Anda di halaman 1dari 6

Home Search Collections Journals About Contact us My IOPscience

Conductor requirements for high-temperature superconducting utility power transformers

This article has been downloaded from IOPscience. Please scroll down to see the full text article.

2010 Supercond. Sci. Technol. 23 014025

(http://iopscience.iop.org/0953-2048/23/1/014025)

View the table of contents for this issue, or go to the journal homepage for more

Download details:
IP Address: 188.22.54.253
The article was downloaded on 25/12/2010 at 08:31

Please note that terms and conditions apply.


IOP PUBLISHING SUPERCONDUCTOR SCIENCE AND TECHNOLOGY
Supercond. Sci. Technol. 23 (2010) 014025 (5pp) doi:10.1088/0953-2048/23/1/014025

Conductor requirements for


high-temperature superconducting utility
power transformers
E F Pleva1 , V Mehrotra1 and S W Schwenterly2
1
Waukesha Electric Systems, Waukesha, WI 53186, USA
2
Oak Ridge National Laboratory, Oak Ridge, TN 37831, USA

E-mail: Ed.Pleva@Waukesha.spx.com

Received 11 September 2009, in final form 19 October 2009


Published 9 December 2009
Online at stacks.iop.org/SUST/23/014025

Abstract
High-temperature superconducting (HTS) coated conductors in utility power transformers must
satisfy a set of operating requirements that are driven by two major considerations—HTS
transformers must be economically competitive with conventional units, and the conductor must
be robust enough to be used in a commercial manufacturing environment. The transformer
design and manufacturing process will be described in order to highlight the various
requirements that it imposes on the HTS conductor. Spreadsheet estimates of HTS transformer
costs allow estimates of the conductor cost required for an HTS transformer to be competitive
with a similarly performing conventional unit.
(Some figures in this article are in colour only in the electronic version)

1. Introduction Electric Systems (WES), SuperPower Inc., Oak Ridge National


Laboratory (ORNL) and the utility Energy East culminated in
Power transformers are an essential component of the electric the testing of a 5 MVA HTS transformer that was intended for
utility grid, providing both voltage step-up from generator operation in the substation at WES’s factory [9]. This unit met
outputs in the range of 25 kV to transmission levels above most of its current carrying and cryogenic goals. However, the
100 kV and step-down back to distribution levels near the cast-epoxy-insulated coils cracked during cooldown, leading
load points. In a power grid system, each MVA of generation to an electrical breakdown when the unit was energized at
capacity requires an average of 5–7 MVA of transformer high voltage. This transformer used first-generation Bi-
capacity between each generator and the loads it serves. Due 2223 conductor and operated near 25 K. The development
to the large number of transformers in the system, even a in recent years of commercial second-generation YBCO
fractional per cent efficiency gain on each one can add up to coated conductor tapes (YBCO-CCs) offers the prospect of
large energy savings. HTS transformers offer the advantages operation in liquid nitrogen. This would allow much simpler
of reduced losses due to the lack of Joule heating, as well refrigeration schemes and improved high-voltage dielectric
as reduced unit weight and volume. Because they use liquid performance. A follow-on collaboration between WES and
nitrogen in place of insulating oil, they present minimal fire ORNL has continued in order to determine whether these
hazard and environmental impact. Furthermore, they can be
advantages can be realized in a practical, production-ready
run at overload with increased refrigeration requirements, but
HTS transformer design with a rating of 25 MVA or above.
no loss of life such as that caused by overheating of the oil
In this paper it is assumed that YBCO-CC HTS tape would be
and insulation in a conventional unit. Finally, it is possible to
used in the transformer.
design an HTS transformer with built-in fault current limiting
capability.
Prototype HTS transformers have been built by teams 2. Transformer layout
in several countries, including Europe [1–4], Japan [5, 6],
China [7], and Korea [8]. In 2004, a Superconductivity Figure 1 shows a generic HTS transformer layout. The high-
Partnership Initiative (SPI) collaboration between Waukesha and low-voltage windings for each phase are concentric and are

0953-2048/10/014025+05$30.00 1 © 2010 IOP Publishing Ltd Printed in the UK


Supercond. Sci. Technol. 23 (2010) 014025 E F Pleva et al

Figure 2. Conventional transformer disc winding showing crossover


transitions.

