Anda di halaman 1dari 11

Electrical Power and Energy Systems 25 (2003) 59±69

www.elsevier.com/locate/ijepes

A wavelet multiresolution analysis for location


of faults on transmission lines
D. Chanda, N.K. Kishore*, A.K. Sinha
Department of Electrical Engineering, Indian Institute of Technology, Kharagpur 721302, India
Received 9 May 2001; revised 1 October 2001; accepted 13 February 2002

Abstract
Faults on EHV lines are quite common. They cause disruption in power supply. Accurate location of faults will result in faster maintenance
and restoration of supply. This paper presents a new method for the location of faults based on wavelet multiresolution analysis (MRA).
EMTP (Microtran) is employed to generate the time domain input signal. Daubechies eight (D-8) wavelet transforms of the three phase
currents on transmission lines from both the ends are used. The effects of fault inception angle and fault impedance are examined. Extensive
simulation work has been carried out and results indicate that the proposed method is very effective in locating the fault with a high accuracy.
q 2002 Elsevier Science Ltd. All rights reserved.
Keywords: Wavelet transforms; Multiresolution analysis; EMTP; Fault location; Power systems

1. Introduction as one of the variables. This requires updating whenever the


system topology undergoes changes. Takagi et al. proposed
The performance of a power system is frequently affected a fault location algorithm based on Fourier transform [1]
by faults, which give rise to disruption in power ¯ow. and Laplace transform [5] assuming loss less circuit
Usually digital fault recorders placed at the two buses elements. It results in appreciable errors for a realistic
connecting the transmission line monitor the line voltages lossy system. The accuracy of the result is also affected
and currents and record disturbance incidents as digital fault by the angle of voltage wave at the time of fault and dc
records. These records are transferred to a central location offset current. Thorp et al. [6] proposed R±L differential
for detailed study and analysis. The analysis of faults equation approach for the faulty circuit to eliminate the
includes the type and location of fault. effect of fault resistance, assuming current in the faulty
The determination of the location of fault quickly with a circuit to be zero at the instant of measuring the impedance
reasonable accuracy helps in faster maintenance and up to the fault point. The problem of measuring instant of
restoration of supply resulting in improved economy, safety zero current with only one side measurement and measuring
and reliability of power system. both voltage and current from a single sample are the major
Most of the fault location schemes are based on travelling drawbacks of this method, as it leads to signi®cant errors in
wave propagation on the transmission line. Another method results.
called pulse radar method is also used in which a measure- Richards and Tan [7] locate faults by a comparison of
ment of the period from emission to return of the pulse is voltage and current at one end of a real line with a digital
involved when an electrical pulse is transmitted on the line model of the line using an optimization procedure. But
[1]. Counter relays for distance protection [2,3] depend on it requires accurate model of the network and iterative
the measurement of the impedance up to the fault point. calculations.
These assume zero fault resistance which is not valid in Wiszniewski [8] proposed a non-iterative technique for
many cases of actual faults. The algorithm proposed by fault location based on standard calculation of resistances
Westlin and Bubenko [4], for fault location uses Newton± and reactances and simultaneously correcting the error due
Raphson method with source impedance of the remote end to fault resistance. But the change in the fault current distri-
bution factor with the system con®guration requires its
* Corresponding author. determination at the fault condition. Sachdev and Agarwal
E-mail address: kishor@ee.iitkgp.ernet.in (N.K. Kishore). [9] also proposed a non-iterative procedure for fault location
0142-0615/03/$ - see front matter q 2002 Elsevier Science Ltd. All rights reserved.
PII: S 0142-061 5(02)00021-2
60 D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69

