The variety of uses for the hardware, software and firmware (hereinafter ―Products‖) described in this Documentation, mandates
that those responsible for the application and use of those Products must satisfy themselves that all necessary steps have been
taken to ensure that each application and actual use meets all performance and safety requirements, including any applicable
laws, regulations, codes and standards in addition to any applicable technical documents.
In no event will Rockwell Automation, Inc., or any of its affiliate or subsidiary companies (hereinafter ―Rockwell Automation‖) be
responsible or liable for any indirect or consequential damages resulting from the use or application of the Products described in
this Documentation. Rockwell Automation does not assume responsibility or liability for damages of any kind based on the
alleged use of, or reliance on, this Documentation.
No patent liability is assumed by Rockwell Automation with respect to use of information, circuits, equipment, or software
described in the Documentation.
Except as specifically agreed in writing as part of a maintenance or support contract, equipment users are responsible for:
• properly using, calibrating, operating, monitoring and maintaining all Products consistent with all Rockwell Automation
or third-party provided instructions, warnings, recommendations and documentation;
• ensuring that only properly trained personnel use, operate and maintain the Products at all times;
• staying informed of all Product updates and alerts and implementing all updates and fixes; and
• all other factors affecting the Products that are outside of the direct control of Rockwell Automation.
Reproduction of the contents of the Documentation, in whole or in part, without written permission of Rockwell Automation is
prohibited.
Throughout this manual we use the following notes to make you aware of safety considerations:
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the drive to alert people that dangerous voltage may be present.
Labels may be located on or inside the drive to alert people that surfaces may be dangerous temperatures.
L15 - NEW Features and Extensions Using
FactoryTalk View ME v6.10 and PanelView Plus 6
Contents
Contents
Before You Begin .......................................................................................................................................... 5
About this lab .................................................................................................................................................................................... 5
Tools & prerequisites ........................................................................................................................................................................ 5
Document conventions ..................................................................................................................................................................... 6
3 of 134
Appendix A .................................................................................................................................................. 93
Creating a ‗Hello World’ Application................................................................................................................................................ 93
Applying Communications to an Application ................................................................................................................................. 108
Testing an Application on the Desktop ......................................................................................................................................... 124
4 of 134
Before You Begin
5 of 134
Document conventions
Throughout this workbook, we have used the following conventions to help guide you through the lab materials.
Words shown in bold italics Any item or button that you must select, click on, or a menu name from
(e.g., RSLogix 5000 or OK) which you must choose an option or command. This will be an actual
name of an item that you see on your screen or in an example.
Words shown in bold This is the name of an item that you see on your screen or in an
(e.g., Communication Setup) example.
Words shown underlined and enclosed in An entry that you must type in the specified field. This is information that
single quotes you must supply based on your application (e.g., a variable).
(e.g., ‘Controller1') Note: When you type the text in the field, remember that you do not
need to type the quotes; simply type the words that are contained within
them (e.g., Controller1).
Note: If the mouse button is not specified in the text, you should click on the left mouse button.
6 of 134
PanelView™ Plus 6
The PanelView Plus are operator interface terminals designed to optimize system development, performance, and efficiency.
The PanelView Plus 6 line is the latest addition to Rockwell Automation‘s versatile family of Allen-Bradley PanelView operator
interface displays for machine level operator terminal applications in industrial environments.
Enhancements to the hardware platform, embedded operating system and development environment enable users to:
Take time and costs out of application development - PanelView Plus 6 dramatically reduces development, setup and
troubleshooting time through features like tag re-use, complete Symbol Factory graphic library and pre-built face plates.
Run their processes more effectively - Improved hardware performance delivers up to 30% faster screen response,
enabling operators to navigate through screens more quickly, and can help avoid maintenance calls resulting from
mistakenly pressing inputs multiple times. In addition, new capabilities wring more value from your process.
Reduce maintenance costs - New features like on-board pdf capability and remote user access enable context-sensitive
help and can avoid on-site visits to get processes back up and running faster when things go wrong.
AC or DC
SD Card Mini B Dual Serial Power Input
Ethernet
USB USB Port
Device 2.0
FactoryTalk® ViewPoint
FactoryTalk ViewPoint is an add-on to FactoryTalk View ME running on PanelView Plus that provides for a fully scalable, fully
animated, read-only view of existing applications from a Web browser.
To make information about your plant or process available on demand from a Web browser in your office, home, or hotel, all you
have to do is select the FactoryTalk View graphic displays you want to make ready for the Web, and then publish the displays to
the FactoryTalk ViewPoint Server which runs on a PanelView Plus.
There is no installation of any Rockwell Software products on the browser computer. All you need to connect to a published
FactoryTalk ViewPoint Web application is the name (or IP address) of the PanelView Plus hosting the FactoryTalk ViewPoint
Server that stores the application.
Once you enter a simple address directly into your Web browser using the name or IP address, the browser will connect to the
published web application and open the initial display selected. Use navigation buttons in the application to view other published
displays, or use the web browser's navigation tools.
7 of 134
What is Silverlight?
FactoryTalk ViewPoint uses Microsoft‘s Silverlight technology to visualize FactoryTalk View content in a browser. Microsoft
Silverlight is a Web presentation technology that was created to run on a variety of platforms to deliver applications for the Web.
It enables the creation of rich, visually stunning and interactive experiences that can run everywhere: within browsers and on
multiple devices and desktop operating systems.
If Silverlight is not installed on a client computer that connects to the PanelView Plus and the client computer is connected to the
internet, the client computer is automatically redirected to the Microsoft Silverlight installation site for download. If the client
computer is not connected to the internet, instructions for installing Silverlight are automatically provided in the browser.
For the purpose of this lab, Silverlight has already been installed.
8 of 134
Chapter 1 – Demo
9 of 134
Before You Begin
1. Launch FTViewME Station by double clicking the icon on the PanelView Plus 6 terminal desktop.
2. Click .
5. Click .
10 of 134
Increase Line Productivity - Managing Machine / Process Parameters with Recipe Manager
Business Issue
Each time MX Toy Company approves a new toy model for production, the control engineer, Rita, spends excess time editing
recipe files within the HMI or Controller application. As a result, Rita is looking for a simplified way to manage recipes.
Solution
Rita takes advantage of the Recipe ActiveX Control which uses a CSV (Comma Separated Values) file format to easily create a
new production recipe using Microsoft® Excel. As a result, Rita is quickly able to edit an old recipe file to accommodate the new
toy model – enabling operators to immediately adjust machine parameters.