a continuous length of conductor to minimize splices. In a


conventional transformer, transitions between discs are made
by making a sharp S-bend on the conductor in the ‘hard’
Figure 1. Schematic of HTS transformer cross section.
direction as shown in figure 2. This sort of abuse would destroy
the superconducting layer if the in-plane bending radius is less
than about 1 m [10]. It can be shown that transitions with such a
enclosed in a vacuum-insulated dewar vessel. The windings
large bending radius would be unreasonably long and interfere
are bathed in pressurized nitrogen held at a temperature near
with the spacers between discs. In an HTS winding, it will
70 K by a cooling shell located at the outer perimeter of
the dewar. The three winding sets are installed on a three- instead be necessary to make these transitions in such a way
phase core of laminated steel. This core is very similar to that the conductor can bend and twist slightly with minimum
the one in a conventional unit. The core is in ambient air, in-plane deformation. Extra support pieces may be needed for
and must be insulated from the inner diameter of the windings the transitions to prevent the conductor from deforming under
by the dewar vessel. Since the dewar vessel cannot form a the winding tension.
shorted turn around a core limb, it must be made of electrically Conventional transformer discs have between 20 and
insulating composite materials. The high-voltage bushings and 30 turns. This keeps the windings and thus the steel core
cryocoolers coupled to the cooling shells are installed in the limbs from becoming too tall. Core limbs longer than 2 m
upper part of the dewar vessel. A weather enclosure surrounds are flexible and difficult to handle in the factory. Enough
the unit in place of the usual oil tank in a conventional unit. window area is needed to accommodate the required winding
Cooling for the core is provided by a blower that forces air turns, insulation clearances, and dewar vacuum spaces. Core
flow through baffles around the upper and lower yokes, and up windows with a height–width ratio in the neighborhood of
through the three annular gaps between the dewars and core 1.5 reduce the required amount of core steel (and thus core
limbs. losses) in comparison with tall, narrow windows. On the
other hand, going to 20 or more turns per disc in an HTS
3. The transformer manufacturing process transformer greatly increases the magnetic fields on the inner
turns, reducing the critical current and increasing the ac loss.
To speed the adoption of HTS materials in transformers, it is Furthermore, shorter windings with more turns per disc have a
highly desirable to use winding concepts that closely parallel greater portion of the volume in the end regions that experience
those for conventional units. This will allow conventional high perpendicular magnetic fields. These perpendicular fields
manufacturing techniques and materials to be used without can reduce the critical current due to the anisotropic field
major modifications and minimize retraining of production dependence, as well as increase ac loss. Discs with about
personnel. High-voltage tests at WES and ORNL have
10 turns would thus be preferable in an HTS transformer.
shown that conventional pressboard and kraft paper materials
However, discs with 10 turns lead to larger-diameter core
impregnated with liquid nitrogen give breakdown strengths
limbs to increase the volts per turn and reduce core height.
comparable to values with oil.
This increases core weight and core losses, which are heavily
penalized by utility customers in their economic evaluation of a
3.1. Winding configuration transformer design. To reduce these disadvantages, conductor
High-voltage transformer windings are generally wound in manufacturers will need to reduce ac losses in the conductor
discs or pancakes as opposed to layer windings. The disc by striating or filamentizing the HTS [11–14]. Introduction of
configuration helps the windings withstand lightning and artificial pinning centers such as nano-particles can also reduce
switching voltage surges by distributing the surge voltage ac losses by improving the critical current and reducing the
more evenly along the winding. The discs are wound from anisotropy of the magnetic field effect [15–22].

