1 Protection Basics
2 Fault Behavior
3 Switchgear, CT & VT
4 Discussion
Protection Basics
Setiap perusahaan listrik harus berupaya meningkatkan
keandalan secara terus menerus.
Tingkat keandalan di representasikan antara lain,
indikator sering terjadinya pemadaman .
Indikasi : Frekuensi dan Lama Gangguan
-Transient voltage:
- Voltage Sag
- Voltage Swell
- apa contoh kejadiannya?
Gangguan pada Sistem Kelistrikan
Daerah Pengamanan
A B C
2 1 2 1 2 1 D E
1 2 3 4 5 7 6 8 9 10 11
(1) Overall Diifferential Relay (5) Distance Relay Zone II di A1 (8) Over Current Relay Trafo sisi 150
Pengaman Utama Gen-Trafo Pengaman Utama Bus B kV Pengaman Cadanngan Lokal
Pengaman Cadangan Jauh Trafo Pengaman Cadangan Jauh Bus C
sebagisn Trafo di B
(2) Over Current Relay Pengaman (9) Over Current Relay Trafo sisi 20kV
Cadangan lokal Gen-Trafo Penga- Pengaman Utama Bus C
man Cadangan jauh Bus A (6) Distance Relay Zone Pengaman Cadangan Jauh saluran
III, Pengaman Cadangan Jauh Trafo CD
(3) Pengaman Bus-Pengaman di B sampai (10 ) Over Current Relay di C1
Utama Bus A ke Bus C Pengaman Utama saluran CD
(7) Differential Relay Pengaman Cadangan Jauh saluran
(4) Distance Relay & PLC di A1 – - Pengaman Utama Trafo DE
Pengaman Utama Saluran AB (11) Over Current Relay di D
Pengaman Utama saluran DE
Pengaman Cadangan Jauh seksi
berikut
SISTEM PENGAMAN
KAWASAN PENGAMANAN
Kawasan Pengaman Utama
Kawasan Pengaman Kawasan Pengaman Kawasan Pengaman
(O.C) Saluran 20 kV dan
Utama Busbar 150 kV Utama Saluran A-B Busbar 150 kV
Cadangan seksi selanjutnya
B
A
20 D E
150 kV kV
PERALATAN PENGAMAN
Overcurrent
Uses current to determine magnitude of fault
Simple
May employ definite time or inverse time curves
May be slow
Selectivity at the cost of speed (coordination stacks)
Inexpensive
May use various polarizing voltages or ground current for
directionality
Communication aided schemes make more selective
Types of Protection
Differential
current in = current out
Simple
Very fast
Very defined clearing area
Expensive
Practical distance limitations
Line differential systems overcome this using digital
communications
Differential
1 pu
IP IP
CT-X CT-Y
IS IS
Note CT polarity
Relay
dots
IR-X IR-Y
This is a through-
current
+1
1 + (-1) = 0 representation
Current, pu
0 Perfect
waveforms, no
-1 saturation
DIFF CURRENT
Differential
2 pu 2 pu
IP
Fault
CT-X CT-Y IP
X
IS IS
Note CT polarity
IR-X
Relay
IR-Y
dots
This is an internal
fault
+2 representation
2 + (+2) = 4
Perfect
Current, pu
0
waveforms, no
-2 saturation
DIFF CURRENT
Types of Protection
Voltage
Uses voltage to infer fault or abnormal condition
May employ definite time or inverse time curves
May also be used for undervoltage load shedding
Simple
May be slow
Selectivity at the cost of speed (coordination stacks)
Inexpensive
Types of Protection
Frequency
Uses frequency of voltage to detect power
balance condition
May employ definite time or inverse time curves
Used for load shedding & machinery
under/overspeed protection
Simple
May be slow
Selectivity at the cost of speed can be expensive
Types of Protection
Power
Uses voltage and current to determine power
flow magnitude and direction
Typically definite time
Complex
May be slow
Accuracy important for many applications
Can be expensive
Types of Protection
Distance (Impedance)
Uses voltage and current to determine impedance of fault
Set on impedance [R-X] plane
Uses definite time
Impedance related to distance from relay
Complicated
Fast
Somewhat defined clearing area with reasonable accuracy
Expensive
Communication aided schemes make more selective
Fault Behavior
Fault Types (Shunt)
AC & DC Current Components
of Fault Current
Variation of current with time
during a fault
Contribution to Faults
Short Circuit Current (3)
Short Circuit Study
ANSI Method
Di dalam standar ANSI, Sistem dimodelkan dengan
masing-masing impedansi internal mesin.
Sistem diasumsikan dalam kondisi seimbang
(balance system).
Kapasitansi saluran dan beban-beban statis
diabaikan
Sistem dikondisikan dalam 3 nilai impedansi yang
berbeda untuk perhitungan arus hubung singkat
momentary, Interrupting, dan Steady State.
