Section 28 Schedule of Prices

The prices are to be quoted in the below mentioned form and shall include the supply and
installation at site of all the equipments, ancillary materials as specified and all such items
whatsoever which may be required to fulfil the intent and purpose as laid down in the
specification and/or the drawings.

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)

Part-A : High Side Works ( Part-I)

1 Air Cooled Chilling Units (Scroll Type)


1.1 Supply, installation, testing &
commissioning of Scroll type Air cooled
chilling units complete with multiple
compressor, motor 3 phase, 50 Hz, 415
volts, chiller, drive sets, mounting frame,
control panel with automatic controls, inter
connecting refrigerant piping complete as
per specifications and drawings including
antivibration arrangement etc.as required.
1.1.1 Air Entering temperature : 35 °C
1.1.2 Chilled water 'in' : 12.2 °C
1.1.3 Chilled water 'Out' : 6.7 °C
1.1.4 Chiller Fouling Factor (FPS) : 0.0005
1.1.5 Refrigerant : R-407

1.1.6 Cooling Capacity : 24 TR Nos. 1 408000 408000


1.1.7 Cooling Capacity : 36 TR Nos. 1 612000 612000

1.2.1 100 mm thick cooling pads complete with


water distribution headers, water collection
tray of 20 Guage stainless steel, 20 Guage
G.I Sheet side & top and bottom cover 1
no. water pump and 500 litre PVC water
tank with necessary connecting pipe
having complete with Pad Area of 14 Sq.m.
for 24 TR Chiller Sets 1 48000 48000

1.2.2 ---do--- for 36 TR Chiller Sets 1 72000 72000

2 Chilled Water Pumps

Monobloc chilled water circulating pump


sets complete with coupling, T.E.F.C.
motor, Bronze/SS Impeller, base plate,
Priming Funnel, air vent, air cock etc. as
per specifications and drawings.

2.1 Chilled water 550 LPM at 24 m head


(1 standby). Nos. 2 40000 80000

3 Hot Water Generator Pumps

Monobloc Hot water circulating pump sets


complete with coupling, T.E.F.C. motor,
Bronze Impeller, base plate, Priming
Funnel, air vent, air cock etc. as per
specifications and drawings.
3.1 3 HP (1W + 1S) Nos. 2 24000 48000

Sub-Total 'A' Rs. : 1268000


BOQ - 2

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)
Part 'B' : Low Side Works (Part-I)

1
Air Handling Units For Operation Theater.

1.1 Providing and fixing floor mounted type


double skin unitary Air Handling Units with
inner skin made up of Aluminium sheet &
complete with 6 row cooling coil, 50 mm
thick PUF injected panel, imported
centrifugal fan at 125 MMwg static, fan
motor TEFC type, drive set, coil section
with cooling coils, mixing chamber, flat
filter section with Pre-filters, High
efficiency filter, HEPA filters 150 mm thick
with 99.97% efficiency down to 0.3 micron
particle size, inclined manometer across
HEPA filters, belt gurd, fire resisting
flexible canvass connection etc. complete
as per specifications.
1.1.1 2720 CUBM/HR with 6 Rows Coil Cooling,
2.2 KW motor, 125 mm of wg static Nos. 3 120000 360000
pressure.
2 Unitary/horizontal Type Air Handling
Units
Ceiling suspended
2.1 Supply, Installation, Testing and
Commissioning of Double skin,
Unitary/horizontal Air Handling Units
complete with fan section with fan and
motor, coil section with cooling coils, Flat
filter section with standard filters and
microvee filters, damper, drive set, belt
guard, flexible connections and controls
complete
2.1.1 3000 cfm with 4 Rows Coil Cooling, 40
mm of wg static pressure. Nos. 3 80000 240000

2.1.2 4000 cfm with 4 Rows Coil Cooling, 40


mm of wg static pressurer. Nos. 1 105000 105000

2.1.3 5000 cfm with 4 Rows Coil Cooling , 40


mm of wg static pressure. Nos. 1 122000 122000

6 Chilled Water Piping

6.1 Mild steel Heavy Class pipes with all


necessary fittings i.e. bends, tees,
reducers, flanges, supports and 50 mm
thick EPS insulation etc.