2
Supercond. Sci. Technol. 23 (2010) 014025 E F Pleva et al

3.2. Conductor design of thickness 1 mm, the resistance can easily be an order of
magnitude above the winding reactance. Such a winding can
YBCO-CCs as they currently come from the manufacturer are
provide significant current limiting, though the current must be
typically 3.0–12.0 mm wide, and are only about 100–200 µm
interrupted by a breaker within ∼0.1 s to prevent overheating
thick. The critical current of the tape must exceed the peak
of the conductor. In this case, the calculated temperature
value of the current in overload operation. Since the critical
rise is on the order of 100 K and the maximum temperature
current is affected by the magnitude and orientation of the
would be about 170 K. The maximum allowable temperature
magnetic field, the location of the area in the windings with
is determined from estimates of differential thermal expansion
minimum critical current needs to be carefully identified. The
stresses and the required re-cooling time for the unit. The
designer must also consider the statistical variation of the self-
greatest stabilizer thickness now offered by US commercial
field critical current over each delivered length of tape.
suppliers is about 0.35 mm.
In a typical substation installation, there are two
The fault currents also create large forces on the windings,
transformers that split the load. Generally, transformers are
and so the conductor must be robust to withstand them. This
designed to be able to operate for short periods of about
is particularly true for the inner winding, which is subjected
30 min at an overload current of twice the rated value, so
that if one transformer fails, the other can assume the full to large radial inward forces and axial compressive forces
load. A single tape in the high-voltage winding of a 25 MVA, that can bend the conductor between spacers. The outer
115 kV transformer would need a minimum critical current winding experiences radial outward forces, but it will still
above 205 A. It will be necessary for manufacturers to offer have high compressive axial forces on the discs near the ends.
a wide range of tape widths so that the transformer designer The windings must be tight to prevent turn motion in faults
can properly match the critical current with the required value and vibration with ac currents. Typical transformer winding
for a given transformer voltage and current rating and optimize tensions are in the range of 90 N (20 lb). The transformer
the design. For conventional transformers, copper conductor windings must also be very tightly compressed along the
dimensions come in 0.1 mm increments. The low-voltage winding axis. This causes the winding turns to partially indent
winding will generally carry a current an order of magnitude the spacers between discs and helps prevent them from slipping
above the high-voltage current. Multiple conductors will be under fault forces. A conductor width-to-thickness ratio near
required, and these will most likely need a different width from six or seven is preferred so that the stack of conductors in a
the high-voltage conductor. The finished conductor should disc will be stable under radial and winding tension forces,
incorporate extra metal stabilizer as discussed below. The but will not twist and tilt under axial forces from faults. In
conductor with its attached stabilizer must have rounded edges a conventional transformer, the windings are compressed with
and be smooth and free of burrs that could trigger a high- hydraulic jacks before the top core yoke is installed, and held
voltage breakdown. The surfaces of currently available YBCO- in compression by the core itself. A typical compression
CCs are quite smooth due to processing requirements, but the pressure is 15 MPa (2200 psi) spread across the top of the
slitting process that sets the finished width produces sharp winding, causing the winding to shorten by about 1.5%. In
edges. These must be smoothed or shielded by the attached an HTS transformer, the windings are supported inside the
stabilizer. dewar vacuum jacket and are not strongly coupled to the core.
The YBCO-CC needs to have extra normal metal stabilizer Compression would instead be provided by end plates retained
added for several reasons. If the transformer terminals are by long non-conductive threaded rods and springs or Belville
short-circuited, fault currents an order of magnitude above the washers.
operating current can flow briefly until circuit breakers in the If the stabilizer is equally distributed on either side of
network open. Enough stabilizer must be provided to carry the tape so that the YBCO-CC is at the neutral axis, it will
the fault current without going too far above liquid nitrogen experience minimal bending forces. Such a conductor can
temperature after the YBCO layer quenches. A stabilizer be bent to a radius near 1 cm without degradation of the
thickness of 1 mm or more is desirable. In a fault, the current critical current [23]. However, in a 25 MVA-class winding
will rise to some multiple of the critical current in the first with diameter in the range of 0.75 m, it may be possible
quarter cycle until the YBCO layer quenches. Current will then to keep bending strains below 0.1%, so that the YBCO-CC
quickly transfer to the stabilizer. The stabilizer current then can be on the outside, bonded to both sides of the stabilizer.
falls to a value determined by the ratio of the winding voltage to This may be beneficial in reducing ac losses in the conductor
its impedance, which is a combination of the winding reactance if the superconductor is able to partially shield the stabilizer
and the stabilizer resistance in quadrature. If the fault is from the magnetic field. However, further testing is needed
terminated when a breaker trips, the temperature rise can be in real winding geometries to determine which configuration
estimated with a straightforward adiabatic calculation from is preferred. It would of course be preferable to deposit the
the stabilizer cross-section area, resistivity, and heat capacity, whole HTS stack including buffer and cap layers directly on the
for a given fault duration. If a copper stabilizer is used, the stabilizer, and we hope that this would be a future development
stabilizer resistance will typically be small compared to the by the conductor suppliers.
winding reactance, and the reactance will determine the fault It could be argued that the addition of extra metal stabilizer
current. For a 0.5 s fault, about 2 mm of copper can limit the reduces the engineering current density in the winding
temperature rise to about 10 K, but will not provide current and might negate the advantages of using superconducting
limiting. With a resistive stabilizer such as stainless steel materials. However, this is not an issue in a transformer

3
Supercond. Sci. Technol. 23 (2010) 014025 E F Pleva et al

because heavy conductor insulation and few-mm clearances


between winding discs must be provided in any case to prevent
high-voltage breakdown. High-field magnets generally require
high winding current densities, but in a transformer the high
permeability of the core steel instead of the conductor provides
the high field of about 1.7 T. Typical copper current densities
in a conventional transformer winding are in the range of
3–4 A mm−2 . In contrast, a YBCO conductor carrying 200 A
with overall dimensions of say, 10 mm × 1.1 mm including
stabilizer has an effective current density of 18 A mm−2 . This
reduces the winding volume, resulting in an HTS transformer
with about half the volume and 60% of the weight of a
conventional unit.

