Function The scope and meaning of the parameters

1 slope
2 limit current
3 slope + limit current
4 slope + soft stop
5 limit current + soft stop
6 slope + limit current + soft stop
7 jumps + slopes
8 jumps + slopes + current limits
9 jumps +ramps + soft stops
10 Jumps, Slopes, Limits, Soft Stops
11

Sudden voltage 40-100% of grid voltage

Jump time 0.02-2.00s

Slope initial voltage 0-50% of grid voltage

Slope start-up time 0-200s

Start current limit value 100-500% of the rated current for the soft starter

Limit current start protection time 1-200s

Soft stop base voltage 50-100%

Soft stop disconnect voltage 0-40%

Soft parking time 0 -30s

Point voltage 0-100% of grid voltage


Factory value

50%

0.20s

25%

30 S

300%

30 S

70%

15%

5S

30%