6.1.1 80 MM RM 36 1950 70200


6.1.2 65 MM RM 25 1750 43750
6.1.3 50 MM RM 40 1350 54000
6.1.4 40 MM RM 35 1150 40250
6.1.5 32 MM RM 15 950 14250
6.1.6 25 MM RM 20 750 15000
6.1.7 20 MM RM 20 650 13000

6.2 Butterfly Valves

6.2.1 80 MM Nos. 12 4500 54000


6.2.3 40 MM Nos. 6 3500 21000
6.2.3 32 MM Nos. 18 3200 57600

6.3 Gate Valve for Drain


Providing and fixing in position the
following Gate Valves duly insulated as
per specifications:

6.3.1 25 MM Nos. 1 3000 3000


6.3.2 20 MM Nos. 1 2500 2500
6.3.3 15 MM Nos. 8 2000 16000

6.4 Ball Valves (without strainer)


BOQ - 3

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)
Providing and fixing in position the
following Ball Valves without strainer duly
insulated as per specifications:

6.4.1 32 MM Nos. 5 3200 16000


6.4.2 25 MM Nos. 2 3000 6000
6.4.3 20 MM Nos. 1 2500 2500

6.5 Balancing Valves

6.5.1 40 MM Nos. 2 4800 9600


6.5.2 32 MM Nos. 6 4200 25200

6.6 Non-Return Valves

6.6.1 80 MM Nos. 2 4500 9000

6.7 3 Way motorised valves

6.7.1 40 mm Nos. 2 12000 24000


6.7.2 32 mm Nos. 6 10000 60000

6.8 Y - Strainers

6.8.1 80 MM Nos. 2 5200 10400

6.9 Pressure Gauges with gauge cock, Nos. 22 1000


thermowell. 22000
6.10 Thermometers with thermowell Nos. 20 1000 20000
6.11 Flow Switches Nos. 2 1000 2000
6.12 Automatic Air Vents Nos. 8 850 6800
6.13 Thermowell of 15 mm dia. Nos. 8 1200 9600
BOQ - 4

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)
6.14 Expansion tank

Providing and fixing Expansion Tank with


50 MM thick EPS insulation and as per
specifications and drawings.

6.14.1 500 Ltrs Nos. 1 2500 2500

7 Pipe Clading

Providing & fixing Aluminium cladding on


pipes/tank with 0.5mm aluminium sheet
with 50mm overlap on joints and fixed with
self tapping screws etc. as per
specifications and drawings. Complete in sqm. 40 2000 80000
all respects.

8 Drain Piping

Providng fixing, testing and commissioning


G.I pipe 'B' class of following sizes with all
necessary fittings, supports duly insulated
with 6mm thick nitrile rubber with
adequate adhesive as per specification etc
as required.

8.1.1 25 MM Rm 30 350 10500


8.1.2 40 MM Rm 15 450 6750
8.1.3 50 MM Rm 15 525 7875

9 Ducting

Sheet metal ducting complete with


supports, dampers, Vanes, nuts, bolts etc.
as per specifications and drawings.

9.1 G.I. Sheet Metal Ducting (Rectangular)

9.1.1 0.63 MM (24 Gauge) Sqm. 180 590 106200


9.1.2 0.80 MM (22 Gauge) Sqm. 65 700 45500

9.2 Aluminium Sheet Ducting

9.2.1 0.63 MM (24 Gauge) Sqm. 160 4000 640000


9.2.2 0.80 MM (22 Gauge) Sqm. 75 5000 375000

9.3 Duct Insulation

Closed cell, Fire retardant, self


extinguishing type crossed linked
polyethylene insulation density not less
than 24 Kg/sqM, 'K' value not more than
0.028 Kcal/degC with adhesive tape etc. on
ducts complete as per specification and
drawings.