3.3. Piece lengths


Utility power transformers typically operate in the range of
70–100 V/turn. Thus the high-voltage winding of a 25 MVA, Figure 3. Winding machine applying insulating tapes.
115 kV transformer might have about 1400 turns. The
average turn diameter is determined by the core diameter plus
clearances for assembly, dewar vacuum jackets, and electrical a few tenths of a tesla. A calculation of the total ac loss
insulation. For a 25 MVA transformer, this would be about distribution in the winding is very complex and requires details
0.75 m as mentioned above. A total of about 6 km of YBCO- of the winding configuration. However, a required average loss
CC would be required for each of the three phases, with figure can be calculated easily. Assume for a 25 MVA unit
respectively about 3.2 and 2.8 km in the high- and low-voltage that a maximum of 1200 W of refrigeration is available, which
windings. The windings would be constructed from 8 to is a practical value for existing commercial cryocoolers. The
10 similar modules that could be separately tested in liquid losses from the current leads, conduction in the structure, and
nitrogen, in order to reduce the amount of expensive YBCO- radiation would total about 400 W, leaving 800 W available for
CC at risk if a module should fail. If the high-voltage winding the ac losses. If the unit contains a total of 18 km of conductor,
has a single conductor, each module would require a 300– the required average ac loss would then be 44 mW m−1 . Loss
400 m long piece of tape. The low-voltage modules would measurements should be made on scaled-down test coils with
have 10 or more conductors in parallel, with each piece length the same layer build as the full-size winding to estimate the
on the order of 20 m. Low-resistance splices can be made loss performance.
to join shorter lengths of tape and to connect the modules
together [24].
4. Economic comparisons
3.4. Conductor insulation A comprehensive spreadsheet tool has been developed for
The conductor is wrapped with roughly 0.5 mm of high- calculating HTS transformer costs, dimensions, weights, and
voltage insulation on automatic high-speed machines before it losses. This has been used to compare the lifetime cost of
is wound into the transformer coils. Figure 3 shows a close-up ownership of a 25 MVA, 115 kV/13.09 kV HTS transformer
of this process. The insulating tapes are under tension, and the with that of a similar conventional unit recently delivered by
extra stabilizer material also helps the conductor withstand side WES. The conventional unit is air-cooled by radiators equipped
forces and torques during the wrapping operation. It should be with fans. It has 15, 20, or 25 MVA ratings with respectively no
noted that the YBCO-CC could not simply be laid next to the fans, one stage of fans, or two stages. It can operate for 30 min
stabilizer and co-wrapped with high-voltage insulation. Our at 50 MVA load with increasing temperature. We propose that
winding tests have shown that if this is done, the component an equivalent HTS unit would have cryocoolers sized to the
on the inside radius tends to buckle and split the insulation, 25 MVA load. It would contain enough HTS conductor so
due to the slightly different bend diameters of the conductor that with a 50 MVA load, the peak current would be below the
layers. HTS critical current. For loads below 25 MVA, the cryocoolers
would be cycled on and off or slowed down to match the
load and maintain a temperature near 70 K. With 50 MVA
3.5. AC loss
operation, the leads and windings would run with high losses
The ac loss at a given point in the winding is a combination and boil off liquid nitrogen. Enough stored nitrogen (roughly
of self-field strip losses, fully penetrated hysteresis losses from 100 l) would be provided on-site so that the transformer could
the external fields produced by the rest of the winding, possible operate at 50 MVA for 30 min. The spreadsheet was run with
ferromagnetic losses from the YBCO-CC substrate, and eddy current commercial copper and steel costs and HTS conductor
current losses generated in the stabilizer. Maximum peak cost assumptions ranging from $10 to $50 kA−1 m−1 . The
magnetic fields in a transformer winding are in the range of utility customer adds a loss penalty to the selling price to

