TITLE :DATA SHEET FOR ULTRASONIC FLARE METER

1 Tag No. FT-9601


2 Line No. 500-FL-A1A-9608
GENERAL

3 Line Size & Thk./Sch. 500NB & Sch20


4 Service Flare
5 P&ID No
6 Quantity 1No
7 Type *
8 End Conn.:Size:Size & Rating *
9 Facing & Finish *
10 Pulses / m3 *
METER / TRANSDUCER

11 Flow Range MMSCFD 0-25


12 Enclosure IP 65
13 Cable Entry 1/2'' NPT(F)/*
14 Material - Body SS 316
15 Material - End Connection *
16 Bi - Directional No
17 Radiography test --
18 Accuracy ±1% OF Reading/*
19 Linearity / Repeatability ±0.25% | ±0.25% of Reading
20 Type 2- wire type, SMART, HART
24 VDC,2 wire Loop powered (9-32 VDC) / 1/2''
21 Power Supply ¦ Cable Entry
NPT(F)/*
22 Enclosure Weather proof to IP-65
23 Intrinsically Safe -
TRANSMITTER

24 Hazardous Area Classification& Certificate IEC Zone 2 Group IIA ,IIB Temp class T3/FM/UL*

25 Transmitter type & Output SMART, HART,4-20 mA DC


26 Mounting 2" Pipe mounting /*
27 Meter Runs *
28 Flow Conditioner *
29 Retractable Probes *
30 Press. Tap on Meter Body *
31 Fluid & State Flare & Gaseous
SERVICE CONDITIONS

32 Flow - Min Max/Min MMSCFD 12/8/'1


33 Pressure Max/Nor/Min KG/CM2 1.5/0.7/0.3
34 Temperature. Max/Nor/Min °C 120/115/0
35 Specific Gravity 0.09
36 Compressibility factor 0.99
37 Molecular Weight 17.4-155.3
38 CP/ CV *
39 Make *
40 Model Number *
NOTES; * Vendor to specify
1 Vendor to confirm the meter size.Also furnish sizing calculation for the given process conditions.
2 Vendor shall supply transmitters compatible to HART protocol.
3 The transmitters shall have tag number plates firmly attached at a visible place.
4 Vendor to quote the recommended “Spares part “ for 2 years of operation
5 All Mandatory spares shall be packed separately in a separate packing .
6 Deviation if any w.r. t. above specification to be categorically mentioned in the offer .
7 Vendor shall supply mounting accessories suitable for 2" pipe along with the transmitter.
8 Calibration certificate required