VMT, Baddi unit has sent a proposal for installation of an AC Drive for varying the
motor speed for controlling the suction pressure instead of closing the damper in duct.
Site was visited on 17/4/09 and data of electrical parameters was recorded using
Portable Load Manager on the 55 KW Danfoss make drive installed for trial purpose.
R Y B
THD (Voltage) % 6.3 6.5 6.1
THD (Current) % 29.3 32.6 31.9
The unit is operating the system at 44 HZ since 25/9/2008 and facing no problem
in the working shed.
Some time the fan motor is operated at 48HZ and payback calculations are given
below:-