x height (mm x mm x mm)  DDE 
  b) Tank length x breadth x height  DDE 
  c) Thickness of plates for   
  i) Side plate (min)  3.15 mm 
  ii) Top and bottom plate (min)  4 mm 
  d) Conservator dimensions  DDE 
31  Radiation:   
  a) Heat dissipation by tank walls excluding top and bottom  DDE
  b) Heat dissipation by cooling tube  DDE
  c) Diameter and thickness of cooling tube  DDE
  d) Total radiating surface in square metre  DDE
e) Whether  calculation  sheet  for  selecting  cooling  area  to  ensure  that  DDE
  the transformer is capable of giving continuous rated output without 
exceeding temperature rise is enclosed. 
32  Inter layer insulation provided in design for :   
  a) Top and bottom layer  Kraft  Paper 
  b) In between all layer  Kraft  Paper 
  c) Details of end insulation  PCB 
  d) Whether wedges are provided at 50% turns of the HV coil.  Provided 
33  Insulation materials provided   
  a) For conductors   
  i. HV  Paper covering 
  ii. LV  Paper covering 
  b) For core  Carlite 
34  Material and size of the conductor used and current density   
  a) HV Dia (mm) SWG  DDE 
  b) LV     i) Strip size  DDE
            ii) No. of conductors in parallel  DDE
iii) Total area of cross section (all particulars as required in  DDE
 
tender). 
c) Current density ‐ HV 
  2.5 A/mm² (Max) 
                                   LV 
  d) Material of winding conductor  Copper 
35  Whether the name plate gives all particulars as required in tender  Confirmed 
36  Particulars of bushings HV/LV   
  a) Maker’s name  As per STL’s approved 

REG. OFFIC:BIL ROAD, BIL,VADODARA - 391 410, GUJARAT,INDIA.


WORKS: NEAR MUVAL SUB STATION, PADRA JAMBUSAR HIGHWAY, GAVASAD, VADODARA – 391430
PHONE: 0265-2680466, 2680566 (BIL PLANT), 7624090901/2 (GAVASAD PLANT)
E-MAIL: info@shilchar.com WEBSITE: shilchar.com
CIN:L29308GJ1986PLC008387
Vendor List. 
HV : Porceling & LV : 
  b) Type 
Epoxy 
HV: 12 kV, 250 A &                 
  c) Current Rating (Amps)/Voltage rating (kV) 
LV: 1.1 kV, 630 A 
  d) Dry power frequency withstand voltage (kVrms)  HV : 28 kV & LV : 3 kV 
  e) Wet power frequency withstand voltage (kV rms)  HV : 28 kV & LV : 3 kV 
  f) Lightning impulse withstand voltage (kVp)  HV : 75 kV & LV : NA 
  g) Creepage distance (mm)  25 mm/kV 
37  Type of insulation used in   
  a) HV windings  Class A 
  b) LV windings  Class A 
38  Type of insulation used on    
  a) Core bolts  NA 
  b) Core bolt washers  NA 
  c) Core laminations  Carlite 
39  Vacuum to which the tank can be subjected without distortion (torr)  As per CBIP 
40  Weight of insulated conductor    
  a) HV  DDE 
  b) LV  DDE 
41  a. Weight of core  DDE 
  b. Tolerance   DDE 
42  Weight of complete Transformer for transport   1925 kg. (Approx) 
43  Period for which this design of transformer has been in commercial use.  Not Applicable 
Reactance of windings at 750C/ph 
44  DDE 
a. HV        b. LV 
Resistance of windings at rated current and frequency  
45  DDE 
a. HV     b. LV 
Type & size of Gas operated relay and whether supervisory alarm and trip 
46  Will be provided 
contacts provided. 
Temperature indicators    
48  a) Oil temperature      b) Winding temperature      Will be provided 
 indicator                          indicator 
As per STL’s approved 
  i) Make & type 
Vendor List. 
  ii) Permissible setting ranges for alarm & trip  DDE 
  iii) No. of contacts  2 No. 
  iv) Current rating of each contact  1/2/5 A 
49  Ratio and type of CT used for winding temperature   
  a) Ratio  335/5A 
  b) Type  Ring type 

REG. OFFIC:BIL ROAD, BIL,VADODARA - 391 410, GUJARAT,INDIA.


WORKS: NEAR MUVAL SUB STATION, PADRA JAMBUSAR HIGHWAY, GAVASAD, VADODARA – 391430
PHONE: 0265-2680466, 2680566 (BIL PLANT), 7624090901/2 (GAVASAD PLANT)
E-MAIL: info@shilchar.com WEBSITE: shilchar.com
CIN:L29308GJ1986PLC008387
50  No. of Breathers provided (Nos.)  1 
51  Type of dehydrating agent used for breathers  Silica Gel 
52  a) Type , make and number of pressure relief device  Without contact 
  b) Minimum pressure at which the device operates, Kg/cm2  DDE 
53  Valves ‐ sizes and numbers required/fitted   
  a) Drain cum sampling valve  DDE 
     b)   Fitter valve  DDE 
54  Characteristics of insulating oil to be used   
  a. Appearance  As per IS 335 
  b. Density (Max) at 20° C  As per IS 335
  c. Kinematic viscosity (max)  As per IS 335
  d. Interfacial tension   As per IS 335
  e. Flash point (Min)  As per IS 335
  f. Neutralization value   As per IS 335 
i) Total acidity (Max) 
ii) Inorganic acidity/Alkalinity  
  a. Pour point (max)  As per IS 335
  b. Corrosive sulphur  As per IS 335
  i. Electric strength (break down voltage (min) with 2.5mm gap)  As per IS 335
i) New Unfiltered oil as in received     condition.  
ii) After filtration. 
  j. Dielectric dissipation factor (tan delta) at 90°C (Max)  As per IS 335
  k. Water content (Max)  As per IS 335
  l.Specific Resistance (Min) (Resistivity)  As per IS 335
i)  At 90°C (min) 
ii) At 27°C (min) 
  m. Oxidation Stability  As per IS 335
i) Neutralization value after oxidation (Max.) 
ii) Total sludge after oxidation (Max.) 
  n. Ageing characteristics after accelerated ageing (Open breaker method  As per IS 335
with copper catalyst) 
a) Resistivity at 27°C 
b) Resistivity at 90°C 
c) Dielectric loss factor (tan delta) at 90°C 
d) Total acidity mg KOH/g 
e) Sludge Content (Max.) 
  o. Presence of oxidation inhibitor (Percent by weight)  As per IS 335
55  Date  of  commencement  of  production  of  distribution  transformer  at  the  After Drawing 
factory of the supplier  approval 
*  Efficiency and Regulations figs mentioned above are the calculated values based on the estimated component loss figs of No load 
loss and load loss which is subject to vary during detailed engineering after receipt of an order. However our commitment remains to 
meet the total losses at 50% load and at 100% load as per energy efficiency level 2 losses of IS‐1180. 

REG. OFFIC:BIL ROAD, BIL,VADODARA - 391 410, GUJARAT,INDIA.


WORKS: NEAR MUVAL SUB STATION, PADRA JAMBUSAR HIGHWAY, GAVASAD, VADODARA – 391430
PHONE: 0265-2680466, 2680566 (BIL PLANT), 7624090901/2 (GAVASAD PLANT)
E-MAIL: info@shilchar.com WEBSITE: shilchar.com
CIN:L29308GJ1986PLC008387

Anda mungkin juga menyukai