using the fundamental frequency voltages and currents at


the line terminals. But the percentage error is high and
increases with the increase in the fault resistance. Abur
and Magnago [10] uses time-delays between modal com-
ponents in a wavelet-based fault location method employing
line model based on frequency dependent parameters. In
this method, the error in the fault location is a function of
the sampling rate chosen and hence modal propagation velo-
city, which changes with system con®guration. Liang et al.
[11] proposed a wavelet correlation function for fault
location. It requires more than one sub-band information Fig. 1. Four hundred kilovolts transmission line system used for the simula-
tion studies.
and two types of wavelet transform (i.e. Harr and spline).
The wavelet multiresolution analysis (MRA) is a new and
powerful method of signal analysis well suited to fault impedance faults with fault resistance as high as 500 V
generated signals [12]. The windowing of wavelet transform and the algorithm works satisfactorily.
is adjusted automatically for low and high frequencies, i.e. it The method is simple and generalized, it is independent
uses short time intervals for high frequency components and of the effects of fault inception angle, fault distance and fault
long time intervals for low frequency components and impedance.
thereby each frequency component gets treated in the
same manner without requiring any reinterpretation of the
results. This gives the wavelet transform much greater 2. Wavelet analysis and MRA
`compact support' for the analysis of the signals with local-
Wavelets are functions that satisfy the requirements
ized transient components. The time frequency localization
of both time and frequency localization. The necessary
means that more energetic wavelet coef®cients are localized
and suf®cient condition for wavelets is that it must be
and therefore `sparse' in the transform domain. This is
oscillatory, decay quickly to zero and have an average
useful for feature extraction. Therefore, it is well suited
value of zero. In addition, for the discrete wavelet transform
for the fault location problem in power systems.
(DWT) considered here, the wavelets are orthogonal to each
The identi®cation of fault is based on the peak absolute
other.
value of third level output for the three phase currents, mean
Wavelets are localized in both time (through translation)
of these three phase currents and the absolute value of the
and frequency (through dilation). Wavelets can provide
summation of these three peak values. The classi®cation
multiple resolutions in both time and frequency. The signal
algorithms [19] are based on the summation of third level
can be accurately reproduced with the wavelet analysis
wavelet transform output S or the ratio of summation of
using relatively small number of components [13]. The
third level wavelet transform output. In Ref. [18], the
analysing wavelets are called the `mother wavelets' and
sharp variation values of three phase detail signals are
its dilated and translated versions are called the `daughter
used for the identi®cation of faults while relative ratios of
wavelets'. It has a digitally implementable counterpart
sum of the ®rst three sharp variation values of three phase
called the DWT. The generated waveforms are analysed
detail signals are used for the classi®cation of faults. It also
with wavelet MRA to extract sub-band information from
requires the calculation of zero-sequence component of
the simulated transients. Daubechies eight (D-8) wavelet
current for classi®cation purpose. Also, in Ref. [18], total
is used in this work for the analysis as it is localized, i.e.
time period considered for the analysis is 0.25 s as against
compactly supported in time and hence is good for short and
0.04 s for the proposed algorithm.
fast transient analysis [14]. In this paper, wavelet coef®-
This work presents an application of wavelet MRA tech-
cients of the signal are derived using matrix equations
nique for fault location in combination with the method of
[15] based on decomposition and reconstruction of a
cubical interpolation. The third level MRA detail signal is
discrete signal using Mallat's algorithm [13].
found to be most suitable for this purpose and only this is
The derivation for the determination of wavelet coef®-
used for the wavelet analysis. This reduces the computa-
cients using matrix equations for signal decomposition
tional burden considerably. The fault location is based on
and reconstruction as employed for fault location problem
the current signals obtained from both the ends of the line.
are discussed in Appendix A.
For simulation and testing of the proposed method, faults
are applied at every 10 km interval over the entire length of
the line. As the fault inception angle a F (angle of voltage 3. Simulation
phasor at the instant of fault occurrence) has considerable
effect on current signals, therefore, its effects are also The model power system considered for the analysis is
considered. shown in Fig. 1. The base values of the voltage and the
The fault location algorithm is also applied to high power in the system are taken as 400 kV and 100 MVA.
D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69 61