Demo
You have been asked to perform a small run of 100 Large cubes and then switch over to produce the new Keychain cube.
1. If not logged in as Operator, click the Login icon at the top of the display on the PanelView Plus 6
terminal.
User name: ‘Operator’
Password: ‘pvp6’.
The login status will update indicating Operator is logged in.
11 of 134
2. Click the Navigation icon at the top of the display.
4. Click the Recipe icon and then click the Recipe Selector icon to bring up the Recipe
selector display.
12 of 134
5. Select the Large Cube recipe in order to complete the 100 piece run by using the Up and Down arrow keys and
The recipe setup consists of two steps. The first step loads the recipe values into the memory space of the
ActiveX control. By doing this, it allows one the ability to change the values of the recipe at the terminal, if
desired, before downloading them to the controller. The second step downloads the values from the ActiveX
control‘s memory into the controller tags.
The values for Heads 1 through 3 may not change depending on what was previously loaded.
8. Select the new Keychain Cube recipe by using the Up arrow and the Enter key.
The new recipe values have now changed. Values that are different from the current values are hi-lighted in
red
13 of 134
10. Click the Download button .
The recipe values for the new Keychain cube have been downloaded to the controller and you are ready to
start production.
14 of 134
Reduce Travel Cost - Alert Personnel of Alarm and Monitor Application Remotely with ViewPoint and Email
Business Issue
Without any visibility to the system, the maintenance engineer, Bill, at MX Toy Company wastes too much time driving to the
plant to assess a non-catastrophic problem. After becoming frustrated, Bill explores alternate options.
Solution
Bill takes advantage of the E-Mail ActiveX to receive an alarm notification and then uses ViewPoint, a thin client connection via a
web browser, to remotely connect to the PanelView Plus 6 terminal. These capabilities provide Bill with real-time data and limited
control to assess the problem and respond appropriately from home. As a result, Bill has eliminated extra trips to the plant.
Email Demo
1. Click the Email icon at the top of the display on the PanelView Plus 6 terminal.
15 of 134
4. Click on the Generate Alarm button to generate an alarm.
The Subject and Body fields are populated appropriately and the alarm is sent
You should see Mail Sent Successfully in the Mail Status field.
If any configuration or transmission error occurs, the alarm message is not sent. An error message and error code will appear in
the Mail Status field.
16 of 134
5. On the Lab PC, click Start > All Programs > Microsoft Office > Microsoft Outlook 2010.
17 of 134
9. Click the PanelView Plus SMTP Demo Email link to view the Email.
18 of 134
ViewPoint Demo
1. Launch Internet Explorer on the PC and enter the following address: http://192.168.1.20/FTVP where
192.168.1.20 is the IP address of your PanelView Plus.
19 of 134
2. Click the Navigation icon in the upper left corner to navigate to the 81 Motor Start display.
4. Click on the New value for the pelleter to bring up the numeric entry keypad.
20 of 134
5. Using the keypad, enter the same value that appears in the Current column. In the example below, it‘s 300.
You may need to drag the keypad to the left in order to fully view it.
21 of 134
Trending
A FactoryTalk ViewPoint trend consists of the trend chart, the pens, a current value legend, a value bar, an X and Y axis, play
and pause buttons, and a pan and zoom slider. Note all the components that make up the trend control.
Y and X axes
Pan and Zoom Play and pause
slider
1. Clear or select the pen‘s checkbox to hide or show the associated pen.
22 of 134
2. Click on the green pen Temperature to display its value range on the Y-axis. If it intersects the value bar, its
tooltip will be larger than others on the value bar.
3. Drag the value bar across the trend data in a FactoryTalk ViewPoint trend to display values associated with
specific trend data points. Note the pen values in the tooltip and current value legend also update to the value
where the pen intersects the value bar. Also note that the trend is paused anytime you interact with it.
4. Click Play to resume viewing data from the point where the trend was paused.
5. Click and drag the left handle on the horizontal slider back and forth to zoom into and out of the trend data.
6. Click and drag the slider back and forth to pan the trend data.
7. Click anywhere on the trend chart and drag back and forth as another method to pan the data.
23 of 134
Reduce Travel Cost - Remote Display Access with New VNC
Business Issue
MX Toy Company fixed a broken Powder Feeder so Laura, Mark‘s manager, has to monitor the data trend to provide a status
update to the plant manager the next morning. However, Laura prefers to monitor it remotely from home.
Solution
Mark uses the IP Info ActiveX tool to provide Laura with the IP address of his terminal. Laura connects to the company‘s VPN
and then to the terminal through VNC using a view only password. She is now able to view a live feed of the terminal‘s display
and is able to monitor the trend data.
Demo
1. Login as Mark by clicking the Login icon at the top of the display on the PanelView Plus 6 terminal.
User name: ‘Engineer’
Password: ‘pvp6’
The login status will update indicating Engineer is logged.
2. Click the Diagnostics icon at the top of the display. Record the IP Address found in Network
Information for the VNC connection.
24 of 134
3. As Laura, launch the TightVNC client from the PC, Start > All Programs > TightVNC > TightVNC Viewer.
25 of 134
6. As Laura, using the VNC connection, try clicking on the icons across the top of the application. Nothing should
happen as Laura only has view control.
7. As Mark, click the Navigation icon at the top of the display on the PanelView Plus 6 terminal.
26 of 134
10. Click on the middle of the feeder to return to the previous display. Feel free to view data for Powder Feeders 2,
3, and 4.
11. Exit the VNC connection on the PC by clicking the X to close the window.
27 of 134
Increase OEE - Archive Production Data with DataStore Plus
Business Issue
MX Toy Company invested in a new production line which is expected to yield higher throughput. The production engineer,
Marcus, is responsible for maximizing throughput and generating daily performance reports.
Solution
Marcus uses the Data Store Plus ActiveX to daily archive new data log files in a CSV (Comma Separated Values) file format. To
access this data from the terminal, Marcus conveniently uses the FTP feature of the PanelView Plus 6 to copy the CSV log files
directly to his PC in order to easily trend and generate yield reports using Microsoft® Excel. As a result, Marcus has optimized
inefficiencies within the new production line.
Demo
1. If not logged in as Engineer, click the Login icon at the top of the display on the PanelView Plus 6
terminal.
User name: ‘Engineer’
Password: ‘pvp6’.
The login status will update indicating Engineer is logged in.
