Anda di halaman 1dari 2

NR Electric Co., Ltd.

PCS-9705
Bay Control Unit

The PCS-9705 Bay Control Unit (abbreviated as BCU) is used The PCS-9705 is designed for switchgear monitoring and
for bay level controlling and monitoring in substation, power controlling. Also, it supports tap changer control for transformer
plant and industrial domain. It is suitable for an application or shunt reactor. Additionally, closing synchronism check (25)
in Substation Automation System (abbreviated as SAS) with and auto-reclosing (79) are integrated.
distributed control IEDs.
The PCS-9705 can be used for both single and 1½ breaker
The PCS-9705 can be applied into SAS via Ethernet network arrangements.
in using different protocols. It can send/receive Generic Object
Oriented Substation Event (abbreviated as GOOSE) message
in a station level network.

Figure 1 Functional bloc diagram

124 Read more on the web


www.nrec.com
NR Electric Co., Ltd.

Functions • Multiplex RJ-45 port for debugging

• Support of PRP/HSR network


Measurement & Control
• AC analog input (Conventional CT/VT)

• AC digital input (Electronic CT/VT, IEC 61850-9-2)


Features
• DC analog input • The PCS-9705 adopts a fully closed chassis with a complete
panel. CompletelyComplete isolation for electronic and
• DC analog output electrical systemsystems is provided.
• Configurable binary input
• A back plug-in module structure is adopted. Electrical and
• Binary output (normally open contact) for switch control and electronic circuits are strictly separated to enhance EMC
interlocking logic immunity performance.
• CB closing synchronism-check
• A back plug-in module structure is adopted.

Monitoring
• The PCS-9705 adopts NR Electric new UAPC hardware
• Switch status supervision platform, 16 bits parallel A/D converter, graphic dot matrix
• Device power supply supervision LCD, and real time multi-task operating system for industrial
purpose so as to realize the high-capacity, high-precision,
• VT circuit supervision (VTS) fast and real-time information processing.

• CT circuit supervision (CTS)


• W i t h t h e h i g h - p r e c i s i o n p a r a l l e l A / D c o n v e r t e r,
synchronization sampling can be conducted for all the
Circuit Breaker Function AC signals to ensure the accuracy of analog quantity
• Auto-reclosing (79) measurement.
• Voltage selection for closing synchronism check
• Software and hardware clock synchronization modes are
both adopted with 1ms timing accuracy to ensure the
Auxiliary Function
resolution of Sequence Of Events (abbreviated as SOE).
• Programmable interlocking logic

• GOOSE tripping (via IEC 61850-8-1) • Large scale LCD providing graph and text makes a
convenient humainhuman-machine interaction.
• Voltage and current drift auto regulation
• Support of PRP (Parallel Redundancy Protocol) and HSR
• Sequence Of Event (SOE) recorder

Automation System
(High-availability Seamless Redundancy) communication
• Disturbance & Fault Recorder (DFR) network.

• Waveform recorder
• Duplex Ethernet ports and serial ports with optical fiber or
• Multiple kinds of clock synchronization methods twisted-pair cable are provided.

Communication • Low power consumption and wide ambient temperature


range.
• Electrical Ethernet ports conform to IEC 61850 and IEC
60870-5-103 protocols over TCP/IP
• The PCS-9705 supports IEC 61850 and NR private 103
• Optical Ethernet ports conform to IEC 61850 and IEC 60870- protocols to fulfill all the requirements of conventional and
5-103 protocols over TCP/IP digital substations.
• GOOSE and SV communication
• Powerful PC configuration software can realize function
• RS-485 port for clock synchronization configuration, setting modification, customized logic
programming and waveform analysis.
• RS-232/RS-485 port for printer