Anda di halaman 1dari 12

Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

Dry Contact for Power Monitoring


Solution without EISU
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

Table of Contents
1. POWER MONITORING DENGAN DRY CONTACT ................................................ 3
1.1 Landasan informasi ....................................................................3
1.2 Tabel alarm dan koneksi ..............................................................3
1.3 Material list ............................................................................4
2. HARDWARE INSTALLATION.................................................................. 6
2.1 DB25 Converter ke SA .................................................................6
2.2 Alarm PLN failure ......................................................................6
2.3 Alarm Rectifier Module/Arrester Rectifier ...........................................7
2.4 Alarm DC low voltage alarm ..........................................................7
2.5 Alarm Input SPD PLN Failure ..........................................................7
2.6 Alarm Battery stolen ..................................................................8
2.7 Alarm High temperature ..............................................................8
2.8 Alarm Diesel Generator Set On .......................................................8
2.9 Alarm Door Open ......................................................................9
3. SETTING ALARM CSU VIA LAPTOP ......................................................... 10

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 2 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

1. Power monitoring dengan Dry contact

1.1 Landasan informasi


Untuk memonitor DC power system ZTE ZXDU48 H002 tanpa menggunakan EISU, maka akan digunakan signal alarm
melalui dry contact.

Pembagian alarm dry contact sbb :

1. Beberapa alarm akan menghubungkan koneksi dari SA cable (cable B3) ke dry contact di SIB pada ZXDU48 H002

2. Beberapa alarm akan menghubungkan konesi dari SA cable (cable B3) ke ke dry contact di ACPDB

3. Tabel dibawah untuk pembagian koneksi dan alarm dry contactnya pada ZXDU48 H002

1.2 Tabel alarm dan koneksi


SA cable B3
NO Alarm Source SIB koneksi Jalur Koneksi Alarm Code di Nodeb
koneksi

Option 1 : Jika ACPDB support terminal contactor


1.Koneksi dari DB25 ke terminal di ACPDB AC power-cut alarm (198092207)
X9 (Pin 5 & 6) 2. Dari terminal ACPDB ke SIB
Dry contat di ACPDB +
1 PLN Failure DB 25 Pin 1 -14 3. Dari SIB ke DB25 Dry contact number : 0
Dry contact di SIB NC-1
Option 2 : Jika ACPDB tidak support terminal contactor Alarm Status : Alarm when open (1)
1. Koneksi dari DB25 ke SIB saja

Rectifier Module Alarm (198092208)


Rectifier Module & X9 (Pin 1 & 2)
2 Dry contact di SIB DB 25 Pin 2 -15 Koneksi SIB ke SA Dry contact number : 1
Arrester Rectifier NO-3
Alarm Status : Alarm when Closed (0)

Battery Low Voltage Alarm (198092259)


X10 (Pin 1 & 2)
3 DC Low Voltage Dry contact di SIB DB 25 Pin 3 -16 Koneksi SIB ke SA Dry contact number : 2
NO-6
Alarm Status : Alarm when Closed (0)

Arrester failure (198092560)

4 Input SPD PLN Failure Dry contat di ACPDB / DB 25 Pin 4 -17 Koneksi ke terminal di ACPDB Dry contact number : 3

Alarm Status : Alarm when open (1)

Battery Stolen (198092555)


Dry contact di SIB + X9 (Pin 4 & 3)
5 Battery Stolen DB 25 Pin 5 -18 Koneksi SIB ke SA+lilitan batere Dry contact number : 4
lilitan batere NC-2
Alarm Status : Alarm when open (1)

High Temp Alarm (198092595)


X10 (Pin 5 & 6)
6 High Temp Dry contact di SIB DB 25 Pin 6 -19 Koneksi SIB ke SA Dry contact number : 5
NO-4
Alarm Status : Alarm when Closed (0)

Genset ON (198092567)
Diesel Generator Set
7 ATS FGS / DB 25 Pin 7 -20 DB 25 Pin 7 -20 di loop Dry contact number : 6
On
Alarm Status : Alarm when open (1)

Door Control Alarm (198092044)


X10 (Pin 3 & 4)
8 Door Open Dry contact di SIB DB 25 Pin 8 -21 Koneksi SIB ke SA Dry contact number : 7
NO-5
Alarm Status : Alarm when Closed (0)

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 3 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

1.3 Material list


No Materials/Cable Name QTY Remark

1 0.3mm2 black single core heat resistant Flexible power cable 10 M Lilitan batere

2 Black dual core heat resistant Flexible power cable 30 M Untuk alarm koneksi dari SIB ke SA

3 Temperature Transducer Cable & sensor 1 KIT Di pasang di X6 SIB

5 SA cable 1 KIT BBU

6 Converter RS232 DB25 1 KIT Dipasang di SA B3 cable

SA cable

Converter RS232 Db25 Cable black dual core

Temperature sensor Lilitan batere

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 4 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

X9 : output relay 1,2,3


Pin 5,6 --> NC-1 di CSU A1
Pin 3,4 --> NC-2 di CSU A2
Pin 1,2 --> NO-3 di CSU A3

X10 : output relay 4,5,6


Pin 5,6 --> NO-4 di CSU A4
Pin 3,4 --> NO-5 di CSU A5
Pin 1,2 --> NO-6 di CSU A6

Info kaki pin

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 5 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

2. Hardware installation

2.1 DB25 Converter ke SA


Install DB25 converter ke SA cable, koneksi kabel SA nya di konektor dengan inisial B3.