The transmission line parameters are R 0 ˆ 0:38848 V=km; The time domain signals are generated by EMTP. Now,
X 0 ˆ 3:25083 mH=km; C0 ˆ 0:00845 mF=km; R1 ˆ 0.02336 fault is itself a phenomena involving large disturbance in the
V=km; X 1 ˆ 0:95102 mH=km; C1 ˆ 0:01237 mF=km: system and the parameter selected for the fault location is
The total impedance of the generator and the transformer the summation of third level output. Hence, in the presence
taken together is …0:2 1 j4:49† V; while the load impedance of `noisy data' found in real recordings, there will be only
considered is …720 1 j1:111† V (this corresponds to a load minor variations in the summation values of third level
of 200 MVA at a power factor of 0.9 lag) and the frequency output as the magnitude of disturbance created by faults
of the system is 50 Hz. From the simulations, the current are always much larger as compared to the noisy data.
signals for each phase are recorded with a sampling time of Also, noise consists of high frequency signals, whereas
80 ms at both the generator and the load ends for each point the third level output of wavelet transform contains signal
of fault. These generated time domain signals are then used only in the frequency range 97±195 Hz. Therefore, the
for the analysis using wavelet transform. Through an noise signal will in general be ®ltered out from the third
exhaustive experimentation for identifying the distinguish- level output. This makes the fault location technique very
ing features of different type of faults and their location, it is effective.
found that the sum of third level output for the three phases The third level output is selected as the parameter for
is best suited for this problem. The types of faults considered fault location as the summation of third level output satis®es
in the analysis are L±G, L±L±G, L±L and L±L±L faults. the necessary conditions for all types of faults [19]. The
The simulations show that fault inception angle has a third level output corresponds to a frequency band of 97±
considerable effect on the current signals and therefore on 195 Hz, i.e. it includes second and third harmonic com-
the wavelet transform output. As the waves are periodic, it is ponents which are predominant in case of faults. Also, the
suf®cient to study the effect of inception angle in the range simulation results show that the summation of third level
0±1808. The effects of fault distance and fault impedance output for all the inception angles considered in the analysis
are also examined. are higher as compared to that of other level outputs. It
For each type of fault and for each inception angle con- indicates that total area under the characteristics of third
sidered in the analysis, simulations are carried out at 31 fault level output are more than that of other level outputs. In
locations at an interval of 10 km for a total line length of the wavelet analysis, the band of frequency is involved
300 km. For each of these fault locations, simulations are with precise time localization but in other techniques like
carried out for a total of 11 inception angles at an interval of DFT, individual frequency components are involved with-
188 between 0 and 1808 for all the four different types of out any time localization. As a result, the determination of
faults. Thus, a total of …31 £ 11† £ 4 ˆ 1364 simulations are sum of third level output involving second and third harmo-
carried out. Based on these simulations, the fault location nic components in wavelet analysis will be simpler and
algorithm is established. different from that of DFT involving determination of
The data considered in the analysis are assumed to be of second and third harmonic components individually. More-
®nite duration and of length 2 N, where N is an integer. If N is over, DFT is not suitable for non-stationary signals. Hence,
chosen to be 9, the total duration of the analysis comes out for power system transients like faults in transmission lines
to be 2 9 …ˆ 512† £ 80 ms ˆ 40:96 ms; which is about two where the waveforms are non-stationary in nature, wavelet
cycles and is suf®cient enough for the fault analysis. With analysis is more suitable.
N ˆ 9; there are …N 1 1† ˆ 9 1 1 ˆ 10 wavelet levels and In practice, the current signals need to be normalized
if these 10 levels are added together, then the original signal before they are sampled by A/D converters. Hence, all
is faithfully reproduced at each of the sample points [15]. the data used in the analysis are normalized to p.u. values
The wavelet transform is applied to all the three phase so that the technique developed becomes general and can
current signals for each fault initiation angle. As the data be applied to systems of all voltage levels without any
length is of ®nite duration and the total duration of the modi®cation. P
analysis is about two cycles, hence, the value of summation If Sa ˆ Nkˆ1 I3a …k†; where I3a …k† is the magnitude of third
S indicates the summation of third level output for this level wavelet component for the current in phase a at the kth
total period of two cycles. Hence, the value of S varies instant and N is thePtotal number of samples.
with types of fault, fault location, fault inception angle Similarly,
PN Sb ˆ Nkˆ1 I3b …k† for the current in phase b and
and fault resistance. Sc ˆ kˆ1 I3c …k† for the current in phase c.
For L±G faults, either Sa ; Sb or Sc is considered depend-
ing on whether phase a, b or c is the faulted phase, i.e. Sp is
4. Algorithm for fault location considered, where p [ …a; b; c†:
For other types of faults, S is considered, where S ˆ Sa 1
In this method of fault location, it is assumed that the fault Sb 1 Sc for L±L±L fault, or S ˆ Sa 1 Sb or Sb 1 Sc or Sc 1
is identi®ed and classi®ed before hand as in Ref. [19]. Prior Sa for L±L±G and L±L faults depending on the faulted
knowledge of the type of fault is a requirement of the phases.
algorithm. Once the wavelet analysis is done, the values of Sp for
62
Table 1
Percentage error in fault location for different types of interpolation from the generator end side