4. Open Internet Explorer on the PC, enter the following information into the address field, and press Enter.
28 of 134
You will receive the following error:
29 of 134
7. Right click on the white space of the new window and select Login as …
8. Enter ‘User1’ and ‘Pass1’ for the login information and click Logon.
9. You are now connected to the PanelView Plus 6. Open the My Documents folder.
30 of 134
10. Copy one of the 3, CSV files from the terminal to the desktop of the PC by dragging the file over.
11. Exit the FTP connection by closing both Internet Explorer windows on the PC.
12. Open the CSV file located on the desktop of the PC and examine its contents.
14. Start the datalog again by clicking the Datalog selector switch on the PanelView Plus 6
terminal.
31 of 134
Reduce Down Time - Troubleshoot System Status using Faceplates
Scenario
Barry is an engineer at the MX Toy Company. Barry receives a message from production that the currently running toy cubes
are not being formed properly. Barry would like to quickly identify what is causing the anomaly.
Solution
Barry accesses the PanelView terminal screen remotely and navigates to the display that contains the ControlLogix faceplate.
Barry uses the faceplate to determine a minor fault has occurred in the Program and proceeds to investigate what caused the
minor fault using RSLogix 5000.
Demo
1. If not logged in as Engineer, click the Login icon at the top of the display on the PanelView Plus 6
terminal.
User name: ‘Engineer’
Password: ‘pvp6’.
The login status will update indicating Engineer is logged in.
32 of 134
2. Click the Diagnostics icon at the top of the display to bring up the Maintenance display.
33 of 134
4. Click the Fault icon on the faceplate to bring up the controller fault status.
5. Click the Trigger Fault button to simulate a minor fault – the Program Fault indicator lights
red.
34 of 134
6. On the PC, click Start > All Programs > Rockwell Software > RSLogix 5000 Enterprise Series > RSLogix
5000.
8. Select Upload
35 of 134
10. Select Minor Faults to obtain more details regarding the minor fault.
11. Click Clear Minors to reset the Program Fault indicator on the Controller faceplate.
36 of 134
12. Exit RSLogix 5000.
37 of 134
Reduce Maintenance Cost - Switch Application Language to Operator’s Native Language
Business Issue
Because the MX Toy Company is shipping new machines to its new production facilities in Europe and Asia, the control engineer
has to create and manage multiple HMI application files which are in the native language specific to the operators so they can
operate the equipment. Managing multiple files is challenging and time consuming.
Solution
The control engineer takes advantage of PanelView Plus language switching capabilities which allows him or her to manage only
one HMI application file. With the push of a button, the operator can simply change the application language to his or her native
language. As a result, the file managing time is reduced because only one application file is required for standardize machines
that ship to different countries.
Demo
1. Click the Home icon at the top of the display of the PanelView Plus 6 terminal to select the overview
display. If the icon is not visible, the application is at the overview display already.
38 of 134
2. Click the Globe icon at the top of the display to bring up the language selection buttons.
3. Click the Chinese flag and notice that most of the text has changed on all of the status objects.
4. Click the other flags and notice how quickly the languages change.
39 of 134
Reduce Development Time - Reuse Common HMI Components with Global Objects
Business Issue
There are four identical Powder Feeders in The MX Toy Company production plant and each one is represented on a different
HMI screen. The control engineer, Ray, has to individually edit each Powder Feeder throughout his development project when
the same updates are required to each Powder Feeder. This repetitiveness consumes too much time – preventing Ray from
working on other projects.
Solution
Ray takes advantage of Global objects with parameter passing to consolidate four HMI screens of the Powder Feeders into one
HMI screen which serves as an overview of all four Powder Feeders. However, each Powder Feeder maintains its unique set of
controller tag values by parameter passing in the specified set of unique tags associated with each Powder Feeder. As a result,
now when updates need to be made to the Powder Feeders, Ray is able to preserve time because he only has to make the
update in his project once in one location.
Demo
1. Click the Navigation icon at the top of the display of the PanelView Plus 6 terminal.
3. When the Powder Feeder overview display opens click on the numbered circle labeled 4 to open the
detail display for powder feeder number 4.
40 of 134
Note that at the bottom of the display is a group of objects that show the name of the feeder, status, SP value and ACT value for
the feeder. This group of objects is a parameterized global reference object that can be used on more than one display.
4. Click on the middle of the feeder to go back to the powder feeder overview display.
5. When the Powder Feeder overview display opens click on another of the numbered circles to open a different
powder feeder detail display.
41 of 134
Increase Line Productivity - Access Reference Material from Terminal with WebBrowser and PDF Viewer
Business Issue
At MX Toy Company, downtime is excessive because many of the printed manuals are disorganized or difficult to locate.
Therefore, the production manager mandated that all reference materials be stored electronically in a central location and
accessible from each PVP 6 terminal.
Solution
The control engineer, Chris, stored the latest PDF Manuals in a network folder accessible from each PVP 6 terminal. The
manuals became accessible from each terminal because Chris added the new WebBrowser ActiveX Control to the HMI
application. This ActiveX enabled a webpage to launch in which provided an index description of all the reference material. From
this index, any operator can open the appropriate PDF manual for help. As a result, the production manager noticed a decrease
in downtime.
Demo
Web access is also available, but the plant manager wants to prevent web surfing.
42 of 134
3. Click the PanelView Plus 6 Installation Guide link.
This document could be any type of reference material such as alarm or machine instruction.
43 of 134
Chapter 2 – How To
44 of 134
Before You Begin
You will explore the FactoryTalk View Machine Edition application that was used to create the Demo. Start by opening the
application on the PC.
1. From the Start menu, select All Programs > Rockwell Software > FactoryTalk View > FactoryTalk View
Studio or All Programs > FactoryTalk View Studio as shown below.
45 of 134
Managing Machine / Process Parameters with Recipe Manager
This scenario uses the Recipe 2 Enhanced ActiveX to manage 4 different recipe files – Keychain, Small, Medium, and Large toy
cubes. The Recipe 2 Enhanced ActiveX uses CSV files and therefore recipes can be managed offline by using Microsoft Excel.
2. Using the Object Explorer, find MERecipe2Enhanced3 and double click it to bring up its properties.
46 of 134
3. Click on the Connections tab to view the tags associated with the ActiveX control.
47 of 134
The New column objects are actually Numeric Entry Input displays and could be used to change the values
of the recipe files online. However, the demo hi-lighted the offline management of recipe files since the
ActiveX utilizes a CSV file. The New column objects are associated to
::[BlockComms]Program:Rotary_Moulder.PVP_recipe_temp[1] -
::[BlockComms]Program:Rotary_Moulder.PVP_recipe_temp[10] (assigned to Float001 – Float010 of the
control)
A goto display button was used to bring up pop-up display, 42 Recipe Load, that contains the
recipe selector.
