ABSTRACT
In this paper computational fluid dynamics (CFD) techniques are used to evaluate the
efficiency of operating room HVAC systems in minimizing the risk of postoperative infection.
Seven different design configurations of operating room HVAC systems have been compared
numerically to assess their agreement with international standards of operating room
ventilation and airflow pattern requirements. The ventilation systems designs considered are
built-in using different air outlet devices, usual, laminar, non-aspirating, and slot diffuser
types. The airflow pattern of each configuration has been analyzed in terms of airflow
vectors, velocities, and turbulent intensity, and pollutant concentration distribution. It was
concluded that all the systems except for the non laminar flow one fulfilled well the
requirements of operating room ventilation, but, that unidirectional airflow with curtain and
zoned exponential unidirectional airflow configurations are the most versatile and energy
efficient.
INTRODUCTION
Operating room is a complex environment that Lidewell2 and Whyte et al. intensively studied
requires ventilation for comfort and to control the transmission of airborne germs in operating
hazardous emissions for patients, and surgical rooms. These investigations resulted in the
staff. Indoor air quality is more critical in health finding that hygienic safety was definitely
care facilities than in most other indoor achieved if less than 10 CFU*/m3 air was
environments due to many dangerous microbial detected in the operating area.
and chemical agents present and due to the Several factors can affect postoperative
increased susceptibility of the patients, infection, including patient factors (e.g.,
especially immunosuppressed persons. susceptibility to infection), surgical field factors
(e.g., the thermal plume from the site), room
The contamination of operating room air with factors (e.g., cleanliness of the operating room),
microbes and viruses is considered as a major and HVAC factors (e.g., air change rate [ACH]
risk factor for surgical site infection (SSI). It and direction of airflow).
was been reported that 80-90% of bacterial Healthcare personnel can also react negatively
contamination found in an open wound comes to cleaning materials, sterilants, disinfectants,
from ambient air1. Operating room air may and anesthetic gases.
contain microbial-laden dust, lint, skin squames, The anesthetic gas and vapors that leak out and
or respiratory droplets. into the surrounding room during medical
2
Table 1: Details of cases considered in study.
Volume Supply
Case
Large array of laminar perforated panels. Two conventional exhaust slot shaped
Complete
System
Ceiling
Position: Position:
Mounted at ceiling immediately above Two 4-grilles groups are mounted on
the operating site. each sidewall (symmetrically distributed
over the wall with 0.25 m from floor,
ceiling, and end walls).
Air-Curtain
supply area, and equipped with two 1 m Located on the facing end-wall at low-
length deflection walls. level, 0.25 m from the floor.
With
Position:
Located at end wall in front of the
operating site, and with 1.3 m from the
foot-end of the operating table
■ Main supply: Arrays of laminar A large floor mounted exhaust was at LAF
supply panels having with 2.96 m*2.36 used having an area of 3m*2.4m. main Panel
m supply area to ventilate the surgery Position:
zone. Located at floor in the center of the
■ side supply: Low induction arrays of room &
supply air terminal device (ATDs)
having a width of 0.12.m for the 0.16 at the
ventilation of the room remainder. side supply
Position:
Mounted at ceiling immediately above
the operating area.
3
Figure 1: Seven cases with different HVAC systems design
configurations.
from it. Return or exhaust air is taken in within the room takes place before this is
multiple locations at the floor level to create carried by the outdoor air to the extract duct.
a “once-through” pattern. This design is This method of ventilation is employed in
widely used with different arrangements; ’clean rooms’, but to be effective the air
entire LAF ceiling, array of LAF diffusers turbulence must be reduced to a minimum
concentrated above surgical zone, and array so that contaminant dispersion is minimized.
of LAF diffusers concentrated above
surgical zone with extending walls or air- NUMERICAL METHOD AND
curtain Peripherally surrounding the LAF. BOUNDARY CONDITIONS
Computational Fluid Dynamics (CFD) was used
3. Horizontal laminar airflow: where the air is to model the air movement in a typical operating
supplied from perforated low induction air room under different HVAC systems
diffusers mounted at one wall directed configurations.
toward the operating table. CFD modeling was conducted to study airflow
patterns, in order to evaluate the effectiveness of
4. Piston ventilation airflow: the proposed ventilation systems designs.
a unidirectional flow of air in which outdoor A commercial CFD program was used in this
air propels the contaminated room air ahead isothermal numerical analysis.