Type Actual Linear interpolation Spline interpolation Quadratic interpolation Cubical interpolation
of fault point of
fault (km) (a) Calculated % error ˆ Calculated % error ˆ Calculated % error ˆ Calculated % error ˆ
point of ((a 2 b)/L) £ 100 point of ((a 2 b)/L) £ 100 point of ((a 2 b)/L) £ 100 point of ((a 2 b)/L) £ 100

D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69


fault (km) (b) fault (km) (b) fault (km) (b) fault (km) (b)

L±G 275 274.70 0.10 274.70 0.10 274.71 0.097 274.70 0.10
225 230.00 21.67 227.30 20.768 227.29 20.763 227.30 20.768
175 172.60 0.800 172.70 20.768 172.66 0.780 172.70 20.768
125 124.80 0.067 124.90 20.033 124.88 0.040 124.90 20.033
75 78.70 21.23 78.60 21.20 78.65 21.22 78.60 21.20
25 22.30 0.900 22.30 0.900 22.31 0.897 22.30 0.900
L±L±G 275 274.30 0.233 274.40 0.20 252.61 4.13 274.40 0.20
225 222.30 0.900 222.60 0.80 222.63 0.790 222.60 0.80
175 178.30 21.10 178.30 21.10 178.25 1.083 178.30 21.10
125 125.80 20.267 124.90 0.033 124.90 0.033 124.90 0.033
75 73.60 0.467 74.20 0.267 67.09 2.637 74.20 0.267
25 23.30 0.567 23.30 0.567 23.33 0.590 23.30 0.567
L±L±L 275 273.50 0.500 276.00 20.333 276.02 20.340 276.00 20.333
225 222.20 0.933 228.30 21.10 228.33 21.11 228.30 21.10
175 177.40 20.80 177.00 20.667 177.02 20.673 177.00 20.667
125 125.60 20.200 124.90 0.033 124.89 0.037 124.90 0.033
75 71.80 1.067 72.00 1.00 68.66 2.110 72.00 1.00
25 28.70 21.10 28.00 1.00 28.00 21.00 28.00 1.00
L±L 275 280.00 21.67 280.00 21.67 278.86 21.287 273.50 0.50
225 222.30 0.90 222.30 0.900 222.45 0.850 222.50 0.833
175 177.40 20.80 177.40 20.80 177.13 20.710 177.10 20.70
125 125.10 20.100 124.80 20.067 124.86 0.047 124.90 20.033
75 78.30 21.10 71.30 1.233 66.07 2.977 71.90 1.033
25 26.00 20.333 26.00 20.333 26.00 20.333 26.00 20.333
Table 2
Percentage error in fault location for different types of interpolation from the load end side

Type Actual Linear interpolation Spline interpolation Quadratic interpolation Cubical interpolation
of fault point of
fault (km) (a) Calculated % error ˆ Calculated % error ˆ Calculated % error ˆ Calculated % error ˆ
point of ((a 2 b)/L) £ 100 point of ((a 2 b)/L) £ 100 point of ((a 2 b)/L) £ 100 point of ((a 2 b)/L) £ 100

D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69


fault (km) (b) fault (km) (b) fault (km) (b) fault (km) (b)

L±G 25.00 25.70 20.233 25.20 20.067 25.21 20.070 25.20 20.067
75.00 75.50 20.167 75.40 20.133 75.51 20.170 75.40 20.133
125.00 126.70 20.567 126.40 20.467 126.55 20.517 126.40 20.467
175.00 175.80 20.267 175.70 20.233 175.71 20.237 175.70 20.233
225.00 223.80 0.400 225.70 20.233 225.73 20.243 225.70 20.233
275.00 274.40 0.200 274.50 0.167 274.34 0.220 274.50 0.167
L±L±G 25.00 25.60 20.20 25.20 20.067 25.25 20.067 25.20 20.067
75.00 75.20 20.067 74.90 20.030 74.84 0.053 74.90 0.030
125.00 125.80 20.267 125.40 20.133 125.45 20.15 125.40 20.133
175.00 175.70 20.233 175.70 20.233 175.89 20.297 175.70 20.233
225.00 223.10 0.633 223.20 0.60 223.14 0.620 223.20 0.60
275.00 272.50 0.833 272.70 0.767 272.61 0.797 272.70 0.767
L±L±L 25.00 25.60 20.20 25.10 20.033 25.14 20.047 25.10 20.033
75.00 75.20 20.067 75.00 0 74.97 0.01 75.00 0
125.00 125.50 20.167 125.20 20.067 125.29 20.097 125.20 20.067
175.00 175.30 20.10 175.10 20.033 175.14 20.047 175.10 20.033
225.00 224.30 0.233 224.40 0.200 224.39 0.203 224.40 0.200
275.00 273.10 0.633 273.70 0.433 273.64 0.453 273.70 0.433
L±L 25.00 25.60 20.20 25.20 20.067 25.21 20.07 25.20 20.067
75.00 72.70 0.767 72.80 0.733 72.72 0.760 72.80 0.733
125.00 125.80 20.267 125.40 20.133 125.42 20.14 125.40 20.133
175.00 175.70 20.233 175.70 20.233 175.74 20.247 175.70 20.233
225.00 223.10 0.633 223.20 0.60 223.13 0.623 223.20 0.60
275.00 272.50 0.833 272.70 0.767 272.61 0.797 272.70 0.767