Short Circuit Current
Momentary
Interrupting
Short Circuit Current (2)
ANSI Definition of Terms
½ Cycle Network
1½ - 4 Cycle Network
30 Cycle Network
→Digunakan untuk menentukan setting peralatan pengaman.
Short Circuit Study
IEC Method
Dalam metode IEC, arus hubung singkat
dikelompokkan berdasarkan magnitudenya
(maksimum / minimum) dan juga berdasarkan jarak
dari sumber (far / near).
Arus hubung singkat dihitung berdasarkan impedansi
substransient mesin dan konstanta waktu.
Standar IEC mulai banyak diimplementasikan karena
praktis dan lebih mudah dikondisikan sesuai dengan
sistem kelistrikan industri.
IEC Short Circuit Current
Purpose of the
IEC Short Circuit Values
Design Criterion Physical Effect Relevant short-circuit current
Power to switchgear is
connected via Cables or Bus Duct
The main internal bus carries
power between elements within
the switchgear
Power within the switchgear
moves from compartment to
compartment on horizontal bus,
and within compartments on
vertical bus
Instrument Transformers (CTs &
PTs) are used to step down
current and voltage from the
primary circuits or use in lower-
energy monitoring and control
circuitry.
Air Magnetic Breakers
SF6 and Vacuum Breakers
A Study of a Fault…….
Fault Interruption and Arcing
49
GE Consumer & Industrial
Multilin
Current Transformers
• Current transformers are used to step primary system currents to
values usable by relays, meters, SCADA, transducers, etc.
• CT ratios are expressed as primary to secondary; 2000:5, 1200:5,
600:5, 300:5
• A 2000:5 CT has a “CTR” of 400
Standard IEEE CT Relay Accuracy
100 V = 20 * 5 * (1ohm)
200 V = 20 * 5 * (2 ohms)
400 V = 20 * 5 * (4 ohms)
800 V = 20 * 5 * (8 ohms)
Standard IEEE CT Burdens (5 Amp)
(Per IEEE Std. C57.13-1993)
Application Burden Impedance VA @ Power
Designation (Ohms) 5 amps Factor
Relaying B1 1 25 0.5
B2 2 50 0.5
B4 4 100 0.5
B8 8 200 0.5
Current into the Dot, Out of the Dot
Current out of the dot, in to the dot
Forward Power
IP
IS
Relay
or Meter IR
Forward Power
IP
IS
Relay
or Meter IR
Voltage Transformers
• Voltage (potential) transformers are used to isolate and step down
and accurately reproduce the scaled voltage for the protective
device or relay
• VT ratios are typically expressed as primary to secondary;
14400:120, 7200:120
• A 4160:120 VT has a “VTR” of 34.66
VP
VS
Relay
Eko Wahyu Susilo
Facilities & Project Engineering – Technical Dept.
Agenda
1 Grounding System
4 Discussion
Grounding System
Equipment Grounding
Prevents shock exposure of personnel
Provides current carrying capability for the ground-
fault current
Grounding includes design and construction of
substation ground mat and CT and VT safety
grounding
System Grounding
Limits overvoltages
Limits difference in electric potential through local area
conducting objects
Several methods
Ungrounded
Reactance Coil Grounded
High Z Grounded
Low Z Grounded
Solidly Grounded
System Grounding
1. Ungrounded: There is no intentional
ground applied to the system-however
it’s grounded through natural
capacitance. Found in 2.4-15kV
systems.
Keuntungan :
Sangat baik mengurangi overvoltage
Tidak membutuhkan pengaman khusus untuk ground fault, ground fault bisa
sekaligus diamankan oleh pengaman gangguan antar fasa (Ekonomis)
Kerugian :
Service continuity rendah
Arus ground fault sangat besar dan berbahaya (sama dengan short circuit 3 fasa)
Application :
Small electrical distribution system
LV distribution system
81
Low Resistance grounding
Pada sistem Grounding ini titik netral diketanahkan dengan
menggunakan hambatan yang relatif kecil, sehingga ketika
terjadi ground fault, maka arus urutan nol yang muncul
dibatasi pada nilai hambatan tersebut.
Keuntungan :
Arus ground fault dibatasi (damage dibatasi)
Sistem proteksi lebih mudah
Overvoltage tidak terlalu tinggi
Kerugian :
Relatif lebih mahal
Memprioritaskan equipment safety daripada
Service continuity
Application :
Powerplant Area
Public and industrial MV distribution systems (currents of several hundred
amperes).
82
High Resistance grounding
Pada sistem Grounding ini titik netral diketanahkan dengan
menggunakan hambatan yang cukup besar, sehingga ketika
terjadi ground fault, maka arus urutan nol yang muncul
dibatasi pada nilai hambatan tersebut.
