Anda di halaman 1dari 7

Design calculation sheet

Project no: Date: 11/27/2019 Computed by:


Subject: Checked by:
Approved by:

Cooling plant characteristics and water flow rates calculation

Cooling plant capacity 250 T.R.

Cooling tower heat rejection 1,099 kW

Cooling tower Range ( To in - To out ) 10.0 o


F 5.6 o
C

Water flow rates


�^𝑜=𝑄/(4.18 × ∆ 𝑇)

mo = 1,099
4.18 x 5.6

mo = 47.3 L/s 749.8 gpm

Water Qualtiy

Make-up water quality T.S.E. water

Cycle of concentration 2.2

Operating hours

Equivalent operating hours 18.0 hours


Design calculation sheet
Project no: Date: 11/27/2019 Computed by:
Subject: Checked by:
Approved by:

Cooling tower calculations

Evaporation rate :
𝐸𝑣𝑎𝑝𝑜𝑟𝑎𝑡𝑖𝑜𝑛 𝑟𝑎𝑡𝑒 (𝑔𝑝�)=𝐹𝑙𝑜𝑤 (𝑔𝑝�) ×𝑅𝑎𝑛𝑔𝑒 (𝐹^𝑜)×0.001

Evaporation rate = 750 x 10.0 x 0.001

Evaporation rate = 7.5 gpm 0.5 L/s

Blow down rate :

𝐵𝑙𝑜𝑤 𝑑𝑜𝑤𝑛 𝑟𝑎𝑡𝑒 (𝑔𝑝�)=(𝐸𝑣𝑎𝑝𝑜𝑟𝑎𝑡𝑖𝑜𝑛 𝑟𝑎𝑡𝑒 (𝑔𝑝�)) /


(𝑁𝑢�𝑏𝑒𝑟 𝑜𝑓 𝑐𝑦𝑐𝑙𝑒𝑠 𝑜𝑓 𝑐𝑜𝑛𝑐𝑒𝑛𝑡𝑟𝑎𝑡𝑖𝑜𝑛 −1)

Blow down rate = 7.5


2.2 - 1

Blow down rate = 6.2 gpm 0.4 L/s

Total amount of make-up water

𝑇𝑜𝑡𝑎𝑙 �𝑎𝑘𝑒𝑢𝑝 𝑤𝑎𝑡𝑒𝑟=𝐸𝑣𝑎𝑝𝑜𝑟𝑡𝑎𝑡𝑖𝑜𝑛+𝐵𝑙𝑜𝑤 𝑑𝑜𝑤𝑛


Total make-up = 0.5 + 0.4

Total make-up = 0.9 L/s

Required utilities

Make-up water Blow-down water

56 m3 / day 26 m3 / day

0.9 L/s 0.4 L/s


Design calculation sheet
Project no: Date: 11/27/2019 Computed by:
Subject: Checked by:
Approved by:
Cycle of
Water Qualconcentra
tion
Fresh Wate 5
T.S.E. wat 2.2

Source Baltimore technical data - Formulas and Tables


Page : J-24

Source Mcgraw-Hill - Handbook Of Air Conditioning And Refrigeration (2Nd Edition)


Page : 10.40
Source ASHRAE - Systems aChapter 12 - Hydronic Heating and cooling system Design - 20
Page : 12.3
Refrigeration (2Nd Edition)
and cooling system Design - 2008