63
64 D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69

L±G faults or the values of S for other types of faults are


plotted corresponding to different fault points at different
inception angles. The method of cubical interpolation is
then applied to ®nd out the location of fault.

5. Fault location using cubical interpolation

The method of cubical interpolation is based on the


development of a set of third order polynomials for the
interval under consideration. Sets of points are estimated
by this interpolation technique within the interval under
consideration. From the simulation results and the calcu-
lated values of Sp or S of third level wavelet transform
output, it is found that cubical interpolation technique is
suitable as the accuracy of location is higher (,1%).
The comparison of percentage error in fault location by
various interpolation techniques are shown in Tables 1 and 2
which reveal that the percentage error as calculated for
cubical interpolation technique is the lowest for all types
of faults considered in the analysis and for measurements
from both the ends of the line. It may be noted that spline
interpolation technique is comparable to cubical interpola-
tion technique in all cases except for a L±L fault at the
generator end as shown in Table 1. In view of the above,
cubical interpolation technique has been chosen for the
algorithm.
The various steps followed in the interpolation technique
are as follows.
(1) At the generator end, the values of Sp in case of L±G
fault and S in case of L±L±L, L±L±G or L±L faults are
determined for all the intermediate locations on the line at
intervals of 10 km. This is repeated for all the inception
angles. All these values of S and Sp are stored in computer
memory.
(2) Step (1) is repeated at the load end.
(3) When the data for a given type of fault at an unknown
location are presented, the wavelet transform parameter Sp if
it is a L±G fault and S in case of L±L, L±L±G or L±L±L
faults is compared with that of the stored values for different
locations at both the ends.
(4) Step (3) is repeated for all the inception angles and the
closest location is determined for each case. If the wavelet
transform parameter Sp or S in step (3) for unknown fault
location falls outside the range of the set of stored values for
a particular inception angle, then that particular inception
angle is not valid as the fault location should always be
within the length of the line.
(5) Two more additional locations, one preceding and
another succeeding the nearest location are also determined
so that the unknown fault location falls within the range of
Fig. 2. A ¯ow chart for the fault location by cubical interpolation method.
these three locations. This is repeated for all valid inception
angles.
(6) Now, using cubical interpolation technique involving (7) Thus two such sets of locations, x1 from generator end
the three locations as determined in step (5) is used to and x2 from load end, are obtained corresponding to each of
estimate the location to a range of 1 km. This is also the valid inception angle.
repeated for all valid inception angles at both the ends. (8) Now, if the distance of the fault point is x from one
D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69 65

Table 3

Type Point of fault Inception Point of fault from Point of fault from % error ˆ
of fault (actual) (km) (a) angle (8) generator end load end (calculated) [(a 2 b)/L] £ 100
(calculated) (km) (b) (km) (c)

L±G 25 0 25.20 274.70 20.067


75 36 75.40 227.30 20.133
125 72 126.40 172.70 20.467
175 108 175.70 124.90 20.233
225 90 225.70 78.60 20.233
275 144 274.50 22.30 10.167
L±L 25 0 25.20 273.50 20.067
75 36 72.80 222.50 0.733
125 72 125.40 177.10 20.133
175 108 175.70 124.90 20.233
225 90 223.20 71.90 0.60
275 144 272.70 26.0 0.767
L±L±G 25 0 25.20 274.40 20.067
75 36 74.90 222.60 20.30
125 72 125.40 178.30 20.133
175 108 175.70 124.90 20.233
225 90 223.20 74.20 0.60
275 144 272.70 23.30 0.767
L±L±L 25 0 25.10 276.0 20.033
75 36 75.0 228.30 0
125 72 125.20 177.0 20.067
175 108 175.10 124.90 20.033
225 90 224.40 72.0 0.200
275 144 273.70 28.0 0.433