Keuntungan :
Arus ground fault sangat kecil (less-no damage)
Service Continuity
Sistem proteksi lebih mudah
Overvoltage relatif lebih tinggi
Kerugian :
Lebih mahal
Application :
Public and industrial MV distribution systems.
83
Ungrounded (open / floating)
Pada sistem Grounding ini titik netral tidak diketanahkan
sehingga ketika terjadi ground fault, maka arus urutan nol yang
muncul sangat kecil yaitu hanya sebesar nilai arus bocor (phase
to earth capacitance) dari feeder.
Keuntungan :
Arus ground fault hampir tidak ada
(no damage)
Service Continuity
Kerugian :
Sistem proteksi lebih rumit
Paling mahal
Overvoltage tinggi
(menambah level insulasi)
Application :
industrial power systems (ex: 15 kV) that require service continuity
84
System Grounding Influences
Ground Fault Detection Methods
Source
Low/No Z
Med/High Z
50 50 50
51 51 51
System Modeling
Resetting
Settings are good and No
coordinated properly?
Yes
FINISH
Contoh koordinasi yang belum tepat (1)
Contoh koordinasi yang belum tepat (1)
Trip ketika motor
beroperasi dengan
pembebanan penuh
Koordinasi masih
belum tepat
Hasil Resetting dengan koordinasi lebih baik (1)
Contoh koordinasi yang belum tepat (2)
Contoh koordinasi yang belum tepat (2)
Koordinasi masih
belum tepat
Grading time
masih terlalu
sempit
Hasil Resetting dengan koordinasi lebih baik (2)
Contoh koordinasi yang belum tepat (3)
Contoh koordinasi yang belum tepat (3)
Akan trip ketika Reaksi terlalu
generator lama
mengalirkan arus
maksimum
1 Protection Philosophy
3 Practice
4 Discussion
Protection Philosophy
Protection Phyllosophy
Protective Devices
Protection Relay
HV/MV CB
Fuses
LVCB
Time-based discrimination
Current-based discrimination
Differential protection discrimination
104
Protection Relay
105
ANSI/IEEE Device (Relay) Number
106
Protection Relay General Characteristic
108
Inverse Time Characteristic
CURRENT
109
IDMT Characteristic
110
IEEE Inverse Curves (North American)
111
How HV/MV CB’s Clear Fault Current
112
How Fuses Clear Fault Current
113
How LVCB’s Clear Fault Current
114
Overcurrent Relay Coordination
Time--based Discrimination
Time
Diskriminasi waktu adalah menentukan
setting rele dengan memeberikan
selisih waktu antara rele downstream
dengan upstream
Semakin dekat rele dengan sumber,
maka setting waktunya harus semakin
lama.
Merupakan koordinasi proteksi yang
paling simple
Sebagai contoh : jika rele D gagal
mengamankan gangguan, maka rele C
sebagai backup akan aktif setelah ∆t
kemudian.
116
Time--based Discrimination (2)
Time
I sA > I sB > I sC
TA > TB > TC
117
Current--based Discrimination
Current
118
Current--based Discrimination (2)
Current
1 Generator Protection
2 Transformer Protection
3 Motor Protection
Since the fault of the generator from the system will interrupt
the operation of electric power systems.
Power Generation System Parts
Brushless Exciter Generator
Brushless Exciter Generator
Generator Operation Limit
Generator Protection at Badak LNG Plant
100 A NGR
Neutral Grounding of generator
146
Current Unbalance – Negative Phase Sequence (46)
149
Thermal Overload (49)
Thermal protection for the generator stator core and windings may be
provided for the following contingencies:
• Generator overload
• Failure of cooling systems
• Localized hot spots caused by core lamination insulation failures or by
localized or rapidly developing winding failures
150
Transformer Protection
Transformer Failure :
Winding failures due to short circuit (turn-turn
faults, phase-phase faults, phase ground, open
winding)
Core faults (core insulation failure, shorted
laminations)
Terminal failures (open leads, loose
connection, short circuits)
On-load tap changer failures (mechanical,
electrical, short circuit, overheating)
Abnormal operating conditions (overfluxing,
overloading, overvoltage)
External faults
152
Two Winding transformer Protection Three Winding transformer Protection
153
154
Motor Protection
156
157
159
START INHIBIT ILLUSTRATIONS
163
164
1. Thermal Overload (49)
Process Caused (Excessive load), high ambient conditions (hot,
blocked ventilation), power supply issues (voltage/current
unbalance, harmonics)
165
2. Stator RTD (49 RTD)
Maintain and monitor the temperature of winding motor
166
Motor Starting & Short Circuit Protection
Phase Differential (87M)
This protection function is mostly used to protect induction and
synchronous motors against phase-to-phase faults. This function
requires two sets of CT’s, one at beginning of the motor feeder,
and the other at the star point.
Load Shedding [BONUS]
Load Shedding System
Contact:
ekowahyu@badaklng.co.id
eko.xciel@gmail.com