of it like a front. The room air is By discretizing the room volume into an
continuously ’swept’ by outdoor air and unstructured grid of finite volumes or cells
little spread of contamination generated (Table-3), where a set of partial differential
4
governing equations for mass and momentum equations. Typically, it is assumed that all mass
can be numerically solved. Mesh refinement and flux across any solid wall is zero and the no-slip
adaptation were used in order to reach a grid condition is applied on the solid walls. The wall
independent solution. function is implemented near the walls in order
to avoid using too many grid points in the
Governing equations It is assumed that the air viscous sub-layer. The mass flow rate of air
is incompressible, homogeneous, and isotropic. supply is adjustable. Before entering the
Furthermore, the three- dimensional airflow in domain, the air flows through a pre-filter to
the working area is steady and maintained at leach larger particles and then flows through a
room temperature. As a result, the physical HEPA filter. Therefore, the inlet air is regarded
problem can be represented by the laws of as a unidirectional uniform flow in the analysis.
conservation of mass, momentum (u, v, w), as The implemented boundary conditions are listed
well as the transport laws of mass diffusion to in the proceeding table (Table-3).
compute for contaminant distribution. Besides,
the k-ε model is also used to describe the flow Table 3: Numerical Conditions
turbulence with the transport equations of
Mesh CASE 1 53536
turbulence kinetic energy (k) and its dissipation
CASE 2 48484
rate (e) involved in the computations. All these CASE 3 56577 Unstructured
equations can be expressed in a general form: CASE 4 53636 tetrahedral
CASE 5 59373 cells
∂( ρφ ) ∂
(ρφ ui ) = ∂ Γφ ∂φ + Sφ
CASE 6 53244
+ (1) CASE 7 54764
∂t ∂xi ∂xi ∂xi Turbulence Standard k- ε model.
Model
Inflow Boundary Uin; shown in table 1,
Where φ is the dependent variable, Table-2 Condition k= 3/2(Uin*Ti)2,
gives the expressions for the source terms Sφ for ε = Cμ 3/4 kin3/2 / l0 ,
each variable that is likely to be needed in l0 =Length scale of supply opening
=0.1 Lin ,
solving ventilation problems. Lin = The characteristic length of
the diffuser.
The numerical algorithm made use of the Ti = Turbulence intensity.
= 0% for perforated LAF ATDs
"SIMPLE Solving Algorithm" [Semi Implicit = 4-10% for other non-laminar
Method for Pressure Linked Equation], for airflow diffuser.
pressure - velocity coupling. Outflow Uout, kout, ε out free slip wall.
boundary
Condition
Table 2: Source Terms in the Transport Equations for Wall Treatment Generalized log law.
Turbulent Flow Uniformly and continuously generated
Contaminant
Equation φ Γφ Sφ throughout the space, simulated with
Continuity 1 0 0 species full transport equation.
Momentum ui μe - ∇P+∇· (μe ∇· U) + ρg
Kinetic Energy k Γk Pk - ρε
Dissipation rate ε Γε C1ε ε Pk / k - C2ε ρε2/k
Concentration C Γc ρCs
RESULTS AND DISCUSSION
The efficiency of air conditioning in the
Where σk =1.0 , σε =1.3, σC =1.0, Cμ =0.09, C1ε =1.44, C2ε=1.92
Cµ ρ k 2
operating room is proved by three ruling
µt = , magnitudes: turbulent energy k, velocity pattern
ε
∂u ∂u ∂u
V of the flow, and the concentration of
Pk = µt i + j i anesthetic gas (N2O) at breathing height which
∂x j ∂xi ∂x j
is 1.5 m above the floor level.
The standard deviation of flow velocity is given
Boundary conditions: The conditions on the ½
surfaces bounding the domain must be clearly by v’ = (2k/3) enabling the calculation of the
defined in order to solve the system of transport degree of turbulence Tu= v’/v. The degree of
5
turbulence may serve as a guiding magnitude That makes it more risky for infection, and thus
for engineers and technicians who bear on-site omitted from use in operating rooms.
responsibilities. The velocity of air describes the
effect of particles re-suspension and thus the Case 2:
risks of germ induction into the inlet air. A smoothly laminated air was depicted by the
Position and size of inlet affect the flow in the velocity profile (figure 3). The eddies occurred
operating area as in all the cases of study the at edges of the table where air is sticking has
inlet air is directed to the operating suite, low intensity compared with case one. The one
conversely the exhaust grilles position affects deficiency of this configuration is the air
only the out less clean zone of the room and the change, which amounts 166 ACH with running
contaminant distribution. Flow velocities are and installing costs.