9.3.1 13 MM Thick Sqm. 200 480 96000


9.3.2 19 MM Thick Sqm. 160 530 84800
9.3.3 19 MM thick with UV protection Sqm. 75 750 56250

9.4 Duct Acoustic Lining

Providing and fixing duct acoustic lining


with 25 mm thick Non woven polyster fibre
insulation of density 48 kg/sqcm, covered
with 0.5 mm perforated aluminium sheet,
nuts, bolts etc. complete as per
specifications and drawings.

9.4.1 25 MM thick Sqm. 45 490 22050


BOQ - 5

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)
BOQ - 6

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)
10 Grilles/Diffusers

Extruded Aluminium grilles/square


diffusers duly powder coated as per
specifications and drawings.

10.1 Aluminium supply air grilles with damper. Sqm. 4 7500 30000

10.2 Aluminium return air grilles without Sqm. 6 5500 33000

Aluminium supply air square diffuser with


10.3 damper . Sqm. 2 10500 21000

Aluminium return / exhaust air square


10.4 diffuser without damper. Sqm. 2 8000 16000

10.5 Aluminium supply air Laminar flow diffuser

aluminium supply air laminar flow diffuser


10.5.1 with damper (2400x2400) Sqm. 3 11000 33000

11 Fresh Air Louvers

Supply, Installation, Testing and


Commissioning of extruded aluminium
louvres with frame bird screeen 50 mm
pre-filter with frame, mounting
arrangement etc. as per specifications and
drawings.

11.1 Fresh Air Louvers Sqm. 2 8500 17000

12 Fire Damper

Providing and fixing Galvanised sheet fire


damper with limit switch as per
specifications and drawings.
12.1 Supply air fire damper Sqm. 1.5 8500 12750
12.2 Return air fire damper Sqm. 1.5 8500 12750
12.3 Solenoid Assembly for Dampers Nos. 6 9500 57000
12.4 Fresh air dampers Sqm. 1 7000 7000

13. Hot Water Boiler


Supply, installation, testing and
commissioning of Electric Hot Water Boiler
complete with 3 nos. Heater per bank,
fittings, controls and accessories as per
specifications and drawings.

13.1 35 KW No. 1 87500 87500

Sub-Total 'B' Rs. : 3315075

Part-C : Electrical Works ( Part-I)

Electrical Control Panel


Supply, installation, testing and
commissioning of main panel boards made
of 2.0 mm thick steel sheet duly powder
coated complete with voltmeter, ammeter,
indicating lights, selector switch, incoming/
outgoing isolators, current operated single
phase prev
1 Main A.C. Panel-P1
1.1 Incomer
- 1 No. 250 Amps MCCB TP+NL incoming
- 1 No. aluminium conductor bus bar duly
- sleeved
1 No. electronic energy meter with CTs.
- 1 No. Ammeter with ASS & CTs.
- 1 No. voltmeter with VSS.
- 3 Nos. phase indicating lamps
BOQ - 7

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)

Outgoing
- 1 Nos. 125 Amps TP+NL MCCB outgoing
for 36 TR chiller.
- 1 Nos. 100 Amps TP+NL MCCB outgoing
for 24 TR chiller.
- 1 No. 125 Amps MCCB TP+NL outgoing for
Hot Water Boiler of 35 KW.
- 2 Nos. 32 Amps MCB TP+NL outgoing for
chilled water pumps . (1 standby)
- 2 Nos. 16 Amps MCB TP+NL outgoing for
Hot water pumps . (1 standby)
- 1 No. 32 Amps MCB TP+NL outgoing for
All starter shall have following
accessories :
- 1 No. overload relay
- 1 No. Ammeter with ASS & CTs.
- 1 No. single phase preventer MPRD-2 type
- 2 Nos. ON/OFF indicating lights
- 2 Nos. ON/OFF push buttons Set 1 1000000 1000000

