/ APPLICATION NOTE

TRANSFORMER MONITORING

Online Moisture Monitoring for


Power Transformers
Power transformers represent 60% react with the cellulose molecules in discharge that damages the
of the asset value in a high voltage and break them down. This is transformer.
substation, making them among the important as when the water content
most expensive assets in electricity in the paper doubles, it can cut the
transmission and distribution. remaining life of the transformer in
Evaluating Moisture
Knowing the condition of power half.
Dynamics
transformers is key to ensuring A scheduled oil sample and KF
reliable grid operation, improving Poor oil quality and high moisture titration in a laboratory is the
risk assessment, and implementing levels can lead to low dielectric common practice for estimating the
more effective maintenance strength and eventual system failure. moisture level of transformer paper
strategies. It has been reported that when based on the moisture-in-oil reading.
relative moisture saturation goes The oil sample for analysis should be
Moisture is one of the dominant above 20%, the relative saturation taken when the insulation system is
factors that limit the lifetime of a (RS) dielectric strength of oil starts in equilibrium and thermally stable
power transformer. For effective to decrease rapidly (Vaisala White – in other words, when winding and
transformer lifetime management, Paper The Effect of Moisture on the oil temperatures have been relatively
the moisture content of the insulation Breakdown Voltage of Transformer constant for a longer period of time.
system, cellulose, and oil should be Oil B211282EN-A).
kept at a low level. But is this really practical? In general,
When the temperature rises, high most water is found in the solid
After initial factory drying, the water content in the insulation, insulation paper and other cellulosic
moisture content in solid insulation combined with dissolved gases in materials. The cellulose-oil insulation
is typically between 0.5 and 1% the oil, may cause bubble formation system in a transformer is complex
depending on requirements, and if the total pressure of gases and in regard to moisture distribution as
starts to increase gradually over the water vapor exceeds the oil pressure the oil and cellulose exhibit reverse
operating lifetime of the transformer. of the transformer. If bubbles form moisture absorption behavior – at
The main moisture sources are or travel into energized parts of the increasing temperatures, moisture is
residual moisture in thick structural transformer like the windings, there released from the paper surface and
cellulose components, ingress from is a severe risk of system failure dissolved in the oil, and absorbed
the atmosphere, and small amounts due to sudden local collapse of the back from the oil to the paper as
of moisture generated as a by- dielectric-medium. temperatures decrease. There may be
product of cellulose decomposition. considerable short-term variation in
In a wet transformer, exceptional the oil moisture driven by changes in
high-loading events can drive excess transformer loading and the ambient
Issues Caused by Moisture moisture from the paper into the oil, temperature. The higher the water
In a power transformer, the majority creating relative moisture saturation content in the paper insulation, the
of water is found in the solid paper of 100% RS and the formation of bigger the variation in oil moisture
insulation. Higher water content free water. The same may happen during temperature fluctuation.
leads to accelerated deterioration if a heavily loaded wet transformer
of the paper, reducing its degree of cools down quickly. Free water may The moisture absorption back
polymerization (DP). Moisture and cause corrosion and rust particles in to paper is a significantly slower
heat provide an optimal environment oil circulation pipes and radiators. process than desorption. This can
for various compounds in the oil – In the worst case, free water can be seen as clear hysteresis in online
such as acids and metal ions – to form around active parts, resulting moisture monitoring data measured
60
as a function of transformer
temperature (Figure 1). With such 50
strong moisture dynamics, it may

Oil moisture (ppm)


be difficult or even impossible to 40

determine the correct moment to


take a representative oil sample for 30
Figure 1. Online moisture
laboratory analysis. For example, monitoring data in ppm
20
if the oil sample is taken from the during temperature
above-mentioned transformer at fluctuation in a 10 MVA
10
35°C, the laboratory result may give 10 15 20 25 30 35 40 45 50 55 (ONAN) transformer
Temperature (°C)
30 ppm or 50 ppm depending on
whether the transformer is in the
cooling or loading phase at the point The moisture dynamics of a operational safety margin. Moreover,
of sampling. Such a large variation transformer during normal operating by using moisture sensor readings
may lead to significantly erroneous conditions can be significant. Online in ppm and published equilibrium
conclusions about the condition of monitoring provides the operator moisture charts, it is possible
the transformer. with valuable information on oil to estimate the water content in
moisture, enabling further analysis the cellulose insulation during
The lower the operating temperature such as evaluation of the risk of transformer operation. This would
of a transformer, the less water is moisture saturation and decreased typically demand an intelligent
found in the oil. This is an important dielectric strength, as well as input cooling system in order to maintain
fact to take into account when data for paper moisture evaluation. the temperature as constant as
assessing the moisture content Online monitoring allows the possible during the time period
in solid insulation and evaluating operator to detect evolving moisture- needed to reach the moisture
its effect on safe operation. A related risks and other early signs equilibrium state.
transformer that operates normally of faults – and react appropriately.
at a relatively low temperature For example, a transformer with high Alternatively, moisture and
and with low oil moisture can have moisture levels may not be permitted temperature readings can be
rapidly increasing moisture in oil to run at full load until dry-out has taken as an average from a longer
levels during a single heavy overload occurred. This can be considered an period, which represents moisture
event due to temperature-induced operational limit, and may differ from equilibrium better than a single point
moisture migration from the paper the nominal limit, which in general oil sample during dynamic loading.
surface. The return of moisture to assumes serviceable and dry oil. Recently published literature also
the previous “normal” level may evaluates cellulose moisture directly
take days or even weeks, meaning Online moisture monitoring can from the measured relative moisture
that during a cooling period, relative provide valuable information on saturation and temperature of oil
moisture saturation can become transformers that have previously (CIGRE TB349).
dangerously high. been identified as having moisture
problems. It is also valuable for Finally, it’s important to remember
relatively lightly loaded transformers that monitoring alone will not fix
Benefits of Online that may have moisture issues that anything – only taking action based
Moisture Monitoring have not been detected by routine oil on monitoring information will result
Online monitoring gives a true and sampling. in condition improvement in the
real-time picture of the moisture long run.
levels in transformer oil in all A moisture sensor provides
operating conditions. the transformer with a proper

Please contact us at Ref. B211611EN-A ©Vaisala 2017


This material is subject to copyright protection, with all

www.vaisala.com/requestinfo copyrights retained by Vaisala and its individual partners. All


rights reserved. Any logos and/or product names are trademarks
of Vaisala or its individual partners. The reproduction, transfer,
distribution or storage of information contained in this brochure
in any form without the prior written consent of Vaisala is strictly