Figure 1:
Relay type MHOB 04 removed from case
2
conditions they are unaffected by windings (3a and 3b) and no in quadrature. The basic unit has
transient line charging currents current flows in the pilot wires. two output contacts; this can be
which are essentially unidirectional.) Under heavy through fault increased by using a contact
Type MHOB 04 relays are for conditions, mismatch of the line CTs multiplying relay, such as an MVAA
general use on three phase feeders may result in a small circulating housed in a separate case.
and have a fixed sensitivity. current. Operation of the relay is The relays are housed in Midos
The MHOC 04 relay has an prevented by a small restraining modular cases suitable for either
additional tap on the primary torque produced by the bias loops rack or panel mounting as shown in
winding which provides a more (7a and 7b). The bias loops also Figure 9. Standard Midos terminal
sensitive range of settings for earth compensate for magnetic flux blocks are located at the rear of the
faults. This allows application to produced by pilot wire capacitance relay providing connections for all
systems where the earth fault current current and ensures that this has no input and output circuits. Each
is limited. effect upon stability. terminal will accept up to two
An internal fault fed from end A of connections using either; an ‘L’
Pilot supervision can be shaped ring connector fastened with
implemented on schemes including the feeder increases the current in
the primary winding (2a) of relay A. a 4mm diameter (M4) screw or; a
the MHOB 04 and MHOC 04 snap-on connector compliant with
relays. This utilises the MRTP01 and This increases the induced voltage
in the secondary winding (3a), BS5057 or equivalent.
MRTP02 relays as shown in
Figure 3. which is not matched at end B and The auxiliary current transformer
results in a current flowing in the required by the MHOA 04 for
The MHOA 04 is intended primarily pilot wire circuit. The flow of this systems with more than 2 ends, is
for three-ended feeders. The scheme current through winding 4a provided with a plate for back of
requires separate auxiliary produces an operating torque in the panel mounting. M6 terminals are
quadrature current transformers (CT) induction disc which trips the relay. provided for connections to the
or transactors, having a linear The relay at end B will not trip as scheme.
characteristic between the primary the pilot wire current is flowing in a
current and the secondary voltage. direction which results in a User interface
The protection is also applicable to restraining torque on the disc.
The basic group of settings on the
systems having more than three line A fault fed from both ends will result MHOB 04 are fixed. On the MHOC
ends, but with reduced sensitivity. in the current reversing in the CT at 04 the optimum group of basic
If there is no possibility of a current end B (1b). This causes the induced settings for applications requiring
in-feed from the remote end of a tee- voltage in winding 3b to add to that more sensitive settings, is selected
off, a relay is not required there, but in winding 3a, producing an by connections to appropriate relay
a quadrature current transformer operating torque, and hence terminals on all versions.
must be included to maintain tripping at both ends.
balance conditions in the pilot A hand-reset operation indicator is
circuit. provided.
Hardware description
Functions The relays consist of robust
induction disc units. Rotation of the
Translay balanced voltage disc in the contact closing direction
protection system is the result of two magnetic fluxes
Figure 2 shows the principle of
operation of the scheme. The unit at Current transformer Current transformer
end A contains two electromagnets
A B
(5a, 6a). The primary summation
winding (2a) on the upper magnet Relay A 1a Relay B 1b
is fed from the line CT (1a) whilst its
secondary winding (3a) is 2a 2b
5a 5b
connected in series with the winding 3a 3b
(4a) on the lower magnet. 7a 7b
This secondary circuit is connected 4a 8a 4b 8b
by the pilot wires to the
corresponding circuit of the relay at 6a 6b
the remote end (4b).
Pilot wires
Whilst the feeder is healthy the
current in the line CTs (1a and 1b)
are equal. This induces equal and
opposite voltages in the secondary
Figure 2: Simplified connections illustrating principles of operation
3
S1 S2
S2 S1
17 18 17 18
19
V
Case V V
earth V 20
MRTP 02
AC auxiliary
supply 20 V
RL2 OP
RL7
Case earth L2 1 Supply fail
19 V >I Reset
1 2
27 OP
3 4 AC RL1 RL3 RL6
power Pilot RL4-1
28 L1 <I L3 Reset 1
5 6 supply S/C Output
contacts
7 8 13 OP
RL8 change state
DC Pilot
9 10 Vx power Reset 1 O/C RL4-2 for pilot fail
14 supply
11 12
4
13 14 RL4
>1 2
15 16 RL5-1
17 18 MRTP 01 Output
contacts
change state
19 20 +VE
RL5 RL5-2 for supply fail
21 22 RL1 RL2 RL3 2
RL1 RL2 RL3
Case –2 –2 –2
23 24 earth –1 –1 –1
Start
25 26 t
27 28
Note 1.
(a) CT shorting links make
before (b) & (c) disconnect
Module terminal block
viewed from rear (b) Short terminals break before (c)
(c) Long terminal
5
11 12
Pilot wire Pilot wire
13 14
1 Case earth
15 16 Note 1.
2 see Note 2
(a) CT shorting links make
17 18 3
21 before (b) & (c) disconnect
19 20 4 22 1P2 1P1 1P2 1P1
(b) Short terminals break before (c)
21 22 23
24 (c) Long terminal
25
23 24 26 2P1 2P2 2P1 2P2 Note 2. Earthing connections are typical only
27
25 26 28 Note 3. CT connections are typical only
3P1 3P2 3P1 3P2
Note 4. Coil connections viewed from front
27 28 MHOA 04
A B C A B C Note 5. If there is no possibility of an in feed from
18 17 the remote end only a quad CT is required
Pb S1 S2 S3 Pa Pb S1 S2 S3 Pa Pilot wire
Module terminal block see Note 5
viewed from rear
C B
Protected zone Protected zone
Phase rotation
P1 P2 P2 P1
A
S1 S2 S2 S1
B
C
1 1
Case earth
Case earth 3 3
Case earth See Note 2
1 2 See Note 2 2 2
3 4 R 4 4 21
5 6 21 3WR
22
7 8 22 W 23
23
9 10 R1 24
24 BK 25
6
11 12 25 & 2WR
26
See Note 3 2WBK 3WBK
13 14 26 27
27
15 16 28
28
17 18
MHOB 04 MHOB 04
19 20 18 S2 S2 18
21 22 R R
See Note 4
23 24 BK BK 17 S1 S1 17
Pilot
25 26 wires
Note 1.
