1)Required following Relay Manuals.

POWER
SR NO RELAY NAME GA REF. MAKE TYPE SPECIFICATION
SUPPLY

CT SEC – 1AMP, BIAS SETTING – 10-50%,


NUM. OVERALL DIFF. SUITABLE FOR 3 WDG TRAFO WITH IEC
1 PROTECTION 87 – 0 ER DUOBIAS-M200 PROTOCOL, WD NO.- 2661W11002 230V DC
STAND BY E/F RELAY FOR CT INPUT – 1A, CASE SIZE – 2/3V, WD NO.-
2 GEN. TRANSFORMER 64S – GT ER MIT161 8431W20161, E/F – 0.5% - 25% IN STEP OF 0.5% 230V DC
CT INPUT – 1A, CASE SIZE – 2/3V, 3 O/C & 1E/F,
O/C & E/F REALAY FOR 50 / 51 RNB – CHARACTERSTICS DTL, SI1,SI3,VI,EI,LTI, WD NO.-
3 GEN.TRANSFORMER GT ( HV ) ER MIT114 8431W21504 230V DC
CT SEC – 1AMP, BIAS SETTING – 10-50%,
NUM. DIFF.& REF SUITABLE FOR 2 WDG TRAFO WITH IEC
4 PROTECTION RELAY 87 - GT ER DUOBIAS-M200 PROTOCOL, WD NO.- 2661W11006 230V DC
CT SEC – 1AMP, BIAS SETTING – 10-50%,
NUM. DIFF.& REF SUITABLE FOR 2 WDG TRAFO WITH IEC
5 PROTECTION RELAY 87 - UAT ER DUOBIAS-M200 PROTOCOL, WD NO.- 2661W11006 230V DC
CT INPUT – 1A, CASE SIZE – 2/3V, 3 O/C & 1E/F,
O/C & E/F REALAY FOR 50 / 51 RNB – CHARACTERSTICS DTL, SI1,SI3,VI,EI,LTI, WD NO.-
6 UAT.TRANSFORMER UAT ( LV ) ER MIT114 8431W21504 230V DC
STAND BY E/F RELAY FOR CT INPUT – 1A, CASE SIZE – 2/3V, WD NO.-
7 UAT TRANSFORMER 64S – UAT ER MIT161 8431W20161, E/F – 0.5% - 25% IN STEP OF 0.5% 230V DC
ROTOR EARTH FOULT NUMBER OF STAGE – TWO WITH
8 PROTECTION RELAY 64F AVK-SEGC MRG1 PROGRAMMABLE OUTPUT 230V DC
NUMBER OF O/P RELAYS – 3, INPUT SUPPLY
9 VECTOR SARGE RELAY 74 AVK-SEGC MRG2 110V AC 230V DC
OUT PUT RELAY – 5, STATUS INPUT – 3 WITH
10 AUTO. SYNCHRONISER AS L&T SPM21 RS485 COMMUNICATION 230V DC
GEN. PROTECTION RELAY BECKWITH-
11 MAIN GPR – M M3425A,USA PT – 110V AC. CT – 1A 230V DC
12 DE MULTI UNIT MAIN DM – M ER REIO-1 NO. OF OUTPUT RELAYS – 32 230V DC
GEN. PROTECTION RELAY BECKWITH-
13 REDUN. GPR – R M3425A,USA PT – 110V AC. CT – 1A 230V DC
14 DEMULTI UNIT REDUN. DM – R ER REIO-1 NO. OF OUTPUT RELAYS – 32 230V DC
CT INPUT – 1A, CASE SIZE – 2/3V, 3 O/C & 1E/F,
CHARACTERSTICS DTL, SI1,SI3,VI,EI,LTI, WD NO.-
15 O/C & E/F REALAY FOR GEN. 50 / 51 RNB ER MIT114 8431W21504 230V DC
2)AVR Panel asbuilt drawing as well as manual required.
3)GCP GRP Panel Precommissioning activites list.
4)Pending points in MOM with Power Gear, which are still not cleare from them.i.e. Point no. 06 ( Provision of Shorting Bus Bar
5)Assembly and de-attachable barrier sheet.
6)Point No. 10 drawing of S8
7)Short supply material in HT Busduct MRJ-1 Al. Couppling plate 12 no. ( 260mm x 100mm x 12mm )
8)EJ -01 Al. Flexiable 12no. ( 570mm x 100mm x 12mm )
9)Pitting and deteoriation on couppling plate ( TRJ – 2 , 24no. / TRJ – 4 , 08no. / TRJ – 5, 04no.) ,After silver plating on this particular plate the
problem of pitting continues ,can not be neglected with respect to future.
10)Clarity in drawing of all copper termination at G.T. , UAT, LAVT, NGTR cubilcal