VERMONT
Successful
Cooling System
Energy
Optimization
Topics for Discussion
• Customer Charge
• Electric Fuel Charge Adjustment
– Fuel Charge Adjustment
• Environmental Surcharge
• Energy Charge
• Kilowatt (kW) Demand/Delivery Charge
• Power Factor Adjustment/Penalty
ASHRAE 90.1-2001 (Mandatory Provisions)
• Full Load (FL)
– Predicts performance at a single operation point
• Doesn’t anticipate how equipment will respond
during off-design conditions
• Equipment with excellent full-load characteristics
may have less than satisfactory part-load
characteristics
• Integrated Part Load Value (IPLV)
– Predicts performance over a defined range of
operating points
• Provides a more accurate account of actual
equipment operation
Equipment Evaluation
Air-Conditioning & Refrigeration Institute
• Provides programs to certify manufacturer’s
published equipment data
– Verified through random testing
• Equipment labeled when in compliance
ARI Standard 550/590-98
Standard defining the testing and rating
requirements for all chillers
Provides an equal baseline for all
manufacturers
Defines testing conditions for real-world,
chiller performance
ARI Standard 550/590-98
• Developed through real-world studies
– 1992 U.S. Department of Energy Study
• DOE/EIA-0246(92)
– 1995 Building Owner’s & Managers Assn.
• 1995 BEE Report
12
kW / ton =
EER
Equipment Evaluation
A/C Chillers w/Condenser
Minimum Efficiencies
COP EER kW / TON
2.80 FL 9.56 FL 1.26 FL
3.05 IPLV 10.41 IPLV 1.15 IPLV
IPLV Comparison
A/C Chiller A = 12.5 EER A/C Chiller B = 15.2 EER
kW/ton12.5 = 12/EER kW/ton15.2 = 12/EER
= 12/12.5 = 12/15.2
= 0.96 kW/ton = 0.79 kW/ton
$15,952
difference!
System Considerations
Air-cooled system Water-cooled system
• Low maintenance Higher maintenance
• Low installation and
equipment costs High-efficiency
• Higher Energy High installation costs
Consumption Low sound
• Water Scarcity
1.100
1.000
Entg Cond
0.900 Wtr Temp
0.800 55 F
kW/ton
0.700 65 F
75 F
0.600 85 F
0.500
0.400
0.300
0.200
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Pct Load
VAR SPEED Chiller Efficiency Matrix
1.100
1.000
Entg Cond
0.900 Wtr Temp
0.800 55 F
kW/ton
65 F
0.700
75 F
0.600 85 F
0.500
0.400
0.300
0.200
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Pct Load
Cooling tower entering condenser
water bin hours for Burlington Vt.:
• 85F ECWT = 10 hrs
• 75F ECWT = 1000 hrs
• 65F ECWT = 1450 hrs
• 55F ECWT and below = 6300 hrs
Chiller Performance Generalities:
• Lower lift = less compressor
energy (Compressor lift is the
difference between the suction and
discharge pressure).
• Capacity has less affect on
compressor performance than lift.
• Different chillers have different
minimum lifts due to design
differences…
Compressor
Flooded
Evaporator
Condenser
@ 44F
@ 85F leaving
ECWT chilled water
Refrigerant Refrigerant
pressure= pressure =
19.1 psia 6.1 psia
Flooded
Evaporator
Condenser
@ 44F
@ 55F leaving
ECWT chilled water
Refrigerant Refrigerant
pressure= pressure =
10.4 psia 6.1 psia
Compressor Flooded
Evaporator
@ 44F
leaving
Condenser
chilled water
@ 55F
Refrigerant
ECWT
pressure =
Refrigerant 6.1 psia
pressure=
Tubes not
10.4 psia
covered by
liquid
New Part load sound levels 5-6 dBA lower than competitors
New load shedding software for noise level management
Soft Start Capabilities for increased motor life
New
New Reduced Full load amps for a reduction in wire sizing
Performance matters
The power of
off design on
Energy - 98%
of operating
hours are at
off design
conditions
$10,000
load points
Annual Savings
5000vshours
– 5000
12.5 15.2 IPLV
$8,000
hours
$7500/year
– savings
$.0813/kWh
$6,000