2 Sub Panel for AHUs


Supply, installation, testing and
commissioning of wall mounted sub panel
boards for AHUs, Blower with switch,
starters, lamps inter connections, current
operated single phase preventer, A/M
switch etc. as per specifications and
drawings and as required

OUTGOING
- 1 No. 16 Amps MCB for 2.2 KW /1.5 KW/1
KW motor
- 1 No. DOL Starter
- 1 No. single phase preventer MPRD-2 type
- 1 No. ammeter
- 2 Nos indicating lights
- 2 Nos. Push buttons Sets 8 35000 280000

3. Electrical cable
Providing and fixing PVC insulated
armoured aluminium conductor cables
from main panel boards to various
equipments through walls/ceiling with
appropriate clamps and fixing
arrangements, cable tray etc. as per
specifications and drawings.
3.1 3 1/2 Core - 50 mm2 RM 20 400 8000
3.2 3 1/2 Core - 35 mm2 RM 20 350 7000
3.3 3 Core - 35 mm2 RM 20 300 6000
3.4 3 Core - 6 mm2 RM 30 250 7500
3.5 3 Core - 4 mm2 RM 30 225 6750
3.6 4 Core - 4 mm2 RM 100 200 20000
3.7 4 Core - 1.5 mm2 (Copper) RM 50 280 14000
3.8 3 Core - 1.5 mm2 (Copper) RM 100 200 20000

4 Earthing

Double earthing continuity conductors


between panel boards and equipments
as required and as per I.E. rules 1956. 6
SWG G.I. Wire. L.S L.S 10000 10000

Sub-Total 'C' Rs. : 1379250


BOQ-8

24/10/2010

Section 30 Schedule of prices

The prices are to be quoted in the below mentioned form and shall include the supply and
installation at site of all the equipments, ancillary materials as specified and all such items
whatsoever which may be required to fulfil the intent and purpose as laid down in the
specification and/or the drawings.

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)

Part-A : High Side Works (Part-II)

1 Conventional Split System

Supply, installation, testing and


commissioning of Modular type indoor/
outdoor units equipped with highly
efficient scroll/rotary compressors, with
constant speed type compressor(s),
special acryl precoated heat exchanger,
low noise condenser fan, suitable for
following capacities as per specifications
and drawings.With R22 refrigerent.

4.1.1 Indoor Units/Outdoor (Ductables)


4.1.2 11 TR capacity No. 1 155000 155000
4.1.3 8.5 TR capacity Nos. 3 130000 390000
4.1.4 5.5 TR capacity Nos. 6 88000 528000
4.1.5 3 TR capacity Nos. 2 60000 120000

4.2 Indoor Units/Outdoor (High Wall)


4.2.1 2.0 TR capacity Nos. 4 35000 140000
4.2.2 1.5 TR capacity Nos. 11 28500 313500
4.2.3 1.0 TR capacity Nos. 8 22500 180000

Sub-Total 'A' Rs. : 1826500


BOQ-9

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)
Part 'B' : Low Side Works (Part-II)

1 Ducting

Sheet metal ducting complete with


supports, dampers, Vanes, nuts, bolts etc.
as per specifications and drawings.

1.1 G.I. Sheet Metal Ducting (Rectangular)

1.1.1 0.63 MM (24 Gauge) Sqm. 425 590 250750


1.1.2 0.80 MM (22 Gauge) Sqm. 75 700 52500

1.2 Duct Insulation

Closed cell, Fire retardant, self


extinguishing type crossed linked
polyethylene insulation density not less
than 24 Kg/sqM, 'K' value not more than
0.028 Kcal/degC with adhesive tape etc.
on ducts complete as per specification
and drawings.

