SISTEM OTOMASI GARDU INDUK

(SOGI)

Jakarta, 1 Juni 2011


PT PLN (Persero) P3B Jawa Bali
Fungsi Yang Terpasang
Di P3B JB
No Perangkat Fungsi % Keterangan

1 RTU C264 100

2 SAS Pacis 80 Time Tag di HMI,


Lokal HMI, IED
beda
3 PLC T390 40

4 PLC 5000 0 Belum berfungsi


Uji Fungsi SCADA
Di P3B JB
NARI ABB Siemens ALSTOM
SOGI RCS 9698 SYS 600 SICAM PAS PACIS
L L L BL

SELTA ABB Siemens ALSTOM


RTU STCE 560 AK 1703 C264
L L L L
L = Lulus
BL = Belum Lulus
SOGI
Standard SPLN
• Teleinformasi Data untuk Pemeliharaan
Instalasi Sistem Tenaga Listrik SPLN
S5.002:2008 dengan SK Dir
No.169.K/DIR/2009
• Protokol IEC 61850 : IED proteksi dan IED
BCU
• Protokol IEC 60870-5-101
Syarat Teknis
• Relay Proteksi lulus Real Time Digital
Simulator (RTDS) dari PLN PUSLITBANG
• Lulus uji protokol IEC 60870-5-101 dan IEC
61850
• Lulus komunikasi partyline dan serial port
RS232
• Lulus uji digital input, digital output ,analog
input, analog output
• Time tag di IED, Lokal HMI, Dispatcher
Syarat Non Teknis
• Surat keterangan kepuasan pengguna dari
P3B JB
• Sudah diimplementasikan di negara maju
diluar negara pembuat
• Original Engineering Manufacture
Proses Lelang
• Dua sampul satu tahap :
– Sampul pertama : Syarat administrasi dan
teknik dan Uji fungsi
– Sampul ke dua : Penawaran harga
Perencanaan PLN
Membangun secara terpadu untuk :
• Gardu Induk
• SOGI
yang memenuhi Teleinformasi Data untuk
Pemeliharaan Instalasi Sistem Tenaga
Listrik SPLN S5.002:2008 dengan SK Dir
No.169.K/DIR/2009
Konfigurasi Master Station
01 02 03 04 05

06
SD

PROLIANT
8000

ESC

SD

DLT

A B C D E F G H
SELECTED
ON-LINE

A B C D E F G H
SELECTED
ON-LINE

SD

CONSOLE

14
LOOP
SD

OK
BRI DSU

B1
B2

LP
S/T CPU
S3

CONSOLE

WIC 0 OK FDX 100 LNK LOOP


AUX WIC 1 OK

OK
BRI DSU

B1
B2

LP
Cisco 1720 S/T CPU
S3

WIC 0 OK FDX 100 LNK WIC 1 OK


AUX

Cisco 1720

12
08

LCD 1 bh 13
Inter Center Link 07
( IEC 870-6 (ICCP) )

09
A B C D E F G H
SELECTED
ON-LINE

11
A B C D E F G H
SELECTED
ON-LINE

RTU
IEC 870-5-101, DNP 3.0 PROLIANT
8000

ESC
SD

Serial
15 16
SD

RTU DLT

IEC 870-5-104
Ethernet 10
Arsitektur SOGI
Kinerja SOGI
• Kapasitas station unit minimal 10.000 I/O.
• Kapasitas Otomasi GI minimal 96 IED
• Kapasitas switch 48 bh, fault recovery time max 150 ms.
• Pertukaran data peer to peer melalui protocol IEC 61850
maksimal 30 milidetik.
• Keakuratan telemetering dari IED BCU:
 Arus dan tegangan kelas 0,5
 Daya aktif dan reaktif (MW dan MVAr) kelas 0,5
 Energi meter (MWh dan MVArh) kelas 1,0
• Switchover otomatis (failover) station unit maksimal 30
detik.
• Penyimpanan urutan kejadian minimal 120.000 event dan
60 recording pengukuran selama 100 hari.
Kapan SOGI Di Bangun
• Gardu Induk Baru
• Penambahan Bay baru
• Rehabilitasi Gardu Induk
• Tersedia media komunikasi 64 kbps
Opsi Pembangunan SOGI

Bay Level RTU Proteksi Panel Kontrol Bay Baru

Opsi 1 : IED I/O Existing Existing BCU & IED Prot


Opsi 2 : Existing BCU per CB BCU & IED Prot
Opsi 3 : BCU & IED Proteksi
Yang Tidak Dibahas Pada
Spesifikasi SOGI
• Peralatan tegangan tinggi
• Power supply
• Telekomunikasi
• Disturbance fault recorder
• Fault locator
• Energy meter
Standard Teleinformasi SCADA
Fungsi Operasi Dan Pemeliharaan
Mnemo Designation

VDCF VDC FAILURE..