end of the line then its distance from the other end should In the event of changing fault resistance like in the case of
be L 2 x; where L is the length of the line. The summations high impedance faults, the wavelet transform parameter Sp
of the locations from both the ends, i.e. x1 1 x2 ; as found in or S at an unknown location is compared with the stored
step (7), are calculated for all the valid inception angles values of Sp or S at different inception angles and locations
and compared with the total length of the line, i.e. 300 km corresponding to different fault resistances and the closest
in this case and the absolute value of the difference is location is determined as described in the algorithm.
determined. Hence, the algorithm for fault location will involve three
(9) Now for whichever valid inception angle, the value of parameters, i.e. location, inception angle and fault resistance
…x1 1 x2 † is closest to L (the line length), that gives the and there will be stored values of Sp or S corresponding to
correct values of x1 and x2 and hence the correct fault loca- different fault resistances at different locations and inception
tion and the fault inception angle. angles.

Table 4

Type Point Inception Point Point % error ˆ


of fault of fault angle (8) of fault of fault [(a 2 b)/L] £ 100
(actual) from generator from load
(km) (a) end (calculated) end (calculated)
(km) (b) (km) (c)

L±G 155 0 155 145 0


235 90 235.90 66.40 20.30
L±L 65 0 67.40 234.0 20.80
245 90 245.10 57.60 20.03
L±L±G 85 0 87.30 214.70 20.76
165 90 164.90 140.0 0.03
L±L±L 45 0 44.20 257.70 0.27
115 90 115.90 187.70 20.30
66 D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69

Fig. 3. Variation of Sa with line length and approximation by cubical Fig. 5. Variation of S with line length and approximation by cubical inter-
interpolation for L±G fault involving phase a and ground at (1) aF ˆ 08 polation for L±L±G fault involving phases a, b and ground at (1) aF ˆ 08
and (2) aF ˆ 908 at the generator end. and (2) aF ˆ 908 at the generator end.

The complete ¯ow chart for the method is shown in load end as can be seen from the simulation results in Figs.
Fig. 2. 4, 6, 8 and 10, where the values of S are very small (of the
The percentage error expressed in terms of the total order of 10 27) as compared to that at the generator end in
length of the line (L), i.e. 300 km in this case is found Figs. 3, 5, 7 and 9, where values of S are of the order of 10 25.
by determining the difference between the actual point Also, the current at the load end will increase with the
of fault at different inception angles and the point of increase in fault resistance.
fault as calculated by the interpolation technique. Results The variation of Sa or S with fault location and its
are tabulated in Table 3. It is found that the percentage approximation by cubical interpolation at the generator
error is always less than 1% for all types of faults con- and the load end for inception angles of 0 and 908 are
sidered in the analysis. shown in Figs. 3±10 for all the four kinds of faults con-
The percentage error for L±L±L fault is minimum among sidered in the analysis.
all types of fault considered. The maximum error, as seen
from Table 3, is only 0.767%. For high impedance faults
also, the percentage error is less than 1% as maximum error 6. Conclusions
found to be 0.80% for the sample cases studied in the analy-
sis as shown in Table 4. In this paper, an application of wavelet MRA theory in
Hence, it may be said that the fault location accuracy of combination with cubical interpolation technique is pro-
this technique is very high. Since, the fault resistance is not posed for the location of fault on a transmission line. The
equal to 0, hence, there will be a ¯ow of small current at the property of multiresolution in both time and frequency using

Fig. 4. Variation of Sa with line length and approximation by cubical Fig. 6. Variation of S with line length and approximation by cubical inter-
interpolation for L±G fault involving phase a and ground at (1) aF ˆ 08 polation for L±L±G fault involving phases a, b and ground at (1) aF ˆ 08
and (2) aF ˆ 908 at the load end. and (2) aF ˆ 908 at the load end.
D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69 67

Fig. 7. Variation of S with line length and approximation by cubical inter- Fig. 9. Variation of S with line length and approximation by cubical inter-
polation for L±L fault involving phases a and b at (1) aF ˆ 08 and (2) aF ˆ polation for L±L±L fault at (1) aF ˆ 08 and (2) aF ˆ 908 at the generator
908 at the generator end. end.

