ELECTRICAL NOTES:

1. ALL WORKS SHALL COMPLY W/ THE LATEST PROVISION OF THE LATEST EDITION OF THE PHILIPPINE AND
NATIONAL ELECTRICAL CODES W/ THE RULES AND REGULATIONS OF THE NATIONAL AND LOCAL
AUTHORITIES CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCES AND W/ THE
RULES AND REGULATIONS OF THE POWER COMPANY CONCERNED.
5
PNL 2
2. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF THE DULY QUALIFIED AND
COMPETENT LICENSED ELECTRICAL ENGINEER.
REF
2
PNL 2
1
PNL 2
3. ALL MATERIALS AND EQUIPMENT TO BE USED SHALL BE NEW AND APPROVED TYPE FOR LOCATION AND
PURPOSES.
RCLT

RCLT RCLT RCLT

s1
4. THE SERVICE ENTRANCE SHALL BE SINGLE PHASE 240 VAC 60 Hz IN uPVC / IMC CONDUIT ( COMPLETING TO
THE POWER UTILITIES REQUIREMENT AND STANDARD ).
s2
5. WHENEVER REQUIRED AND NECESSARY PULL BOXES AND JUNCTION BOXES GAUGE NO.16 SHALL BE
INSTALLED AT CONVENIENT SPACE AND LOCATION.
UP UP
6. ALL PANEL BOARDS SHALL BE BREAKER TYPE ENCLOSED IN METAL CABINET PANEL SHALLBE BOLT-ON
INDUSTRIAL TYPE, FOR LIGHTNING ADD EMERGENCY PANEL SHALLBE BOLT-ON COMMERCIAL TYPE AS
MANUFACTURED BY "G.E." OR APPROVED EQUAL.

7. ALL COVENIENCE OUTLET, 3 PRONG ( PARALLEL SLOT , GROUNDING TYPE ) AND LIGHTNING SWITCHES SHALL
BE RATED 15 A, 25OV, AND 10A, 250V, RESPECTIVELY AS MANUFACTURED BY " NATIONAL "OR APPROVED
EQUAL.

8. THE MINIMUM SIZE OF WIRES AND CONDUIT SHALL BE 3.5 Sq. mm. IN TYPE THIN COPPER AND 15mm. DIA
RESPECTIVELY ( REFER TO LOAD SCHEDULE FOR OTHER WIRE SIZES AND TYPE OF INSULATION.
6
PNL 2

s3
9. FOR EACH SPARE BRANCH CURCUIT IN PANEL BOARD PROVIDE ONE15mm. DIA EMPTY CONDUIT
CONNECTED TO AN OCTAGONAL BOX AT ABOVE CEILING.
SERVICE

10. ALL FEDERS AND BRACH CURCUIT SHALL BE INSTALLED AS INDICATED ON PLAN INDIVIDUAL CURCUIT
HOMERUNS TO PANEL BOARD SHALL NOT COMBINED IN THE SAME RACEWAY UNLESS OTHERWISE
INDICATED ON THE PLAN.

11. THE CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF SERVICE ENTANCE FOR CONNECTION TO THE
POWER SUPPLY AND ALSO THE ACTUAL LOCATION OF TELEPHONE SERVICE REQUIREMENT FOR THE
CONNECTION TO MAIN TELEPHONE CABINET.

12. THE METHOD OF WIRING SHALL BE AS FOLLOWS :

· POWER SERVICE ENTRANCE uPVC CONDUIT ( EMERALD OR NELTEX )


· MAIN FEEDER, FEEDER & SUB-FEEDER uPVC CONDUIT ( EMERALD OR NELTEX )
· LIGHTNING AND CONVENIENCE OUTLET uPVC CONDUIT ( EMERELD OR NELTEX)
· CABLE TV PVC PIPE ( EMERALD OR NELTEX )
· FIRE ALARM SYSTEM / BURGLAR ALARM SYSTEM PVC PIPE ( EMERALD OR NELTEX )
· TELEPHONE & PAGING SYSTEM PVC CONDUIT SCHEDULE 40 ( NELTEX OR APPROVED
EQUAL )