48 of 134
5. Using the Object Explorer, find PilotedListSelector1 and double click it to bring up its properties.
When the state changes based on using the arrow keys and the enter key, the state value is passed into
Recipe\RecipeNumber (assigned to RecipeNumber of the control). This number corresponds to the 4 recipe
files. Each state‘s caption uses an embedded string variable associated to Recipe\Recipename1 –
Recipe\Recipename4 (assigned to RecipeName001 – RecipeName004 of the control). These are the names
of the recipe files.
49 of 134
The Recipe Selector display contains a multistate indicator to show the recipe action status.
8. Using the Object Explorer, find MultistateIndicator1 and double click it to bring up its properties.
50 of 134
9. Click the Connections and States tabs to explore the properties.
The ActiveX control passes its state info to the control‘s Status property. Status is assigned to
Recipe\Status_Tag. This value corresponds to the value assigned to the 6 states. Each state displays the
unique caption corresponding to the status of the control.
The final object pertaining to recipes is a Download to Controller button . Pressing this
button updates the corresponding controller tags with the selected recipe values – the values in
::[BlockComms]Program:Rotary_Moulder.PVP_recipe_temp[1] -
::[BlockComms]Program:Rotary_Moulder.PVP_recipe_temp[10] are copied to .
11. Close the 41 Rotary Moulder Recipe and 42 Recipe Load displays. Select No if prompted to save any
changes.
51 of 134
Alert Personnel of Alarm and Monitor Application Remotely with ViewPoint and Email
This scenario uses the E-mail ActiveX to alert Bill of a process anomaly. Bill then uses ViewPoint to remotely connect to the
PanelView Plus 6 terminal and address the process anomaly.
EMAIL
The ―100 SMTP EMAIL‖ display was created to allow configuration of e-mail & text message options. For the purposes of this
section, we will focus on the ActiveX control properties and the Alarm message configuration and not on the specific display
creation.
52 of 134
1. Open the 99 Load ActiveX display by double clicking it.
2. Using the Object Explorer, find ME_EmailSenderControl1 and double click it to bring up its properties.
53 of 134
3. Click the Connections tab to view the tags associated with the ActiveX control.
The control uses an SMTP server to send an e-mail or text. Depending on the specific SMTP server, it may
require a User id, Password, SSL, and SSL port number. Or, it may send the e-mail or text anonymously
and use the standard port number. This demo used ArGoSoft Mail Server as the SMTP server. The server
is installed locally in the VM Ware image and is used when internet access is not available.
SMTPSrvrAddress is 192.168.1.1 since it is loaded locally.
SMTPUserid is the user name of the account and is blank in this case.
SMTPUserPwd is the password for the account and is blank in this case.
SSLEnable is set to a 0 as the mail server is set to not use SMTP authentication.
SMTPPort is set to 25, which is the default SMTP port number.
From_Address is set to a Gmail account address. A Gmail account was created so that e-mails or texts
could also be sent through the Gmail SMTP server if internet access is available.
From_Name is set to ―PanelView Plus SMTP Demo‖.
These parameters were passed to the ActiveX control by using a macro.
4. Close the ME_EmailSender Control Properties window and the 99 Load ActiveX display. Select No if
prompted to save any changes.
54 of 134
5. Open Alarm Setup by double clicking it.
The Alarm Setup was configured to send an alarm message to a tag instead of a printer or a display. The
alarm message is the body of the e-mail or text. Alarm message #2 was used in the demo. It is configured
to send the text ―Pelleter High Speed Warning!‖ to SMTP_EMAIL\Body when SMTP_EMAIL\Alarm_Digital2
goes to a 1.
55 of 134
7. Click the Triggers tab to explore its configuration.
The Alarm Setup contains 5 digital triggers – SMTP_EMAIL\Alarm_Digital2 was the only trigger used in the
demo. The Optional trigger connections – Message and Message Notification were tied to HMI tags.
Message is associated to the ActiveX control‘s Body property. This is the body of the e-mail or text message
and in this case is alarm message #2. The trigger setting connection, Message Notification, is assigned a
digital tag and it goes to a 1 when trigger setting connection, Message, receives a new string value.
Message Notification is used to trigger the E-mail ActiveX control.
Message Notification stays at 1 for the hold time of 750mS and then is reset to 0.
The ActiveX control writes a 1 to its Handshake property once it recognizes the e-mail or text message – the
string contained in Body.
56 of 134
9. Close the Alarm Setup window.
57 of 134
13. Open Macro 2 by double clicking it to explore its configuration.
Macro2 triggers the e-mail to be sent and adds the Subject to the e-mail.
58 of 134
Macro3 resets the E-mail ActiveX Trigger and Handshake.
59 of 134
FactoryTalk ViewPoint Administration
Configuration of FactoryTalk ViewPoint is done through the FactoryTalk ViewPoint Administration tool, launched from
FactoryTalk View Studio. Here, the desired displays are selected and published so that they will be available to any browser
client connecting to your operator interface terminal.
With FactoryTalk ViewPoint ME, the Administration tool runs on the same computer as FactoryTalk View Studio and is installed
using the FactoryTalk ViewPoint ME install available on the ViewPoint CD. The FactoryTalk ViewPoint ME Administration tool is
separate from the ViewPoint ME server that runs on PanelView Plus because the components used to convert and publish
ViewPoint displays are not supported on the PanelView Plus and are too large to store on the terminal.
1. Select ViewPoint Administration from the Application menu to launch the tool.
60 of 134
2. Scroll down to 80 VP Production Data & 81 VP Motor Start.
These displays were selected to be published and the 80 VP Production Data display was selected to be the
initial display shown when connected to the Viewpoint server on the PanelView Plus 6 terminal.
61 of 134
Configuring FactoryTalk ViewPoint ME security
New in ViewPoint 2.0 is the ability to secure individual display access as well as secure the new write capability. You can also
continue to secure the entire application if you like, just as you have been able to do with previous versions of ViewPoint.
1. Select Security Settings on the red navigation bar in the FactoryTalk ViewPoint Administration tool window.
Note that in ViewPoint 2.0 security is role based rather than user based. As a result only User Groups are
shown and not individual users. You can expand on the groups that have a + sign beside them to see the list
of users assigned to each group but you cannot individually select the user.