220RF 220VDC RECTIFIER FAILURE

110RF 10VDC RECTIFIER FAILURE


Jumlah Input/Output IBT
Operasi Pemeliharaan

Telemetering 4 37

Remote Control 3 18

Telesignal Double 6 17

Telesignal Single 17 129


Station Level Opsi 1

Control Center

Gateway

Station Unit 1 Station Unit 2

Switch Switch

Switch
Station Level Opsi 2

Control Center

Gateway

Station Unit 1 Station Unit 2

Switch Switch

Switch
Bay Transformer
Bus A

Q0A

Q0AB

Q0B

Bus B

1 IED untuk bay TRAFO


Bay Level Double Busbar
Bus 1
Single Line
Diagram

Bus 2
Q1 Q2 Q1 Q2 Q1 Q2

Q0 Q0 Q0

Q9
Q8

Transfor Bus
OHL
mer Coupler

Station LAN
IEC 61850: Ethernet 100 Mbps
Fiber Optic single ring

switch switch switch switch switch

OHL Trafo Trafo Busbar & Common


Coupler

BCU BCU MPU BCU IED I/O

MPU AVR BPU1 MPU

BPU BPU2 BPU


Level 150 kV One Half Breaker
Bus A

Station LAN
IEC 61850: Ethernet 100 Mbps
Fiber Optic single ring
Q0A

switch switch switch switch switch switch

Q0AB
OHL Diameter Trafo Trafo Busbar Common

MPU BCU A AVR MPU BUS PRO IED I/O


BUS A
Q0B
BPU BCU AB BPU 1 BUS PRO
Bus B BUS B
CCP BCU B BPU 2 CBF AB
(N Diemeter)
CCP
Level 500 kV One Half Breaker
Bus A

Station LAN
IEC 61850: Ethernet 100 Mbps
Q0A Fiber Optic single ring

switch Bay switch switch switch switch switch switch switch switch

Q0AB

OHL OHL Diameter Trafo Trafo Trafo BUSBAR BUSBAR COMMON


Q0B
BUSPRO BUSPRO
MPU 1 MPU 2 BCU A MPU1 MPU2 IED I/O
BCU 150 kV Bus A Bus A
Bus B Main 1 Main 2
CCP 2 BCU AB AVR RST BPU1 BPU2 BUSPRO BUSPRO
CCP 1
Bus B Bus B
Main 1 Main 2
BCU B CCP1 CCP2
CBF AB1 CBF AB2
(n diameter) (n diameter)
Penambahan
Bay Baru dan Up Grade RTU

Gateway

Station Unit 1 Station Unit 2

Switch Switch

Switch Switch Switch

IED I/O MPU BCU


BPU-1 AVR
BPU-2

Bay Trafo Baru


Penambahan
Diameter, Unit Pembangkit dan IBT
Station Level
• HMI
• Station Unit :
– Server redundant
– Fungsi SCADA, historikal data dan statistik
– Server berfungsi untuk manajemen dari IED dan
workstation.
• Gateway
• Dapat menampung IED sesuai kapasitas I/O
• Dapat meneruskan perintah kontrol dari
Master station atau lokal kontrol.
• Inverter 110 VDC ke 220 VAC.
Peralatan Yang Diakusisi SOGI

1. Pemutus (CB):
a. Status & perintah open-close
b. Counter of circuit Breaker
c. Pressure (SF6)
d. Alarm gangguan (misal: SF6 alarm)

CB untuk transmisi

Kontrol box CB Indicator alarm tekanan SF6 Transducer: tekanan SF6 ke 4-20 mA
(berupa kontak saja) “untuk monitor SF6 Pressure”
Peralatan Yang Diakusisi SOGI

2. Pemisah (DS/isolator)
a. Status & perintah open-close
b. Alarm gangguan
Peralatan Yang Diakusisi SOGI

3. Sakelar pentanahan (Earthing Switch)


a. Status & perintah open-close
b. Alarm gangguan
Peralatan Yang Diakusisi SOGI
4. Lightning Arrester

Lightning Arrester dengan counter Lightning Arrester tanpa signal untuk SOGI
Peralatan Yang Diakusisi SOGI
5. Transformator (Daya & Inter Bus Transformator)
a. Tap position indication dari OLTC
b. Counter pengoperasian OLTC
c. Temperature winding & oil
d. Transformer electromechanical protection (level alarm maupun trip)
e. Sistim pendinginan
f. Early Warning System
g. Alarm gangguan
Peralatan Yang Diakusisi SOGI

6. Counter operasi OLTC

Counter operasi OLTC OLTC Motor Drive Unit


Peralatan Yang Diakusisi SOGI
7. Automatic Voltage Regulator

Automatic Voltage Regulator Kontrol panel


Peralatan Yang Diakusisi SOGI
8. Panel distribusi tegangan menengah 20kV
a. Status dari Circuit Breaker, Earthing Switch, posisi CB rack in-rack out.
b. Kontrol CB
c. Alarm gangguan
d. Pengukuran besaran-besaran listrik

Penyulang 20kV dengan IED IED Kontrol & proteksi


Peralatan Yang Diakusisi SOGI

9. Ruang kendali GITET/GI


Temperatur & Kelembaban

Ruang kendali GI IED sensor kelembaban dan suhu


Peralatan Yang Diakusisi SOGI
10. Sistim SOGI

Control centre ICCP/TASE 2


Control centre

IEC 60870-5- 101 Lokal HMI

Time synchr (optional)


Log.IN1
1100
F1 1530
1530
8888 Log.Out1
>1
1503 2173
Log.IN2 2173
F2
Log.IN3
1530

Ethernet
IEC 60870-5-104
(eksisting) IEC 60870-5-101
LFC Modbus
IEC 60870-5-103 IEC 61850 (temperatur &
(eksisting) kelembaban)
Kesimpulan
• Sertifikasi uji fungsi dari PUSLITBANG
• Kepuasan pengguna
• Pembangunan terpadu peralatan Gardu Induk
dengan SOGI
• Audit spesifikasi teknik, proses lelang dan
pengujian
• Performance terbaik yang terpasang di PLN
• ALSTOM agar mengganti/memperbaiki PLC
T390, PLC 5000 dan PACIS