PERHITUNGAN
Gambar A.1. Nilai Vb = 0,929 m3/kg pada T3= 39,35 °C dan T4 = 34°C
x
Air mass flow rate (m) = 0,137 √
Vb
15
= 0,137√0,929
= 0,5505 kg/s
Air volume flow rate (V) = m x Vb
= 0,5505 kg/s x 0,929 m3/kg
= 0,5114 m3/s
Cross sectional area empty tower (A) = 0,15 m x 0,15 m
= 0,0225 m2
V
Kecepatan udara =
A
0,5114
=
0,0225
= 20,0549 m/s
A.1.2. Perhitungan Kecepatan Udara dan Approach to Wet Bulb
Cooling load (Q) = 1 kW
Laju alir = 35 g/s
Orifice differential (x) = 15 mmH2O
Temperatur wet bulb masuk (T2) = 36,3℃
Temperatur air keluar (T6) = 38,3℃
Approach to Wet Bulb (T6-T2) = 38,3℃-36,3℃
= 2℃
x
Air mass flow rate (m) = 0,137 √
Vb
15
= 0,137 √
0,931
= 0,5499 kg/s
Air volume flow rate (V) = m x Vb
= 0,5499 kg/s x 0,931 m3/kg
= 0,5119 m3/s
Cross sectional area empty tower (A) = 0,15 m x 0,15 m
= 0,0225 m2
V
Kecepatan udara =
A
0,5119
=
0,0225
= 22,751 m/s
A.1.3. Perhitungan Kecepatan Udara dan Approach to Wet Bulb
Cooling load (Q) = 1 kW
Laju alir = 45 g/s
Orifice differential (x) = 15 mmH2O
Temperatur wet bulb masuk (T2) = 36,3℃
Temperatur air keluar (T6) = 38,3℃
Approach to Wet Bulb (T6-T2) = 38,3℃-36,3℃
= 2℃
Gambar A.3. Nilai Vb= 0,932 m3/kg pada T3= 40,25 °C dan T4= 34 °C
x
Air mass flow rate (m) = 0,137 √
Vb
15
= 0,137 √
0,932
= 0,5496 kg/s
Air volume flow rate (V) = m x Vb
= 0,5496 kg/s x 0,932 m3/kg
= 0,5122 m3/s
Cross sectional area empty tower (A) = 0,15 m x 0,15 m
= 0,0225 m2
V
Kecepatan udara =
A
0,5122
=
0,0225
= 22,7640 m/s
A.1.4. Perhitungan Kecepatan Udara dan Approach to Wet Bulb
Cooling load (Q) = 1,5 kW
Laju alir = 25 g/s
Orifice differential (x) = 15 mmH2O
Temperatur wet bulb masuk (T2) = 38,3℃
Temperatur air keluar (T6) = 42,1℃
Approach to Wet Bulb (T6-T2) = 42,1℃-38,3℃
= 3,8℃
Gambar A.4. Nilai Vb = 0,935 m3/kg pada T3= 41,75 °C dan T4= 34 °C
x
Air mass flow rate (m) = 0,137 √
Vb
15
= 0,137 √
0,935
= 0,5487 kg/s
Air volume flow rate (V) = m x Vb
= 0,5487 kg/s x 0,935 m3/kg
= 0,5130 m3/s
Cross sectional area empty tower (A) = 0,15 m x 0,15 m
= 0,0225 m2
V
Kecepatan udara =
A
0,5130
=
0,0225
= 22,8000 m/s
Gambar A.5. Nilai Vb= 0,936 m3/kg pada T3= 41,85 °C dan T4= 34 °C
15
= 0,137 √
0,936
= 0,5484 kg/s
Air volume flow rate (V) = m x Vb
= 0,5484 kg/s x 0,936 m3/kg
= 0,5133 m3/s
Cross sectional area empty tower (A) = 0,15 m x 0,15 m
= 0,0225 m2
V
Kecepatan udara =
A
0,5133
=
0,0225
= 22,8130 m/s
x
Air mass flow rate (m) = 0,137 √
Vb
15
= 0,137 √
0,937
= 0,5481 kg/s
Air volume flow rate (V) = m x Vb
= 0,5481 kg/s x 0,937 m3/kg
= 0,5135 m3/s
Cross sectional area empty tower (A) = 0,15 m x 0,15 m
= 0,0225 m2
V
Kecepatan udara =
A
0,5135
=
0,0225
= 22,8200 m/s