1.2.1 13 MM Thick Sqm. 425 480 204000

1.3 Duct Acoustic Lining

Providing and fixing duct acoustic lining


with 25 mm thick Non woven polyster
fibre insulation of density 48 kg/sqcm,
covered with 0.5 mm perforated
aluminium sheet, nuts, bolts etc.
complete as per specifications and
drawings.
1.3.1 25 MM thick Sqm. 75 490 36750

2 Grilles/Diffusers

2.1 Extruded Aluminium grilles/square


diffusers duly powder coated as per
specifications and drawings.

2.1.1 Aluminium supply air grilles with damper. Sqm. 6 7500 45000

2.1.2 Aluminium return air grilles without Sqm. 6 5500 33000

2.1.3 Aluminium supply air square diffuser with


damper . Sqm. 4 10500 42000

2.1.4 Aluminium return / exhaust air square


diffuser without damper. Sqm. 4 8000 32000
BOQ-10

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)

2.2 Fresh Air Louvers

Supply, Installation, Testing and


Commissioning of extruded aluminium
louvres with frame bird screeen 50 mm
pre-filter with frame, mounting
arrangement etc. as per specifications
and drawings.
2.2.1 Fresh Air Louvers Sqm. 2 8500 17000

3 Fire Damper

Providing and fixing Galvanised sheet fire


damper with limit switch as per
specifications and drawings.

3.1.1 Supply/Return air fire damper Sqm. 5 8500 42500


3.1.2 Solenoid Assembly for Dampers Nos. 12 9500 114000
3.1.3 Fresh air dampers Sqm. 2 7000 14000

4 Refrigerant Piping

4.1 Supply, Installation, testing and


commissioning of Interconnecting
refrigerant pipe work between each set
of indoor & outdoor units all piping inside
the room shall be properly supported with
MS hanger and all external piping shall
run on cable tray. The suction line shall
be insulated with 9 mm thick nitrile
rubber insulation as per specifications &
drawings.
4.1.1 11 TR RM 30 1,450 43500
4.1.2 8.5 TR RM 45 1,250 56250
4.1.3 5.5 TR RM 90 1,150 103500
4.1.4 3 TR RM 30 900 27000
4.1.5 2 TR RM 60 750 45000
4.1.6 1.5 TR RM 165 650 107250
4.1.7 1 TR RM 120 650 78000

5 Drain Piping

Supply & Installation of heavy duty PVC


drain pipe with min. wall thickness of 4
mm with insulation. Insulation shall be of
6 mm thick sleeve of nitrile
rubber/polyethylene foam having K valve
0.027 W/mk at a mean temp. of 10°C and
min. density of 26 Kg/m3. Insulation on
drain pipe shall be carried out only where
the pipe is running within the wall.
Exposed pipe shall be without insulation.
The insulation joints shall be properly
sealed with rubber based adhesive to
ensure proper bonding.
5.1 50 mm dia RM 30 275 8250
5.2 40 mm dia RM 50 225 11250
5.3 25 mm dia. RM 100 195 19500
BOQ-11

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)
7 Ventilation Equipment

7.1 Propellor fan


Supplying, Installing, Testing and
Commissioning of Propeloor fans
complete with , supporting frame, gravity
louvres, etc. as per drawings and
specifications.
7.1.1 225 MM Dia @ 10 mm static pressure Nos. 20 2200 44000
7.1.2 300 MM Dia @ 10 mm static pressure Nos. 6 2750 16500

8. Electric Heating Set

Supply, installation, testing and


commissioning of Electric Heating Set
complete with the following as per
specifications and drawings
8.1 Split Unit of 11 TR complete with
- 3 nos. Strip heater of 3.7 KW each
- 1 no. contracter of 63 Amps
- 1 no. M.S. Mounting Frame
- 1 no. Safety Themostat Set 1 22000 22000

8.2 Split Unit of 8.5 TR complete with


- 3 nos. Strip heater of 3 KW each
- 1 no. contracter of 40 Amps
- 1 no. M.S. Mounting Frame
- 1 no. Safety Themostat Set 3 17000 51000