62 of 134
2. Select the Secured Displays tab.
Enable Application Security is checked. Security was applied to each published display.
Engineers were given write and view privileges. Operators and PlantManagers were given only view
privileges.
63 of 134
4. Select 81 VP Motor Start to explore its security settings.
Engineers were given write and view privileges. Operators and PlantManagers were given only view
privileges.
64 of 134
Creating a runtime file with ViewPoint content
When the runtime file (*.MER) is created, the published ViewPoint displays and security settings will automatically be included in
this file. The transfer of the MER file to the terminal will download the FactoryTalk View ME application as well as the published
displays and security settings.
2. Include ViewPoint content was checked and FactoryTalk ViewPoint 2.10 was selected.
3. Select Cancel.
65 of 134
Remote Display Access with New VNC
This scenario uses the IP Info ActiveX and VNC to allow Laura to remotely access a PanelView Plus 6 terminal. In this scenario,
the IP Info ActiveX provided the terminal‘s IP address without having to shutdown the application.
IP Info ActiveX
The IP Info ActiveX control was used to provide the terminal‘s IP address without needing to shutdown the application.
2. Using the Object Explorer, find MEIPInfoControl1 and double click it to bring up its properties.
66 of 134
3. Click the Connections tab to view the tags associated with the ActiveX control.
4. Close the ME IPInfo Control Properties window and the 99 Load ActiveX display.
67 of 134
VNC – Virtual Network Computing
The PanelView Plus 6 terminal comes with a VNC server pre-loaded. The terminal ships with this server disabled by default.
1. Click on the very bottom of the PanelView Plus 6 screen to bring up the task bar.
3. Double click in the Control Panel of the terminal. The VNC Server was enabled by clicking the VNC
Server button to change it from red to green, indicating it is enabled.
68 of 134
5. Double click located in the Control Panel of the terminal. The VNC Server tab is used to set security
for the VNC server. View Only (no remote control) was unchecked and Enable security was checked. A
password for Password and View-only password were created by typing the password in the text box for each
selection.
If write control is desired, you would connect to the PanelView Plus 6 using the password for Password. If
Enable security & View Only (no remote control) is unchecked, no password is needed when connecting
to the terminal and full control is granted. Checking View Only (no remote control) overrides any write
control privileges.
69 of 134
Archive Production Data with DataStore Plus
This scenario uses the DataStorePlus ActiveX Control and FTP to demonstrate how to remotely access a data log file.
2. Using the Object Explorer, find MEDataStorePlus1 and double click it to bring up its properties.
This ActiveX control allows one to configure which analog tags and string tags to log to a CSV file.
70 of 134
3. Click the General tab to explore the file management settings. The control was setup to start a new log file
every hour and to only maintain 3 log files total.
4. Click the Advanced tab to explore the logging settings. The control was setup to log data every second and to
keep each log file to a maximum size of 1MB.
71 of 134
5. Click the Connections tab to view the tags associated with the ActiveX control.
The FileLocation connection uses a literal string that places the 3 log files into My Documents on the
PanelView Plus 6 terminal and to include Block_log in the name of each file. The Trigger connection uses a
digital HMI tag to enable and disable the data logging.
This same digital HMI tag is also tied to the Datalog enable/disable selector switch
The Float01 – Float06 connections specify to log Zone1 – Zone6 current temperature values.
6. Close the ME DataStore Plus Properties window and the 99 Load ActiveX display.
72 of 134
FTP
There is a FTP server that is pre-loaded and enabled by default on the PanelView Plus 6 terminal.
1. Click on the very bottom of the PanelView Plus 6 screen to bring up the task bar.
3. Double click in the Control Panel of the terminal. The FTP Server is running as indicated by the
green button.
73 of 134
5. Double click in the Control Panel of the terminal. Two user accounts, User1 & User2, were created.
Click X to exit User Account Manager.
7. Select the FTP Server tab. Under the General settings, the Default Directory was set to ―\‖ so that all the
folders on the terminal are seen upon a connection.
74 of 134
8. Scroll down to the Security options.
Use Authentication was checked, the 3 Anonymous options were unchecked, and the User List was
modified to include the user accounts, User1 & User2, that were previously created using the NTLM Account
Manager.
75 of 134
Troubleshoot System Status using Faceplates
This scenario uses a ControlLogix faceplate to determine that a minor program fault had occurred. There are a number of
faceplates available to help customers troubleshoot their systems or to quickly apply basic configuration parameters to various
Rockwell Automation products.
The faceplates are available from the sample code library - http://samplecode.rockwellautomation.com.
1. Browse to the following folder on your lab PC to learn more about the ControlLogix faceplate – its use and
configuration:
C:\Lab Files\NEW Features and Extensions Using FactoryTalk View ME v6.10 and PanelView Plus 6\
Logix_Diag_Toolkit_Instructions_V1_10.pdf
2. Close the pdf viewer and the explorer window when finshed.
76 of 134
Switch Application Language to Operator’s Native Language
This scenario uses Language Switch buttons to quickly switch between different languages.
1. Languages were added into the application by clicking Tools from the menu in FTViewME and then clicking
Languages.
2. The desired languages were added by clicking Add and then selecting the language from the pick list.
This process was performed to add Chinese, French, German, and Italian languages. English is selected as
the default language.
77 of 134
3. Once the languages were added to the application, the strings were exported to an Excel file.
5. The updated Excel file containing the translations was imported back into the application.
78 of 134
8. Open the Banner display under Global Objects by double clicking it.
9. Using the Object Explorer, expand Group5. Find LanguageSwitchButton1 and double click it to explore its
properties.
79 of 134
10. Click the General tab to explore its configuration.
The language associated to the button was selected, in this case English.
The flag image associated to each language was selected, in this case the US flag.
80 of 134
12. Close the Language Switch Button Properties window and the Banner display.
81 of 134
Reuse Common HMI Components with Global Objects
This scenario uses global objects with parameters and the parameter list feature of the goto display button to pass in the name of
the powder feeder to the detail display.
Ray created a global object for the powder feeder details on a global object display called ―Screen Objects‖ that Ray used to hold
a collection of global objects for use in the application. The global object display called ―Screen Objects‖ is a special display
within the Machine Edition application that the operator does not see however the individual global objects it contains can be
used in one or more places within the application. The base object defined here can be modified and any change will replicate to
all the reference objects used in the application.