4
Supercond. Sci. Technol. 23 (2010) 014025 E F Pleva et al

Table 1. Comparison of required conductor properties with current and more compact, and would reduce both core no-load losses
available values. and conductor load losses. To handle insulating, winding, and
Conductor property Required value Current value fault forces as well as heating generated in faults, 1 mm or
−1 −1 more of extra stabilizer must be bonded to the YBCO-CC.
Price ($ kA m ) 20 400–500
Available width 6–12 in 0.1 mm 3, 4, 4.4, 6, 12 The conductor must be smooth with rounded corners for high-
(mm) increments voltage integrity. Piece lengths on the order of 400 m for the
Winding magnetic 0.3 2 high-voltage winding and 20 m for the low-voltage winding are
field (T) required. Table 1 compares current commercial offerings by
AC loss (mW m−1 ) 40–50 (average in Winding-dependent US suppliers with these requirements [25–27]. Available piece
winding)
Stabilizer thickness 1 0.35
lengths, widths, and field capabilities meet the requirements
(mm) for prototype test units. Measurements of ac loss are highly
Piece length (m) 400 1000 dependent on winding design, but preliminary results on test
coils appear to be acceptable. The main requirement for
prototype units that still needs to be satisfied is the provision
determine a total lifetime cost of ownership. These loss penalty of thicker stabilizer material.
costs vary greatly among various utility companies, but typical
values are $1250 kW−1 for load losses and $2500 kW−1 for
References
no-load losses. The calculations show that if the YBCO-
CC costs $20 kA−1 m−1 and cryogenic refrigerator costs are [1] Zueger H 1998 Cryogenics 38 1169–72
half the current values, the HTS and conventional lifetime [2] Jelinek Z et al 2003 IEEE Trans. Appl. Supercond. 13 2310–2
costs of ownership are comparable. Note that the required [3] Godeke A et al 2001 IEEE Trans. Appl. Supercond. 11 1570–3
YBCO-CC price is less than 5% of current prices. The current [4] Kummeth P et al 2000 Supercond. Sci. Technol. 13 503–5
[5] Kamijo H et al 2007 IEEE Trans. Appl. Supercond.
prices are so far not very sensitive to purchased lot sizes 17 1927–30
because price reductions are brought about more by increases [6] Bohno T et al 2005 Physica C 426–431 1402–7
in the manufacturer’s total production volume, not the size [7] Wang Y et al 2006 IEEE Trans. Appl. Supercond. 16 1477–80
of individual lots. The price is expected to fall an order of [8] Kim S et al 2005 IEEE Trans. Appl. Supercond. 15 2214–7
magnitude to about $50 kA−1 m−1 during the next decade. [9] Weber C et al 2005 IEEE Trans. Appl. Supercond. 15 2210–3
[10] van der Laan D C et al 2008 Supercond. Sci. Technol.
Even at this price level, HTS transformers may be competitive 21 115002–7
with conventional units in certain applications where their [11] Amemiya N et al 2004 Supercond. Sci. Technol. 17 1464–71
additional advantages are most important. As mentioned in [12] Duckworth R et al 2009 IEEE Trans. Appl. Supercond.
section 1, these include higher efficiency, greatly reduced fire 19 3327–31
and environmental hazards due to the lack of flammable oil, [13] Lee J et al 2009 IEEE Trans. Appl. Supercond. 19 3340–3
[14] Majoros M et al 2009 IEEE Trans. Appl. Supercond.
reduced weight and size, overload operation with no loss of 19 3352–5
life, and fault current limiting capability. [15] Funaki S et al 2009 IEEE Trans. Appl. Supercond. 19 3168–71
[16] Chen J et al 2009 IEEE Trans. Appl. Supercond. 19 3254–7
5. Summary [17] Pomar A et al 2009 IEEE Trans. Appl. Supercond. 19 3258–61
[18] Yoshida Y et al 2009 IEEE Trans. Appl. Supercond. 19 3262–5
The foregoing investigations show that for HTS transformers to [19] Wee S et al 2009 IEEE Trans. Appl. Supercond. 19 3266–9
be cost-competitive with conventional units, a conductor price [20] Haugan T et al 2009 IEEE Trans. Appl. Supercond. 19 3270–4
[21] Miura M et al 2009 IEEE Trans. Appl. Supercond. 19 3275–8
reduction to less than 5% of current levels is needed, as well
[22] Namba M et al 2009 IEEE Trans. Appl. Supercond. 19 3495–8
as a 50% reduction in current cryocooler costs. The minimum [23] Verebelyi D et al 2003 Supercond. Sci. Technol. 16 1158–61
YBCO-CC critical current in the windings must be above the [24] Rey C M et al 2009 IEEE Trans. Appl. Supercond. 19 2317–20
transformer’s peak current in overload operation. Conductor [25] See 2009 DOE Peer Review presentations at http://www.
should be available in custom widths to properly match the htspeerreview.com/agenda.html
[26] See American Superconductor site at http://www.amsc.com/
unit’s rated peak current. The conductor must operate in a
products/htswire/2GWireTechnology.html
maximum peak ac field of a few tenths of a tesla. Reduction [27] See SuperPower site at http://www.superpower-inc.com/
of ac losses would allow the transformer core to be lighter content/products

Anda mungkin juga menyukai