2.2 Alarm PLN failure


Option 1 : Jika ACPDB panel tersedia terminal dry contact alarm untuk phase failure

Step :

a. Install kabel signal dari DB25i pin 1 ke terminal dry contact di ACPDB

b. Install kabel signal dari terminal dry contact untuk terminal lainnya di ACPDB ke SIB X9 pin 5

c. Install kabel signal dari SIB X9 pin 6 ke DB25 pin 14

Warna merah pake kabel isi 2

Warna hitam pake kabel isi 1

Option 2 : Jika ACPDB panel tidak tersedia terminal dry contact alarm untuk phase failure

Step :

a. Install kabel signal dari DB25 pin 1 ke SIB X9 Pin 5

b. Install kabel signal dari DB25 pin 14 ke SIB X9 Pin 6

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 6 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

2.3 Alarm Rectifier Module/Arrester Rectifier


Kabel signal yang dipakai isi 2 pcs

Step :

a. install kabel signal dari DB25 pin 2 ke SIB X9 Pin 1

b. Install kabel signal dari DB25 pin 15 ke SIB X9 Pin 2

2.4 Alarm DC low voltage alarm


Kabel signal yang dipakai isi 2 pcs

Step :

a. install kabel signal dari DB25 pin 3 ke SIB X10 Pin 1

b. Install kabel signal dari DB25 pin 16 ke SIB X10 Pin 2

2.5 Alarm Input SPD PLN Failure

Jika ACPDB panel tersedia terminal dry contact alarm untuk arrester failure

Kabel signal yang dipakai isi 2 pcs

Step :

a. Install kabel signal dari DB25 pin 4 ke dry contact di ACPDB

b. Install kabel signal dari terminal dry contact untuk terminal lainnya di ACPDB ke DB25 pin 17

Jika tidak tersedia, cukup di loop koneksi di DB25 converter pin 4 ke pin 17

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 7 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

2.6 Alarm Battery stolen


Kabel signal yang dipakai isi 1 pcs

Step

a. install kabel signal dari DB25 pin 5 ke SIB X9 Pin 3

b. Install kabel signal dari DB25 pin 18 ke SIB X9 Pin 4 setelah

Melakukan lilitan pada semua bank batere

2.7 Alarm High temperature


Kabel signal yang dipakai isi 2 pcs

Step

a. Install temperature sensor di SIB di X6

b. install kabel signal dari DB25 pin 6 ke SIB X10 Pin 5

c. Install kabel signal dari DB25 pin 19 ke SIB X10 Pin 6

2.8 Alarm Diesel Generator Set On


Loop koneksi dari DB25 pin 7 ke DB25 pin 20

Smartfren nantinya yang akan instal sendir ke Genset

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 8 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

2.9 Alarm Door Open


Kabel signal yang dipakai isi 2 pcs

Step :

a. install kabel signal dari DB25 pin 8 ke SIB X10 Pin 3

b. Install kabel signal dari DB25 pin 21 ke SIB X10 Pin 4

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 9 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

3. Setting Alarm CSU via laptop

Karena menggunakan relay output, untuk alarm yang tidak dipakai dari penjelasan diatas harus di
set NULL alarm alokasi relaynya dan alokasi yang dipakai juga harus di set sesuai pengaturan
koneksi diatas.

Dikarenakan default CSU sudah di set alokasi relaynya, untuk memudahkan perubahan harus
menggunakan laptop yang di hubungkan ke CSU

Step

1. Dari CSU pilih menu local set, akan tampil beberapa sub menu
2. Pilih Network dan tampil sub menu lagi dan pilih Wire Network
3. Selanjut pilih local IP mode nya ke Static

4. Konek kabel LAN dari laptop ke CSU

5. Set IP laptop

6. Via browser, masukin IP CSU, di coba beberapa kemungkinan user dan password dibawah

user : Power; password:ZTECorporation@0063

user : power; password : 0063

user : ZTECorporation; Password : 0063

user : admin; Password : 0063

user : admin; Password : power123

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 10 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

7. Pilih out-relay parameter

8. Set Alarm level dibawah ini dan untuk alarm lainya harus di set di set NULL

Parameter Name Parameter Value

AC Power OFF A1

AC Voltage Low A1

AC Phase Lack A1

AC SPD Abnormal A3

SMR Fan Fault A3

SMR Communication Fail A3

DC Voltage Low A6

DC SPD Abnormal A3

Battery Voltage Low A6

Battery Loop Broken A2

Environment Temp High A4

Door Alarm A5

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 11 / 12
Panduan Dry contact untuk ZXDU48 H002 Smartfren LTE Project

This material is proprietary to PT SMART TELECOM and is strictly confidential. No information contained herein
may be copied, translated, transcribed or duplicated for any commercial purposes or disclosed to third parties in
any form without the prior written consent of PT SMART TELECOM.

[POC Test] | 12 / 12