1. Open the Screen Objects display under Gloabal Objects by double clicking it.
82 of 134
2. Using the Object Explorer, find Group21 and right click on it.
83 of 134
The global object contains a parameter reference that can be replaced by all or part of a tag name or literal
value at runtime. The reference, #1, will be replaced by the number of the feeder such as ―4‖ by using the
parameter list feature of the goto display button.
4. Close the Global Object Parameter Definitions window and the Screen Objects display.
84 of 134
This powder feeder overview display contains 4 goto display buttons, numbered 1-4 such as . They
provide navigation to the ―51 Powder Feeder‖ display which is the powder feeder detail display.
85 of 134
6. Using the Object Explorer, find GotoDisplayButton12 and double click it to explore its properties.
The configuration of the goto display button shows that the button calls the ―51 Powder Feeder‖ display and
passes it the number 4 as the first parameter. In this case we are looking at the goto display button for detail
of powder feeder number 4, anywhere that a #1 is listed on the ―51 Powder Feeder‖ display, a 4 will replace
the #1 at runtime.
86 of 134
8. Close the Goto Display Button Properties window and the 50 Powder Feeders Four display.
NOTE: Each time a powder feeder detail display is opened the global object shown below is being opened
with a different set of parameters allowing for different values to be shown using the same object. Ray
designed a global object once and used global object parameters to shown different values for different
powder feeders rather than creating duplicate objects with different tag values assigned. If Ray needs to edit
this object in the future he can do it by editing the global objects base object in one place and the changes
will replicate to every instance of the global object reference objects used in the application.
Other parts of the application use the global objects defined on the global object display called ―Screen
Objects‖. One of the most powerful features of the global object parameters is that more than one copy of the
global object can be used on the same display and each can have a unique parameter assigned to it that is
not used anywhere else on the display. This can be seen in the ―Main‖ display that contains multiple copies
of the same global objects yet each displays a value for a unique part of the block machine.
87 of 134
Right clicking on any global reference object on the ―Main‖ display and selecting Global Object Parameter
Values will show you what parameters have been defined for that global object.
Below we can see that the global reference object we selected has been defined with a literal value of ―6‖.
When the ―Main‖ display is opened at runtime the #1 for this global object will be replaced by ―6‖. Other
global objects on the display will use different literal or tag values at runtime.
88 of 134
Also note that the drop down menus at the top of the application are global reference objects that were
designed once and used throughout the application. Below is what the navigation button bar looks at as a
global object base object at design time.
89 of 134
Access Reference Material from Terminal with WebBrowser and PDF Viewer
The Web Browser functionality is executed by properly configuring the new WebBrowser ActiveX Control. In the next steps,
we‘ll illustrate how the WebBrowser ActiveX Control was configured.
90 of 134
2. Right click in the middle of the display and select Properties.
3. After selecting properties, you should notice the window below. Click the Connections tab.
Notice that you have now reached the parameter settings for the WebBrowser ActiveX control which needs
to be configured by the application developer.
The URL parameter can be assigned to a tag which contains the website address or html file location. The
value for the ―URL\URL_PB4‖ tag is located in the HMI tag database.
91 of 134
5. Double click on Tags to open the HMI Tag Database and then double click on the URL sub-folder.
Notice this tag value contains the path to the html file which can be stored on local memory or on a network
server. Alternately, this tag value could also be a web address.
This capability allows you to quickly access reference material directly from your terminal without shutting
down your application. Also, the ActiveX can be used to specify a web address that restricts the user to only
that web page.
7. Close the HMI Tag Database window and the 220 HTML_Popup display.
92 of 134
Appendix A
1. Using the Start menu select All Programs>Rockwell Software>FactoryTalk View> FactoryTalk View Studio
item.
After the FactoryTalk View Studio for Machine Edition application opens, you will see a screen similar to the screenshot shown
below:
93 of 134
2. Click the New tab to activate the tab.
94 of 134
If you are unfamiliar with FactoryTalk View Studio for Machine Edition, please review the information in the next few pages.
95 of 134
contains computer-scoped components,
FactoryTalk View Data Server and FactoryTalk Services
Platform objects.
96 of 134
By default, new projects in FactoryTalk View Studio for Machine Edition are configured for a PanelView Plus 700 terminal with a
640x480 resolution. In this lab, you are using a PanelView Plus 1250; this terminal has a larger display and resolution, so you
next need to change the project window size to match for your project.
5. Maximize FactoryTalk View Studio by clicking the maximize button in the upper right-hand corner.
6. Double-click the Project Settings item located in the System container to open its dialog.
7. Select the PVPlus 1250 (800x600) item from the Project window size setting using the dropdown list
.
97 of 134
9. Click the OK button to proceed. There is no need to change any setting on this dialog.
Upon creation of a new project, FactoryTalk View ME 6.X now automatically creates a default display called MAIN which is also
defined as the initial startup display. We will use this display for the following steps in our lab. If you require more displays, you
can always add a new display to the project you are working on. We will see an example of this in the section on Global Objects.
10. To open existing displays, open the Displays container by clicking the expander from the Explorer Pane
window.
Common Configure the object‘s size (Height and Width) and display position. Display top-left
corner is {0,0} coordinate.
Each object provides a set of tabs that vary with the object type. For instance, most objects that display static text (e.g. Text,
Shutdown button) have a Label tab.
1. Select the Text tool , and add a text box to the display.
When you release the mouse button, the Text Properties dialog will immediately open.
98 of 134
2. Click the Text field and enter ‘Hello World! This is my VZ01 application’.
4. Close the display using the File > Close menu item.
When prompted to save ‗MAIN‘ click the YES button.
99 of 134
Now that you have created objects on the Main display, verify that it is configured as the application‘s Startup graphic.
5. To open the Startup dialog, double-click on the Startup item in the System container.
100 of 134
2. Save the runtime project using the suggested name ‘VZ01.mer’ by clicking the Save button .
101 of 134
After creating the runtime MER file, the FactoryTalk View Studio for Machine Edition displays the open application.
1. To download the runtime MER to the PanelView Plus 1250 terminal at your workstation, first select the Tools>
Transfer Utility menu item:
102 of 134
The Transfer Utility will open.
2. Click the Source File Browse button to select the runtime MER file to download.
103 of 134
3. Click on the VZ01.mer file to select the project. The File Name box should update to reflect the selection.
6. Select the 192.168.1.20, PanelView Plus_6 1250, PanelView Plus_6 1250 item by clicking on it once. The
screen that you will see may look slightly different from the example shown below:
104 of 134
When the download process completes a confirmation dialog is shown.