8.3 Split Unit of 5.5 TR complete with


- 3 nos. Strip heater of 2 KW each
- 1 no. contracter of 40 Amps
- 1 no. M.S. Mounting Frame
- 1 no. Safety Themostat Set 6 12000 72000

8.4 Split Unit of 3 TR complete with


- 3 nos. Strip heater of 1.1 KW each
- 1 no. contracter of 16 Amps
- 1 no. M.S. Mounting Frame
- 1 no. Safety Themostat Set 2 7000 14000

Sub-Total 'B' Rs. : 1602500


BOQ-12

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)
Part 'C' : Electrical Works (Part-II)

Electrical Control Panel


Supply, installation, testing and
commissioning of main panel boards
made of 2.0 mm thick steel sheet duly
powder coated complete with voltmeter,
ammeter, indicating lights, selector
switch, incoming/ outgoing isolators,
current operated single phase prev

1 Sub Panel
1.1 Sub Panel 1: Incomer/Outgoing
- 1 No. 63 Amps MCCB TP+NL incoming Set 1 22000 22000
/outgoing for Electric Heating Set
- 1 No. 63 Amps aluminium conductor bus
bar duly sleeved
- 1 No. Ammeter with ASS & CTs.
- 1 No. voltmeter with VSS.
- 3 Nos. phase indicating lamps

1.2 Sub Panel 2: Incomer/Outgoing


- 1 No. 40 Amps MCCB TP+NL incoming Set 3 15000 45000
/outgoing for Electric Heating Set
- 1 No.40 Amps aluminium conductor bus
bar duly sleeved
- 1 No. Ammeter with ASS & CTs.
- 1 No. voltmeter with VSS.
- 3 Nos. phase indicating lamps

1.3 Sub Panel 3: Incomer/Outgoing


- 1 No. 32 Amps MCCB TP+NL incoming Set 6 10500 63000
/outgoing for Electric Heating Set
- 1 No.32 Amps aluminium conductor bus
bar duly sleeved
- 1 No. Ammeter with ASS & CTs.
- 1 No. voltmeter with VSS.
- 3 Nos. phase indicating lamps

1.4 Sub Panel 4: Incomer/Outgoing


- 1 No. 16 Amps MCCB TP+NL incoming Set 2 8000 16000
/outgoing for Electric Heating Set
- 1 No.16 Amps aluminium conductor bus
bar duly sleeved
- 1 No. Ammeter with ASS & CTs.
- 1 No. voltmeter with VSS.
- 3 Nos. phase indicating lamps
BOQ-13

S.No. Description Unit Qty. Rate Amount


(Rs.) (Rs.)

2. Power & Control Cabling

Supply and fixing of PVC insulated


armoured aluminium conductor cables
1100 Volts grade from main panel
boards to various equipments through
walls/ceiling with appropriate
clamps,cable termination and fixing
arrangements, cable tray etc. as per
specifications and drawings.
2.1 4 Core - 6 mm2 RM 100 450 45000
2.2 4 Core - 4 mm2 RM 40 415 16600
2.3 6 Core - 2.5 mm2 (Copper) RM 200 325 65000
2.4 4 Core - 2.5 mm2 (Copper) RM 300 300 90000
2.5 4 Core - 1.5 mm2 (Copper) RM 120 275 33000
2.6 2 Core - 1.5 mm2 (Copper) RM 40 250 10000

4. Isolator (for outdoor units)

Providing & fixing weather proof isolator


near each outdoor unit.

4.1 63 Amps TP+NL Isolator near outdoor unit Nos. 4 15000 60000
4.2 40 Amps TP+NL Isolator near outdoor unit Nos. 6 8000 48000
4.3 32 Amps TP+NL Isolator near outdoor unit Nos. 2 6500 13000

5. Earthing

Double earthing continuity conductors


between panel boards and equipments
as required and as per I.E. rules 1956. 6
SWG G.I. Wire. L.S L.S 10000 10000

Sub-Total 'C' Rs. : 536600