27 28
(a) CT shorting links make Note 2. Earthing connections are typical only
before (b) & (c) disconnect
Note 3. CT connections are typical only
(b) Short terminals break before (c)
Module terminal block Note 4. Coil connections viewed from front
viewed from rear (c) Long terminal
C B
Protected zone Phase rotation Protected zone
P1 P2 P2 P1
A
S1 S2 S2 S1
B
C
1 1
Case earth
Case earth 3 3 See Note 2
Case earth
1 2 See Note 2 2 2
3 4 R 4 4 21
5 6 21 3WR
22
7 8 22 W 23
23
9 10 R1 24
24 BK 25
11 12 25 & 2WR
26
7
See Note 3
13 14 26 2WW 27
N=2.25 27 N=2.25
15 16 N=6 2WBK 3WBK 28 N=6
28
17 18 See Note 5 See Note 5
MHOC 04 MHOC 04
19 20 18 S2 S2 18
21 22 R R
See Note 4
23 24 BK BK 17 S1 S1 17
Pilot
25 26 wires
Note 1.
(a) CT shorting links make Note 2. Earthing connections are typical only
27 28
before (b) & (c) disconnect
Note 3. CT connections are typical only
(b) Short terminals break before (c)
Note 4. Coil connections viewed from front
Module terminal block (c) Long terminal
viewed from rear Note 5. Make appropriate connection for required earth fault sensitivity
(see fault settings table)
Ratings
Inputs:
AC current (In) 1A or 5A
Frequency 50/60Hz
Operating time
900
500
400
300
100
60
50 Max. setting scale
40
30
20
10
0 2 4 6 8 10 14 18 22 26 30
Thermal withstand
8
The MHOB 04 and MHOC 04 electromagnet saturates at high currents, so
that the rms voltage applied to the pilots does not exceed 250V at maximum
fault levels. However, the voltage output waveform becomes sharply peaked,
with voltage spikes at each half cycle of peak value of the order of 1000V at
150 times setting current.
9
Settings
Due to the use of a summation winding, the basic settings of the relays differ
for the various types of faults, as shown in the table below.
The MHOA 04 provides two alternative sensitivities by the use of alternative
tap on the quadrature CT (13V or 26V). The use of the 13V tap provides
higher through-fault stability as indicated in Table 1.
Table 1
The minimum fault setting provided by the MHOA 04 on the two taps are
shown in Table 2.
The MHOB 04 and MHOC 04 have identical minimum fault settings (when
N=2.25) as shown in Table 2. The MHOC 04 has an additional tap (N=6)
on the primary winding which provides a more sensitive range of settings for
applications where the earth fault current is limited.
Table 2
Note: N refers to the relative neutral turns on the summation winding 1:1:N.
The settings shown for the MHOA 04 are for a 3 ended system. When the
relay is applied to a four ended system the settings will be increased by a
factor of 1.25.
These settings are quoted for a pilot of negligible resistance. The fault settings
will increase in proportion to any pilot resistance (Figure 8). The basic
minimum settings of the relays can be increased by a factor of up to 2, by
increasing the control spring tension by means of a calibrated knurled disc.
10
3
Contacts
Output contacts 2 normally open
Contact rating Make and carry 750VA with a
maxima of 6A and 250V ac or dc.
Electrical environment
EMC compliance Compliance to the European
89/336/EEC Commission Directive on EMC is
claimed via the Technical
Construction file route.
EN 50081-2: 1994 Generic standards were used to
EN 50082-2: 1995 establish conformity.
Product safety
73/23/EEC Compliance with European
Commission Low Voltage Directive.
EN 6101-1: 1993/A2: 1995 Compliance is demonstrated by
EN 60950: 1992/A11: 1997 reference to generic safety
standards.
11
Atmospheric environment
Temperature Storage and transit –20°C to +60°C
Mechanical environment
Vibration
IEC 60255-21-1: 1988 Response class 1
12
Cases
MHOA 04, MHOB 04 and MHOC
04 relays are all housed in a Midos
size 6 case as shown in Figure 9.
The outline of the auxiliary current
transformer for the MHOA 04 is
shown in Figure 10.
103.6
149 4 holes Ø 4.4
23.5
Push button
151
projection 10 max.
Panel cut-out:
Flush mounting fixing details.
32 212
25 min.
155 Reset
Flush mounting. 11
9 off M6 terminals
17
173
12.7
216.5 Ø14
13
89
242.5
178
Dimensions in mm
13
Additional information
Service manual R8140
MVAA auxiliary relay R6009
MRTP supervision for AC pilot circuit R6026
MMLG/MMLB Midos test facility R6004
Teed feeders
(see note below) A
Plain feeders
(standard earth fault) B
Plain feeders
(sensitive earth fault) C
Case size
Midos size 6
CT secondary rating
1A 1
5A 5
Frequency
50Hz 5
60Hz 6
Transformer ZB9011
1A 039
5A 040
14
15
ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England
Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: enquiries@pcs.alstom.co.uk Internet: www.gecalsthomgpc.co.uk
©1998 ALSTOM T&D Protection & Control Ltd
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.