1. Tap on the PanelView Plus screen on your lab station if the screensaver is active.
You will now see the PanelView Plus 6 desktop.
2. Locate the FTView ME Station icon on the desktop and double-tap it to launch FTView ME Station.
105 of 134
4. Select the VZ01.MER file from those available from the terminal‘s Internal Storage.
6. When prompted, press Yes [F7] to overwrite the terminal‘s current communication configuration with the
configuration contained within the VZ01.MER file.
7. Once successfully loaded, press the Run Application [F2] to start executing the runtime file.
106 of 134
After the start-up processing completes, you should see your application‘s startup display:
Congratulations!!
You have successfully created a FactoryTalk View Studio for Machine Edition application, added application content, created a
runtime file, downloaded the runtime file to a terminal, and ran the application on a PanelView Plus terminal.
107 of 134
Applying Communications to an Application
Completing this section requires approximately 30 minutes.
In this section you will learn how to:
Configure RSLinx Enterprise Communications for an application.
Add ‗Live‘ object to a display.
Test an application on the Desktop.
Configuring Communications
2. Right-click on the Communication Setup item and select Open to launch the RSLinx Enterprise
Configuration Wizard.
Communication Configuration
Create a new configuration
Generates an empty communication
configuration scheme for the application.
Copy an existing configuration from a
previously created projects
Reuse a communication configuration
from a different application file.
Copy the configuration that is currently
running on this workstation
Infrequently used; copies the
communication configuration from an
application currently being hosted using
FactoryTalk Machine Edition Station on
the same workstation.
108 of 134
4. Click the Finish button . The Communication Setup dialog opens.
You can resize the dialog by using the size handles, or click the maximize button.
109 of 134
Exploring the Communication Setup Dialog
The Communication Setup dialog has three main areas.
Network Path
Displays the
network topology
Device Shortcuts path to the device
A list of shortcuts associated with the
defined on the selected shortcut.
workstation in RSLinx Also used to create
Enterprise. a new shortcut to
the select network
device.
You will notice that the Network Path dialog area has two tabs, Design (Local), and Runtime (Target). The definitions below should help you
to understand how to use these tabs, and why there provide powerful flexibility when designing an application. These tabs allow you to
develop and debug an application while at your desk, working on the shop floor, or some other location that is not co-located with the control
system.
The tabs can be used as described below
Design (Local) Configure the network and device path(s) for the development environment in
which the application will be designed and debugged. This network topology
and device path(s) may be different than the production environment where the
application will ultimately run.
If the development and production environments are identical, you can copy
the Design (Local) configuration to the Runtime (Target) configuration using
the Copy from Design to Runtime button .
Runtime (Target) Configure the network and device path(s) for the production environment in
which the application will run (e.g. customer facility). The network topology
and path(s) may be completely different than those defined using the Design
(Local) tab.
110 of 134
5. To create a new shortcut, click the Add button in the Device Shortcuts area.
When you click the Add button, a
new shortcut is created. The
shortcut’s name field is open and
ready to be edited.
6. Name the shortcut ‘VZ01’ and then press the [Enter] key on the keyboard.
If you have successfully completed these steps, the Communication Setup dialog will look like this:
8. Click the expander once to open the 192.168.1.1, SoftLogix 5800 EtherNet/IP, SoftLogix 5800
EtherNet/IP item.
9. Click the expander to open the 1789-A17/A, 1789-A17/A Virtual Chassis item.
10. Select 2, 1789-L60/A, Block_Machine by clicking on it once. The dialog should now look like this:
111 of 134
11. Click the Apply button to associate the selected device (e.g. SoftLogix 5800 Controller) with the selected
communication shortcut (e.g. VZ01).
In this lab, the design and production environments are identical. To proceed you have two options:
A. Use the Copy from Design to Runtime button to copy the design environment
topology and device paths to the production environment (e.g. Runtime (Target) tab).
It is estimated this option will require less than 5 minutes to complete.
B. Manually configure the production environment so that you understand how this functionality works. It is estimated
manual configuration will require 5 to 10 minutes to complete.
112 of 134
Option A
a) Click the Copy from Design to Runtime button to copy the communication
configuration from the Design (Local) tab to the Runtime (Target) tab.
d) Go to step 17.
Option B
b) Right-click on EtherNet, Ethernet item to open the context menu, and select Add Device.
c) Click Add Device which opens the Add Device Selection dialog.
113 of 134
f) Select SoftLogix 5800 EtherNet/IP, Major Revision 19.
g) Click the OK button to accept the selection. This action opens the Device Properties dialog.
h) Enter ‗192.168.1.1‘ in the Address field to set the device‘s TCP/IP address.
114 of 134
k) Click the OK button to add the device to the Runtime (Target) configuration.
l) Use the expander to open the 192.168.1.1, SoftLogix5800 EtherNet/IP, SoftLogix 5800 EtherNet/IP device.
m) Right-click the 1789-A17, 1789-A17 Virtual Chassis item and select Add Device.
115 of 134
p) Click the OK button to accept the selection.
r) Click the OK button to add the device to the Runtime (Target) configuration.
t) Click the Yes button to apply the changes to the VZ01 shortcut.
116 of 134
15. Click the Verify button to confirm the Design and Runtime associations.
Confirm both the Design and Runtime devices are assigned for shortcut VZ01.
16. Close the Shortcut Verifier dialog by clicking the Close button .
17. Click the OK button to complete the communication setup and close the Communication Setup dialog.
Be sure to use the OK button! If you close the dialog with the Close button, the communication setup will not be saved to
the application.
117 of 134
Adding ‘Live’ Objects to a Display
Now that a communication path to a controller is configured, you are ready to add objects (buttons, numeric displays, etc.) to the
display that use information from the controller. The lab uses a variety of different buttons, data displays, and images to illustrate
FactoryTalk Machine Edition functionality and application capabilities.
2. Select the Numeric Display tool from the Objects toolbar or select Objects->Numeric and String-
>Numeric Display.
3. Move the mouse cursor onto a free area of the MAIN display frame; click and hold the left mouse button, and
then drag down and to the right to create a Numeric Display object.
118 of 134
4. Position the cursor over the Numeric Display and double-click the mouse to open the Numeric Display
Properties dialog.
6. Change the Height, Width, Top, and Left fields to size and position the Numeric Display exactly.
Height 85
Width 100
Top 175
Left 250
7. Click the Apply button to commit these changes. The button should move and resize on the display
to match these settings.
