GENSET PERFORMANCE DATA

Customer Name PLTD Generator Model C900D5


Engine Model : QSK23 - G3 𝐕 𝒙 𝑰 𝒙 √� Generator Model S/N F17K202848
KW= x PF
Engine S/N : 85003038 1000 Genset No. 1 (satu)
Alternator S/N : A17E198804 Capacity No. 500 KW
Testing Date : 10 April 2018 Sheet No. :1
HP = 0,746 KW=

A. Genset Operating Data Test

Time Load (%) HM Voltage Ampere KW KWH PF Freq (Hz)


R-S S-T T-R R S T
14:00 50% 552 380 380 380 389 428 424 252 146,524 0.93 50
15:00 50% 553 380 381 380 389 425 426 252 146,774 0.94 50
18:00 75% 556 380 381 381 540 545 558 358 147,850 0.96 50
21:00 75% 559 381 380 380 542 543 558 358 148,920 0.97 50
100%

B. Max. Load Condition C. Electrical Control Panel (Switchboard) D. Maintenance Evacua


INSPECTION ITEM CONDITION INSPECTION ITEM CONDITION INSPECTION
Fuel Rail Pressure PSI Voltage Meter OK Engine Oil
Turbo Boost Pressure In.Hg Ampere Meter OK Engine Oli Filter
Engine Blow by In.Hg Frequency Meter OK Fuel Filter
Exhaust Gas Temp. 454 Deg. C KW Meter OK Air Cleaner
Exhaust Smoke Normal DCA Consitration

E. Engine Safety Device (Shutdown) F. Performance Test


INSPECTION ITEM CONDITION *Lakuan pengujian performance test pada load 50% selama 1 jam tan
Fuel Rail Pressure PSI *Lakuan pengujian performance test pada load 75% selama 2 jam tanpa berhenti (beban stabil, load tidak boleh
Turbo Boost Pressure In.Hg *Lakukan pengujian performance test pada load 100% selama 1 jam tanpa berhenti (beban stabil, load tidak bole
Engine Blow by In.Hg *Lakukan pengujian performance test pada load 110% selama 1 jam tanpa berhenti (beban stabil, load tidak bole
Exhaust Gas Temp. Deg. C *kemudian pengujian pada load 100% selama 3 jam tanpa berhenti (beban stabil, load tidak boleh kurang dari 10
Exhaust Smoke *Kemudian pengujian pada load 100% selama 3 jam tanpa berhenti (beban stabil, load tidak boleh kurang dari 1
*Pencatatan setiap 10 menit
*Penstabilan beban selama 30 menit
* Lakukan pencatatan SFC

PT. ALTRAK 1978 PT. PLN (PERS

(.....................................) (......................................) (............................................)


Oil Press W/Temp. Man.Temp. Ambient Humadity
RPM
PSI/kpa Deg. C/F Deg. C/F Deg. C/F %
63 76 81 1500 27 39
63 76 82 1500 27 39
64 78 83 1500 28 45
64 78 84 1500 29 41

Maintenance Evacuation
INSPECTION ITEM CONDITION
ne Oil GOOD
ne Oli Filter GOOD
Filter GOOD
leaner GOOD
Consitration

50% selama 1 jam tanpa berhenti (beban stabil, load tidak boleh kurang dari 50%)
abil, load tidak boleh kurang dari 75%)
stabil, load tidak boleh kurang dari 100%)
stabil, load tidak boleh kurang dari 110%)
k boleh kurang dari 100%)
k boleh kurang dari 100%)

PT. PLN (PERSERO)

(...............................................)
Customer Name : PLTD Kelong Generator Model : C900D5
Engine Model : QSK 23 G3 Generator Model S/N : F17K201624
Engine S/N 85002998 SMR :
Alternator S/N : X17B063702 Genset No. : G1
Testing Date : Capacity No. :

LOAD REJECTION TEST


DAYA DAYA POWER LUBE OIL COOLING OIL TEMP FUEL BATTERY
REAKATIF FREQ. VOLTAGE AMPERE TEMP. TEMP. SPEED
TIME AKTIF FACTOR PRESSURE VOLTAGE Keterangan
(Hz) (V) (A) (ºC) (rpm)
(kW) (kVar) (PF) (PSI) (ºC) (ºC) (V)
0 0 49,98 380 0 1 70 77 64 32 26,93 1500 Kondisi sebelum diuji
378 112 50,02 380 564 0,95 67,1 77 79 33 27,24 1500 Kondisi sebelum diuji
0 0 49,95 380 0 1 71 77 78 44 27,70 1500 Kondisi sebelum diuji

Noted : Test dilakukan pada beban 50% dan beban 75% hingga MCR (Maximum Continuous Rating)
kemudian beban jaringan dilepas sampai 0% atau tanpa beban dan kondisi Genset tidak boleh shutdown.

