Anda di halaman 1dari 4

FROM DATA SHEET

PUMP TAG NO =
No of Identical Pumps = 2
WT OF PUMP/MOTOR ASSY. T = 0.3
NO OF POCKETS IN X = 3
NO OF POCKETS IN Y = 2
C/C OF POCKETS IN X mm = 1000
C/C OF POCKETS IN Y mm = 1000
SIZE OF SQ. POCKETS IN X*Y*Z mm = 250 250
SIZE OF BASE PLATE IN X mm = 2400
SIZE OF BASE PLATE IN Y mm = 1400

LEVELS
GROUT THICKNESS mm 50
T. O. PEDESTAL m = 100.300
H.P.P m = 100.000
N.G.L m = 99.500
B. O. FOOTING m = 98.400
FOOTINGTHICKNESS m = 0
MACHINE AXIS HEIGHT m = 101
NET SAFE BEARING CAPACITY T/m2 = 5

FOUNDATION SIZE PROVIDED REQUIRED


SIZE OF PEDESTAL IN X mm = 2600 2500
SIZE OF PEDESTAL IN Y mm = 1600 1500
SIZE OF FOOTING IN X mm = 2600 2900
SIZE OF FOOTING IN Y mm = 1600 1900

CHECK FOR 3 TIMES WEIGHT


WT OF FOOTING T = 2.6 x 1.6 x (100.3 - 98.4 - 0 ) x 2.5 + 2.6 x 1.6 x
= 19.76 >
FORCE CALCULATION
WT OF OVERBURDEN SOIL AT EL.98.4 T = 0 (Top of FDN)
Vertical Force (FDN + PUMP + SOIL) T = 20.06
Addl. Vertical Force V1 T = 0.045 (0.15 x 0.3)
Total Vertical Force Pt T = 20.105
Longitudinal Horizontal Force H1 T = 0.024 (0.08 x 0.3)
Transverse Horizontal Force H2 T = 0.045 (0.15 x 0.3)
Mx H2(h+h1) T-m = 0.1170
My H1(h+h1) T-m = 0.0624
ey Mx / Pt m = 0.0058
ex My / Pt m = 0.0031

BASE PRESSURE CALCULATION IN (T/m2)


AT B. O. FOUNDATION LEVEL
SAFE 0.490 0.374 SAFE

SAFE 0.356 0.361 SAFE

MTO (FOR 2 NOS)


Vol of Concrete m3 = 15.1
Vol of PCC 75 thk at bottom m 3
= 0.9

R/F CALCULATION FOR BLOCK


The block is assumed to be under direct compression, only skin reinforcement
Provide: 12 Ø @ 150 c/c = 34 Kg/m3 SATISFIED

length of reinforement :
28000 24000
32500 22500
19250 19500

PLAN ELEVATION
T.O.PED h1
H.P.P h2
h3 h
Z
B.O.F t
X

ELEVATION

a
400
b d

Y c
X PLAN

UNIT WT OF CONC = 2.5 t/m3


UNIT WT OF SOIL = 1.8 t/m3

00.3 - 98.4 - 0 ) x 2.5 + 2.6 x 1.6 x 0 x 2.5


3 x0.3=0.9 SATISFIED

(Top of FDN)

(0.15 x 0.3)

(0.08 x 0.3)
(0.15 x 0.3) As Per EIL Design Guide No.
8-16-48-1004
@ 25 Kg/m3 is required.

ELEVATION