If you accidently clicked OK button, simply reopen the button‘s property dialog by double-clicking the button.
9. In the Value row, click on the Browse button in the Tag column.
119 of 134
Understanding the Tag Browser
The Tag Browser is used to view and select tags from the application‘s configured data sources. When you configured
RSLinx Enterprise earlier in this lab, you were configuring a data source. Other data sources might be a PLC5 or SLC500
processor, or a device accessed using available KEPware drivers.
Tag Area
Used to select a
specific tag from the
Folder List selected folder
Used to browse a
shortcut’s Controller
and Program tags
and UDTs Tag Filter
Shows only those tags that start with
the user-entered filter. Press [Enter] to
apply a filter to the Tag Area.
120 of 134
The following further defines and highlights the uses and functionality provided in the Tag Browser.
Folder List
HMI Server (e.g. )
Contains tags defined in the HMI Server,
referred to as memory tags. The
FactoryTalk Machine Edition runtime
manages and updates these tags.
System
Contains default HMI tags for system
information, such as, time of day, date,
etc.
<Communication Shortcut> (e.g. VZ01)
Contains tags that exist in the memory of
the device the shortcut represents.
Diagnostic Items
Predefined diagnostic and troubleshooting
tags useful for monitoring communication
and controller status.
Online
Tags contained in a Logix Controller’s
memory; the tags are directly referenced
by the FactoryTalk Machine Edition
runtime.
Tag Area
Name
Column containing the tag’s name. Use
the Tag filter function to quickly find tags
that start with the user-entered filter.
Access Rights
Beginning with V18 firmware, Logix
Controllers implement Access Rights for
tags. This column displays a tag’s
Access Rights property. Tags are either
ReadOnly or ReadWrite.
10. Right-click on the VZ01 item in the Folders list; select the Refresh All Folders item.
121 of 134
11. Double-click the VZ01 folder to expand.
13. In the Tag Area, locate and select the tag Extruder_speed_actual.
Note that the Selected Tag text box reflects your selection.
122 of 134
15. This display should look similar to the following:
16. Save the MAIN display using the File> Save menu item.
17. Close the MAIN display using the File> Close menu item.
123 of 134
Testing an Application on the Desktop
There are two methods available to test an entire application. One is to download the application to a PanelView Plus terminal.
The other is to use the terminal emulation capability that is included with FactoryTalk Studio for Machine Edition. You will be
testing the application on the desktop using the terminal emulation functionality.
When the runtime MER file is built, the system loads the runtime MER in to an emulation mode. The application will appear in
the upper left-hand corner of the computer display.
124 of 134
2. Click on the Shutdown button to end the emulation.
Congratulations!!
You have successfully added ‗live‘ content; configured communications with a controller; created a runtime file; and exercised
the application on your desktop.
125 of 134
Notes
126 of 134
Lab Setup and Configuration Information
Lab Information
NEW Features and Extensions Using FactoryTalk View ME v6.10 and PanelView
Lab Name Plus 6
Demo highlighting some of the features in FTView ME 6.10 & PanelView Plus 6 2.0
Lab Description OS & a how to section describing how the demo was created.
Lab Creator Wil Mattheis
Date Created 09-30-2011
Updates:
Hardware Configuration
Qty Demo Cat.# / Description Communication Location Firmware
2711P-RP9A ser A or later / 6.10 w/ 2.0
1 PanelView Plus 6 logic module ethernet OS
2711P-RDT12C ser C or later
/ PanelView Plus 1250 display
1 module
1 Ethernet crossover cable
127 of 134
Computer/Host Settings
Location Files
Computer Name CORE
IP Address 192.168.1.1
Operating System Windows 7
Photograph of Hardware:
128 of 134
Basic Setup Diagram
Student Station
PanelView Plus 6 1250
High level Tank 02
ON
ON
Level H234
Temp.:
123deg PLANT J45 Start/Stop
Auto
Press.: Manual
12Pa
Level:
Tank ON
ON
P Na Force
P H2O 345
4,5m
02 ON
OFF
P Ca 34
Setpoint
Output
P Li LL L H HH
ON
P Pb
ON
P Cu
React. A
ON Output:
Temp.: 123 gr React. B
M Speed: 56 m/s Tank 01
Tank 02 React. C
Waste
Converter
Tank 03
React. D
Tank 04
React. E
F1 F2 F3 F4 F5 F6
F7 F8 F9 F10 F11 F12
12 102 31
IP Addr: 192.168.1.20
Subnet: 255.255.255.0
CAT5E cross-over
cable
NIC 2
Host computer TCP/IP setting: DHCP
VMWare image TCP/IP setting: IP Addr 192.168.1.1
Subnet 255.255.255.0
NIC 1
Host computer TCP/IP setting: DHCP
CAT5E cable
To Classroom network
DHCP assigned IP
129 of 134
Application/Programming
Location Files
C:\Lab Files\ NEW Features and Extensions
Using FactoryTalk View ME v6.10 and PanelView
Plus 6 Block_Machine.apa
C:\Lab Files\ NEW Features and Extensions
Using FactoryTalk View ME v6.10 and PanelView
Plus 6 Block_Machine.ACD
Batch file to update the PVP6 firmware and to place the
CSV, HTM, and pdf files into My Documents on the terminal
130 of 134
RSLinx Enterprise - Shortcut Configuration
Topic Name Path to Hardware
Through SoftLogix Ethernet IP module in slot 3 to SoftLogix processor in slot
2
BlockComms Ethernet, Ethernet > 3, 192.168.1.1 > Backplane > 2, 1789-L60 v19
Application Versions
Service
Version
Vendor Software Pack
FactoryTalk View Machine Edition Studio 6.10
FactoryTalk Services Platform 2.40
RSLinx Enterprise 5.40
RSLinx Classic 2.58
RSLogix 5000 19
SoftLogix 5800 19
FactoryTalk® ViewPoint 2.10
Microsoft Excel 2010
Silverlight 4.0.60531.0
Tight VNC Client 2.0.3
131 of 134
Required Pre-Lab Configuration
Select Virtual Network Editor from the Edit menu to open the Virtual Network Editor dialog.
132 of 134
Select the Host Virtual Network Mapping tab.
For VMnet0 select the physical ethernet adapter that will be connected to the PanelView Plus terminal.
Click the OK button to commit the changes that have been made.
133 of 134
134 of 134
Publication CE-DM214A-EN-E— October 2011 Copyright© 2011 Rockwell Automation, Inc. All rights reserved.