wavelets and the property of cubical interpolation technique Corresponding wavelet equation is given by:
are found very effective for the scheme. This proposed new
technique is suitable at any voltage level. Using the techni- LX
21
que, the location of fault can be estimated with a very high W…x† ˆ …21†k ck w…2x 1 k 2 …L 2 1† …A2†
degree of accuracy. For practical systems, the scheme will kˆ0
be very effective in locating the fault point resulting in faster
restoration of power supply.
One way of solving the dilation equation is by an iteration of
the scaling equation

Appendix A. Wavelet analysis and MRA LX


21
wi …x† ˆ …21†k ck wi21 …2x 2 k† …A3†
A.1. Dilation and wavelet equation [16] kˆ0

The wavelet transform involves two fundamental equa-


tions: (i) dilation equation and (ii) wavelet equation. The until wi21 ù wi :
dilation equation links a scaling function w…x† and its trans- The initial value of w…x†; w0 …x†; is assumed to be a unit
lates w…2x†: This is given by box function, i.e.

LX
21 (
1 0#x#1
w…x† ˆ ck w…2x 2 k† …A1† w0 …x† ˆ …A4†
kˆ0 0 x.1
where L is an even number.

Fig. 8. Variation of S with line length and approximation by cubical inter- Fig. 10. Variation of S with line length and approximation by cubical
polation for L±L fault involving phases a and b at (1) aF ˆ 08 and (2) aF ˆ interpolation for L±L±L fault at (1) aF ˆ 08 and (2) aF ˆ 908 at the load
908 at the load end. end.
68 D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69

The numerical values of ck for D-8 wavelet considered in and if the levels are denoted by …y1 ; y2 ; y3 ; ¼; yN11 †; then
this work are taken from Refs. [16,17].
y1 ˆ …A0 †T a…1†; y2 ˆ …A1 †T a…2†;
If the input signal be denoted by g…x†: Then the decom-
posed signal is given by 6 7
6 a…2N21 1 1† 7
" # 6 7
a…3† 6 7
T6
6 . 7
7
X
3 y3 ˆ …A2 †T ; ¼; yn11 ˆ …AN † 6 .. 7
g…x† ˆ a0 w…x† 1 a1 W…2x† 1 ai W‰2x 2 …i 2 2†Š a…4† 4 5
N
iˆ2 a…2 †
X
7 …A9†
1 ai W‰2x 2 …i 2 4†Š 1 ¼
iˆ4
The original signal is reconstructed as
nX
11
2NX
21
Yr ˆ yk …A10†
1 ai W‰2N21 x 2 …i 2 2N21 †Š …A5† kˆ1
iˆ2N 2 1

A.4. Interpolation technique [20]