PT. ALTRAK 1978 PT. PLN (PERSERO)


gan

um diuji
um diuji
um diuji
PT. ALTRAK 1978

AREA/LOCATION PLTD PULAU BURUNG MANUFACTURE KYORitsu


SYSTEM : MEASURE EARTH TEST CALIBRATED DATE :10-9-2017
EARTHING RESISTANCE TEST RECORD
TOOL NAME : TYPE/SERIAL NO : Earth tester 4105 A
DATE 14 JANUARI 2018
TEST TEST ELECTRODE SPACING SOIL ELECTRODE UNDER TEST RESULT TEST
REMARK
NO P C DEPTH TYPE TYPE DEPTH MATERIAL ( OHM)
1 10,000 10,000 150 TR-GROUNDING EARTH 150 CU 0.09 Good

2 10,000 10,000 150 LIGHTING PROTECTION EARTH 150 CU 0.11 Good

3 10,000 10,000 150 GENSET-GROUNDING EARTH 150 CU 0.10 Good

4 10,000 10,000 150 NGR-GROUNDING EARTH 150 CU 0.08 Good

PT. ALTRAK 1978 PT. PLN (PERSERO)

(..........................) (.................................) (.............................) (.............................)


PT. ALTRAK 1978

AREA/LOCATION PLTD PULAU BURUNG MANUFACTURE


SYSTEM : MEASURE EARTH TEST CALIBRATED DATE
EARTHING RESISTANCE TEST RECORD
TOOL NAME : TYPE/SERIAL NO
DATE 14 JANUARI 2018
TEST TEST ELECTRODE SPACING SOIL ELECTRODE UNDER TEST RESULT TEST
REMARK
NO P C DEPTH TYPE TYPE DEPTH MATERIAL ( OHM)
1 10,000 10,000 150 TR-GROUNDING EARTH 150 CU 0.69 Good

2 10,000 10,000 150 LIGHTING PROTECTION EARTH 150 CU 0.64 Good

3 10,000 10,000 150 GENSET-GROUNDING EARTH 150 CU 0.70 Good

4 10,000 10,000 150 NGR-GROUNDING EARTH 150 CU 0.36 Good

PT. ALTRAK 1978 PT. PLN

(..........................) (.................................) (.............................) (.............................)


KYORitsu
:10-9-2017
: Earth tester 4105 A

REMARK
Good

Good

Good

Good

(.............................)
PT. ALTRAK 1978

AREA/LOCATION PLTD KUALA ENOK MANUFACTURE


SYSTEM : MEASURE EARTH TEST CALIBRATED DATE
EARTHING RESISTANCE TEST RECORD
TOOL NAME : TYPE/SERIAL NO
DATE 25 JANUARI 2018
TEST TEST ELECTRODE SPACING SOIL ELECTRODE UNDER TEST RESULT TEST
REMARK
NO P C DEPTH TYPE TYPE DEPTH MATERIAL ( OHM)
1 10,000 10,000 150 TR-GROUNDING EARTH 150 CU 0.45 Good

2 10,000 10,000 150 LIGHTING PROTECTION EARTH 150 CU 0.80 Good

3 10,000 10,000 150 GENSET-GROUNDING EARTH 150 CU 0.46 Good

4 10,000 10,000 150 NGR-GROUNDING EARTH 150 CU 0.32 Good

PT. ALTRAK 1978 PT. PLN (PERSERO)

(..........................) (.................................) (.............................) (.............................)


KYORitsu
:10-9-2017
: Earth tester 4105 A

REMARK
Good

Good

Good

Good

RSERO)

(.............................)
PT. ALTRAK 1978

AREA/LOCATION PLTD KUALA ENOK MANUFACTURE


SYSTEM : MEASURE EARTH TEST CALIBRATED DATE
EARTHING RESISTANCE TEST RECORD
TOOL NAME : TYPE/SERIAL NO
DATE 25 JANUARI 2018
TEST TEST ELECTRODE SPACING SOIL ELECTRODE UNDER TEST RESULT TEST
REMARK
NO P C DEPTH TYPE TYPE DEPTH MATERIAL ( OHM)
1 10,000 10,000 150 TR-GROUNDING EARTH 150 CU 0.63 Good

2 10,000 10,000 150 LIGHTING PROTECTION EARTH 150 CU 0.36 Good

3 10,000 10,000 150 GENSET-GROUNDING EARTH 150 CU 0.69 Good

4 10,000 10,000 150 NGR-GROUNDING EARTH 150 CU 0.70 Good

PT. ALTRAK 1978 PT. PLN (PERSERO)

(..........................) (.................................) (.............................) (.............................)


KYORitsu
:10-9-2017
: Earth tester 4105 A

REMARK
Good

Good

Good

Good

RO)

(.............................)