Anda di halaman 1dari 1

ESP CALCULATIONS :

Project : Ajlan Al Kaabi Building


Dwg Ref. : SD_AJLAN AL KAABI (1)
Fan Tag : S-PR-01

S-PR-01 : 8,245 LPS


S/N Element Flow Frictional Element / Duct Size (mm) Element Air Loss Velocity Friction Corr. Estd. Reference / Applied Value
Rate Length, L Used For Calculation / Duct Velocity, Coefficent Pressure Loss per Factor Total
(L/s) (m) Dia (mm) Width, Height, Area, A V (m/s) ,C (Pa) Meter Pressure
W(mm) H(mm) (m2) (Pa/m) Loss (Pa)
Louver 8,245 - - - - - - - - - - 70.000 Assumed Value
1

Metal Duct 8,245 0.4 - 1,100 500 0.55 14.99 - 133.0 2.30 - 0.920 SMACNA Duct Friction
2

Metal Elbow 8,245 - - 1,100 500 0.55 14.99 0.52 133.0 - - 69.147 SMACNA Elbow F, H/W=0.45, R/W=0.75
3

Metal Duct 8,245 24.5 - 1,100 500 0.55 14.99 - 133.0 2.30 - 56.350 SMACNA Duct Friction
4

Metal Transition 1,795 - - 1,100 500 0.55 3.26 0.04 6.3 - - 0.252 SMACNA Converging Flow B, A1/A= 2.75 , θ=30
5
1100X500>>400X500
Metal Duct 1,795 6.6 - 400 500 0.20 8.98 - 47.7 1.70 - 11.135 SMACNA Duct Friction
6

Grills 916 - - - - - - - - - - 40.000 Assumed Value


7

Pressure Loss Sum 247.80


(ESP)
Safety Allowance (25%) 61.95

Overall Pressure Loss 309.8


(ESP) PA
Overall Pressure Loss 1.2
(ESP) INWG

NOTES:
1 ESP calculations are carried out based on the above mentioned drawings provided by Contractor.
2 Leminar is not responsible for any design and modifications done at site, due to which a change in ESP may result. Leminar cannot be
held responsible for any installation issues or design issues. Calculations are purely carried out based on the provided data and referred drawing.
3 25% safety factor has been considered additional to the actual calculated data for any missing information.