13. THE MOUNTING HEIGHT SHALL BE AS FOLLOWS :

· LIGHTNING SWITCHES 1.40 M.ABOVE FLOOR FINISH


· CONVENIENCE OUTLET 0.30 M. ABOVE FLOOR FINISH
· TELEPHONR OUTLET 0.30 M. ABOVE FLOOR FINISH
· PANEL BOARD , TEL., CAB. 1.40 M. ABOVE FLOOR FINISH

1 GROUND FLOOR LIGHTING LAYOUT 2 GROUND FLOOR POWER LAYOUT


SCALE 1:100
3 SCHEMATIC SINGLE LINE RISER DIAGRAM
SCALE
·
·
PULL ALARM
F.A. BELL & ANNUNCIATOR
1.40 M. ABOVE FLOOR FINISH
2.70 M. ABOVE FLOOR FINISH
E-1 SCALE 1:100 E-1 E-1 · SPECIAL OUTLET AS DIRECTED BY THE ELECTRICAL ENGR.

14. ALL MOUNTING HEIGHTS ARE SUBJECTED TO PROJECT MANAGER / ELECTRICAL ENGINEERS APPROVAL PRIOR
TO INSULATION.

15. ALL METAL HOUSING OF LIGHTING FIXTURES, BOXES, CONDUIT , PANEL BOARD SHALL BE PROPERLY
CONNECTED TO THE GROUNDING SYSTEM OF THE BUILDING.

16. UPON COMPLETION OF ELECTRICAL CONSTRUCTION WORK, THE FOLLOWING TEST SHALL BE PERFORMED BY
THE CONTRUCTOR INCLUSIVE OF THE INSTILLATION TO BE REPORTED IN DETAILS OF FORMS APPROVED BY
THE OWNER'S REPRESENTATIVE :

· INSULATION RESISTANCE TEST , 500 VDC


· GROUND RESISTANCE TEST
· PHASE BALANCING TEST
· PHASE SEQUENCE TEST
· SYSTEM TEST AND ACCEPTANCE

COLOR CODING OF WIRES SHALL BE AS FOLLOWS : ( FOR THREE PHASE ONLY )


s1
4
PNL 2
· A.PHASE A BLACK CONTROL WIRE WHITE
· B. PHASE B RED CONTROL WIRE BLUE
· C.PHASE C YELLOW CONTROL WIRE GREEN

s1 WORKMANSHIP : THE WORK THROUGHOUT SHALL BE IN THE MOST AND THROUGH


MANNER KNOWN TO TRADE AND TO THE SATISFACTION OF THE
OWNER ( LBP ) AND THE ELECTRICAL ENGINEER.

SCHEDULE OF LOADS

RCLT

s1

RCLT

3
PNL 2

RCLT

LEGENDS SPECIFICATION
SERVICE ENTRANCE

LP LIGHTING PANEL

REF REFRIGIRATOR OUTLET

OUTLET

4 SECOND FLOOR LIGHTING LAYOUT 5 SECOND FLOOR POWER LAYOUT


SCALE 1:100 CONDUCTOR SIZE : 30 mm² THHN WIRE 1-80 mm² GROUND IN 40 mm Ø PVC PIPE RECESSED LIGHTING
E-1 SCALE 1:100 E-1 RCLT

CEILING MOUNTED LIGHTING

SERVICE SERVICE OUTLET

PRC NO. : R.A. 9266 SEC. 33 : Ownership of Plans, Specifications PROJECT TITLE : CLIENT NAME: SHEET CONTENT(S) : SHEET NO.:
and Other Contract Documents. - Drawings and
specifications and other contract documents duly
IAPOA NO:
signed, stamped or sealed, as instruments of service, PROPOSED EXPANSION GROUND FLOOR LIGHTING LAYOUT
are the intellectual property an d documents of GROUND FLOOR POWER LAYOUT
TIN :

E-1
ARCHITECT LEONARD P. CORDERO,UAP, whether the SECOND FLOOR LIGHTING LAYOUT

PTR NO. :
object for which they are made is executed or not. It
shall be unlawful for any person to duplicate or to PTR NO. : PRC NO. : LOCATION :
CHONA YAMAGATA SECOND FLOOR POWER LAYOUT
m ak e c op ies of s aid do cu men t s f or use in t h e SCHEDULE OF LOADS
repetition of and for other projects or buildings, RISER DIAGRAM