significantly below 0.5 m/s in the working area
in all cases, thus avoiding draught. Case 3:
In the profile of velocity contour (figure 4), the
The inlet jet is ranked stable if a moderate laminar jet coalesces a bit as it goes away from
variation of influencing magnitudes does not the diffuser resulting in a smaller area covered
cause significant alterations of the laminar flow. with laminar flow at the operating table. This
Flow exhibits typical features despite the may result in shortage in safety from infection.
varying positions of obstacles. The vertical This can be solved by adding either deflecting
component of flow Vy at varying distances walls or by increasing the area of LAF diffusers
above the table where turbulent flow occurs, as occurred in case 4.
however for laminar flow cases these
turbulences has too low kinetic energy Case 4:
(k<<0.002 m2/s2). 4
The zoned LAF system (figure 5) showed
In order to make the results from contaminant within-standards velocity besides a low
concentration distribution more representative turbulence kinetic energy with only 23.12 ACH,
for zones of anesthetic gases exposure risk, the that make it also an energy efficient solution for
N2O concentration was normalized by the operating room ventilation.
standard threshold limit value (TLV) of the
contaminant. Case 5:
The flow seems low a bit at operating table and
Case 1: the whole curtained zone (figure 6). It may be
The first design configuration evaluates the for deficient simulation of LAF diffuser. The
performance of ventilation system using mixing curtain acts as a barrier preventing contaminants
flow. Figure 2 shows the CFD results with the from the outer zone to come through.
species transport and airflow pattern. The results
are available for all three dimensions, but the The demerit that was in this configuration is
figures illustrate the results only in two sections, dead zones outside the curtain; this has been
a vertical section at the center plane of the overcome by adjusting two arrays of four
operating room and a horizontal section at the conventional grilles well distributed at each
breathing level to assess the exposure risk of sidewall. It is thought to be a great innovation in
surgical staff to the anesthetic gas (N2O). operating room ventilation.
The contaminant is hasted with the jet from the
inlet diffuser causing it to spread in front of it, Case 6:
reaching a maximum value of 282.5 ppm at the The horizontal LAF showed somewhat high
breathing level. Besides, the velocity flow velocities (figure 7) at the surgical zone. The
pattern (figure 2) and profile of kinetic energy use of deflecting walls takes a room of the
shows high turbulence intensity at the operating operating theatre making it more confined. And,
table and the working space. it is thought that it will deflect greatly from that
showed pattern in non-isothermal studies.
6
Besides if the surgical staff and medical devices 3- Friberg B, Friberg S, Burman LG.
are taken in consideration, they will act as “Inconsistent correlation between aerobic
blocking barriers in its way, therefore it is not bacterial surface and air counts in operating
recommended to be used. rooms with ultra clean laminar air flows:
proposal of a new bacteriological standard
Case 7: for surface contamination.” J Hosp Infect
The piston ventilation HVAC system 1999; 42: 287-293
configuration that is real laminar airflow 4- ASHRAE2003-application Handbook.
showed excellent agreement with standards at 5- Friberg B. “Ultraclean laminar airflow Ors”.
the surgical zone. The velocities above the AORN J 1998; 67:841-51.
operating ranges from 0.11 to 0.17 as stated in 6- F. Memerzadah, A. Manning, “Reducing
recommendations. The turbulence kinetic risks of surgery”, ASHRAE Journal, Feb.
energy is of 10-4 order of magnitude (<< 0.002), 2003.
that shows a real laminar flow. 7- F. Memerzadah, A. Manning, “Comparison
Besides, at the breathing level (1.5 m above of operating room ventilation systems in
floor) the concentration of the anesthetic gas is protection of the surgical site”, ASHRAE
maximum 8 ppm that is so far safe from the Transactions, 2002.
hygienic limit (50 ppm). 8- Lemaire, A.D., Ham, P.J. and Luscuere,
The only defect in this configuration is the P.G. 1995. Evaluation of computer flow
highly expensive initial and running costs. modelling in operating theatres, Proc.13th
Int. Symp. on Contaminant Control, The
Hague, The Netherlands.