where ai represents wavelet coef®cients.
When a suitable model of a data set is created, then it is
possible to estimate the value of the dependent variable for
A.2. Calculation of wavelet coef®cients any desired value of independent variable. When the desired
value of the independent variable lies within the range of
The coef®cients ai are calculated using Mallat's algo- magnitude of the independent variable of the data set, then
rithm [13]. The calculation of ai requires the transformation the estimation is called interpolation.
matrices Li and Hi for i ˆ 1; 2; ¼; N which are of dimen- Hence, we ®nd that, if a function f …x† is given in an
sions …2i21 £ 2i †; where L and H are formed from low-pass interval a # x # b; and we want to approximate f …x† over
and high-pass D-8 ®lter coef®cients. that interval by a function g…x†:
The wavelet coef®cients are calculated using Li and Hi as Then, in the case of cubic interpolation technique, the
follows. If we de®ne function f …x† is approximated by a single polynomial of
! third degree over the entire interval a # x # b: However,
Y
N there will be oscillations between the common endpoints or
Ak ˆ Hk Li …A6† knots but it depends on the distribution of the data points in
iˆk 1 1
the function f …x†: Thus, if a function f …x† is approximated by
a function g…x† in the interval a # x # b by a cubic poly-
where k ˆ 0; 1; 2; ¼; N 2 1 and with HN ˆ AN and H0 ˆ 1; nomial, then the equation for g…x† is given by g…x† ˆ a 1
then bx 1 cx2 1 dx3 for a # x # b:
2 3 The order of the polynomial depends on the number of
A0
6 7 data points available. For nth order polynomial, it requires a
6A 7 minimum of …n 1 1† data points. Thus, for a cubic inter-
6 17
6 7 polation technique, there should be atleast four data points.
Gˆ6 . 7 …A7†
6 . 7
6 . 7 All the intermediate points in the entire interval is estimated
4 5
by the interpolation technique once the function f …x† is
AN
approximated by a cubic polynomial.
is a …2N £ 2N † dimension matrix.
If …2N † diagonal matrix D be de®ned as D…1; 1† ˆ 22N ; References
D…2; 2† ˆ 22N ; D…j; j† ˆ 22…N122i†; where i ˆ 3; 4; ¼; N 1
1 and j ˆ 2i22 1 1; 2i22 1 2; ¼; 2i21 and if a is a vector [1] Takagi T, Yamakoshi Y, Baba J, Uemura K, Sakaguchi T. A new
of wavelet coef®cients, then algorithm of an accurate fault location for EHV/UHV transmission
lines. Part I. Fourier transform method. IEEE Trans Power Appar Syst
1981;PAS-100(3):1316±22.
a ˆ DGy …A8† [2] McInnes A, Morrison IF. Real-time calculation of resistance and
reactance for transmission line protection by digital computer. EE
where y is the …2N £ 1† vector of the signal. Trans Inst Engr, Aust 1971;EE-7(1):1623.
[3] Ranjbar A, Cory BJ. An improved method for the digital protection of
high voltage transmission line. IEEE Trans 1975;PAS-94(2):554±6.
[4] Westlin SE, Bubenko JA. Newton±Raphson technique applied to the
A.3. Signal reconstruction and individual signal levels fault location problem. IEEE PES Summer Meeting A76 334-3; 1976.
[5] Takagi T, Yamakoshi Y, Baba J, Uemura K, Sakaguchi T. A new
If a signal of length 2N is decomposed to …N 1 1† levels algorithm of an accurate fault location for EHV/UHV transmission
D. Chanda et al. / Electrical Power and Energy Systems 25 (2003) 59±69 69

lines. Part II. Laplace transform method. IEEE Trans Power Appar [13] Mallat SG. A theory for multiresolution signal decomposition: the
Syst 1982;101(3):564±73. wavelet representation. IEEE Trans Pattern Anal Mach Intell 1989;
[6] Thorp JS, Phadke AG, Horowitz SH, Beehler JE. Limits to impedance 11(7):674±93.
relaying. IEEE Trans Power Appar Syst 1979;PAS-98(1):246±60. [14] Zhao W, Song YH, Min Y. Wavelet analysis based scheme for fault
[7] Richards GG, Tan OT. An accurate fault location estimator for trans- detection and classi®cation in underground power cable systems.
mission lines. IEEE Trans Power Appar Syst 1982;PAS-101(4):945± Electr Power Syst Res 2000;53:23±30.
50. [15] Asamoah F. Discrete wavelet analysis of signals. Int J Electl Engg Ed
[8] Wiszniewski A. Accurate Fault Proceedings, vol. 130(6), part C; 1999;36:255±63.
November 1983. p. 311±4. [16] Newland DE. An introduction to random vibrations, spectral and
[9] Sachdev MS, Agarwal R. A technique for estimating transmission line wavelet analysis. New York: Wiley, 1994. Chapter 17; p. 295±339.
fault locations from digital impedance relay measurements. IEEE [17] Daubechies I. Orthonormal bases of compactly supported wavelets.
Trans Power Deliv 1988;3(1):121±9. Commun Pure Appl Maths 1988;41:909±96.
[10] Abur A, Magnago FH. Use of time delays between modal components [18] Liang J, Elangovan S, Devotta JBX. A wavelet multiresolution analy-
in wavelet based fault location. Electl Power Energy Syst sis approach to fault detection and classi®cation in transmission lines.
2000;22:397±403. Electl Power Energy Syst 1998;30(5):327±32.
[11] Liang J, Elangovan S, Devotta JBX. Application of wavelet transform [19] Chanda D. Analysis of power system transients empolying wavelet
in traveling wave protection. Electl Power Energy Syst 2000;22:537± transform. Ph. D. thesis: Indian Institute of Technology, Kharagpur,
42. India.
[12] Chui C. An introduction to wavelets. New York: Academic Press, [20] Kreyszig E. Advanced engineering mathematics. 5th ed. New York:
1992. Wiley, 1991. p. 781±2.

Anda mungkin juga menyukai