CONCLUSION AND MAJOR FINDINGS 9- C. Hartung, J. Kugler, “Perturbations
The CFD modeling provided a great deal of Affecting the Performance of Laminar Flow
information the designers would not otherwise in Operating Theatres”, 1998.
have had. It was instrumental in comparing 10- Anesthetic Gas Pollution in Operating
between various operating room configurations Theatres: New Prospects in HVAC System
in a cheap easy manner. Design - Mazzacane S, Italy (UoF) 11-
From the seven configurations, the forth and 11- Y. Liu, A. Moser, “Airborne particle
fifth cases are recommended, namely the zoned concentration control for an operating room
LAF system and the vertical LAF with curtain 12- CDC-Guidelines for Environmental
as they divided the room into zone ultra-clean, Infection Control in Health-Care Facilities,
clean, and less clean zones, fulfilling the Centers for Disease Control and Prevention
recommended direction of airflow which is (CDC), U.S. Department of Health and
almost important and should be from clean to Human Services, 2003.
less clean area preventing back flow into cleaner 13- R Meierhans, "New hospital-hygiene
one. guidelines – new technical standards for
HVAC equipment" ,Proceedings of Indoor
REFERENCES Air 2002.
1- Chen, Q., Jiang, Z and Moser, A. Control of 14- H. Grotjans, and F. Menter, “Wall functions
airborn particle concentration and draught for general application CFD codes”,
risk in an operating room. Indoor air 91, ECCOMAS 98 Proceedings of the 4th
1991. European Computational Fluid Dynamics
2- Lidwell, OM, Lowbury, EFL, Whyte, W, Conference, pp1112-1117.
Blowers, R, Stanley, SJ and Lowe, D, 15- U. moscato, T. esposito, G. vanini, "nitrous
“Effects of ultra-clean air in operating room oxide pollution: a geo-statistical method to
on deep sepsis after total hip or knee assess spatial distribution of anesthetic gases
replacement: a randomized study”, Med. J., and hospital staff exposure", Proceedings of
285, pp 10-14, 1982. Healthy Buildings 2000, Vol. 1.
7
16- Awbi, H.B., “Ventilation of Buildings,” E & /exponential LAF-screen. A promising new
F Spoon Press, Second Edition (1995). concept in ultra-clean air technology for
17- K. A. Henderson and I. P. Matthews, additional operating room ventilation. J
“Biological monitoring of midwives’ Hosp Infect. 2002; 50:286-292. doi:
exposure to N2O using the Bio-VOC breath 10.1053/jhin.2001.1164.
sampler”, Journal of Exposure Analysis and 20- Friberg B., “Ventilation in the Operating
Environmental Epidemiology, 2002. Theatre. From asepsis in the Operating
18- “Air quality guidelines for Europe”, Theatre”, Mölnlycke Health Care AB,
Copenhagen, WHO Regional Office for Göteborg, Sweden, 1999.
Europe, 2000 (WHO Regional Publications, 21- Friberg B. “Ultraclean Laminar Airflow
European Series, No. 91). Ors”, AORN Journal, 1998
19- Friberg B, Lindgren M, Karlsson C,
Bergström A, Friberg S. "Mobile zoned
8
Figure 2: Computed air and contaminant distribution for case 1:
(a) Air velocity in middle section(z=3.05), (b) Turbulence kinetic energy in middle section(z=3.05),
(c) Contaminant distribution at breathing level, 1.5m from the floor
9
Figure 3: Computed air and contaminant distribution for case 2:
(a) Air velocity in middle section (z=3.05), (b) Turbulence kinetic energy in middle section(z=3.05),
(c) contaminant distribution at breathing level , 1.5m from the floor
10
Figure 4: Computed air and contaminant distribution for case 3:
(a) Air velocity in middle section(z=3.05), (b) Turbulence kinetic energy in middle section(z=3.05),
(c) contaminant distribution at breathing level , 1.5m from the floor
.
11
Figure 5: Computed air and contaminant distribution for case 4:
(a) Air velocity in middle section(z=3.05), (b) Turbulence kinetic energy in middle section(z=3.05),
(c) Contaminant distribution at breathing level, 1.5m from the floor
.
12
Figure 6: Computed air and contaminant distribution for case 5:
(a) Air velocity in middle section(z=3.05), (b) Turbulence kinetic energy in middle section(z=3.05),
(c) Contaminant distribution at breathing level, 1.5m from the floor
.
13
Figure 7: Computed air and contaminant distribution for case 6:
(a) Air velocity in middle section(z=3.05), (b) Turbulence kinetic energy in middle section, (z=3.05)
(c) contaminant distribution at breathing level , 1.5m from the floor
14
Figure 8: Computed air and contaminant distribution for case 7:
(a) Air velocity in middle section(z=3.05), (b) Turbulence kinetic energy in middle section(z=3.05),
(c) Contaminant distribution at breathing level, 1.5m from the floor
.
15
16