This article has been downloaded from IOPscience. Please scroll down to see the full text article.
(http://iopscience.iop.org/0953-2048/23/1/014025)
View the table of contents for this issue, or go to the journal homepage for more
Download details:
IP Address: 188.22.54.253
The article was downloaded on 25/12/2010 at 08:31
E-mail: Ed.Pleva@Waukesha.spx.com
Abstract
High-temperature superconducting (HTS) coated conductors in utility power transformers must
satisfy a set of operating requirements that are driven by two major considerations—HTS
transformers must be economically competitive with conventional units, and the conductor must
be robust enough to be used in a commercial manufacturing environment. The transformer
design and manufacturing process will be described in order to highlight the various
requirements that it imposes on the HTS conductor. Spreadsheet estimates of HTS transformer
costs allow estimates of the conductor cost required for an HTS transformer to be competitive
with a similarly performing conventional unit.
(Some figures in this article are in colour only in the electronic version)
2
Supercond. Sci. Technol. 23 (2010) 014025 E F Pleva et al
3.2. Conductor design of thickness 1 mm, the resistance can easily be an order of
magnitude above the winding reactance. Such a winding can
YBCO-CCs as they currently come from the manufacturer are
provide significant current limiting, though the current must be
typically 3.0–12.0 mm wide, and are only about 100–200 µm
interrupted by a breaker within ∼0.1 s to prevent overheating
thick. The critical current of the tape must exceed the peak
of the conductor. In this case, the calculated temperature
value of the current in overload operation. Since the critical
rise is on the order of 100 K and the maximum temperature
current is affected by the magnitude and orientation of the
would be about 170 K. The maximum allowable temperature
magnetic field, the location of the area in the windings with
is determined from estimates of differential thermal expansion
minimum critical current needs to be carefully identified. The
stresses and the required re-cooling time for the unit. The
designer must also consider the statistical variation of the self-
greatest stabilizer thickness now offered by US commercial
field critical current over each delivered length of tape.
suppliers is about 0.35 mm.
In a typical substation installation, there are two
The fault currents also create large forces on the windings,
transformers that split the load. Generally, transformers are
and so the conductor must be robust to withstand them. This
designed to be able to operate for short periods of about
is particularly true for the inner winding, which is subjected
30 min at an overload current of twice the rated value, so
that if one transformer fails, the other can assume the full to large radial inward forces and axial compressive forces
load. A single tape in the high-voltage winding of a 25 MVA, that can bend the conductor between spacers. The outer
115 kV transformer would need a minimum critical current winding experiences radial outward forces, but it will still
above 205 A. It will be necessary for manufacturers to offer have high compressive axial forces on the discs near the ends.
a wide range of tape widths so that the transformer designer The windings must be tight to prevent turn motion in faults
can properly match the critical current with the required value and vibration with ac currents. Typical transformer winding
for a given transformer voltage and current rating and optimize tensions are in the range of 90 N (20 lb). The transformer
the design. For conventional transformers, copper conductor windings must also be very tightly compressed along the
dimensions come in 0.1 mm increments. The low-voltage winding axis. This causes the winding turns to partially indent
winding will generally carry a current an order of magnitude the spacers between discs and helps prevent them from slipping
above the high-voltage current. Multiple conductors will be under fault forces. A conductor width-to-thickness ratio near
required, and these will most likely need a different width from six or seven is preferred so that the stack of conductors in a
the high-voltage conductor. The finished conductor should disc will be stable under radial and winding tension forces,
incorporate extra metal stabilizer as discussed below. The but will not twist and tilt under axial forces from faults. In
conductor with its attached stabilizer must have rounded edges a conventional transformer, the windings are compressed with
and be smooth and free of burrs that could trigger a high- hydraulic jacks before the top core yoke is installed, and held
voltage breakdown. The surfaces of currently available YBCO- in compression by the core itself. A typical compression
CCs are quite smooth due to processing requirements, but the pressure is 15 MPa (2200 psi) spread across the top of the
slitting process that sets the finished width produces sharp winding, causing the winding to shorten by about 1.5%. In
edges. These must be smoothed or shielded by the attached an HTS transformer, the windings are supported inside the
stabilizer. dewar vacuum jacket and are not strongly coupled to the core.
The YBCO-CC needs to have extra normal metal stabilizer Compression would instead be provided by end plates retained
added for several reasons. If the transformer terminals are by long non-conductive threaded rods and springs or Belville
short-circuited, fault currents an order of magnitude above the washers.
operating current can flow briefly until circuit breakers in the If the stabilizer is equally distributed on either side of
network open. Enough stabilizer must be provided to carry the tape so that the YBCO-CC is at the neutral axis, it will
the fault current without going too far above liquid nitrogen experience minimal bending forces. Such a conductor can
temperature after the YBCO layer quenches. A stabilizer be bent to a radius near 1 cm without degradation of the
thickness of 1 mm or more is desirable. In a fault, the current critical current [23]. However, in a 25 MVA-class winding
will rise to some multiple of the critical current in the first with diameter in the range of 0.75 m, it may be possible
quarter cycle until the YBCO layer quenches. Current will then to keep bending strains below 0.1%, so that the YBCO-CC
quickly transfer to the stabilizer. The stabilizer current then can be on the outside, bonded to both sides of the stabilizer.
falls to a value determined by the ratio of the winding voltage to This may be beneficial in reducing ac losses in the conductor
its impedance, which is a combination of the winding reactance if the superconductor is able to partially shield the stabilizer
and the stabilizer resistance in quadrature. If the fault is from the magnetic field. However, further testing is needed
terminated when a breaker trips, the temperature rise can be in real winding geometries to determine which configuration
estimated with a straightforward adiabatic calculation from is preferred. It would of course be preferable to deposit the
the stabilizer cross-section area, resistivity, and heat capacity, whole HTS stack including buffer and cap layers directly on the
for a given fault duration. If a copper stabilizer is used, the stabilizer, and we hope that this would be a future development
stabilizer resistance will typically be small compared to the by the conductor suppliers.
winding reactance, and the reactance will determine the fault It could be argued that the addition of extra metal stabilizer
current. For a 0.5 s fault, about 2 mm of copper can limit the reduces the engineering current density in the winding
temperature rise to about 10 K, but will not provide current and might negate the advantages of using superconducting
limiting. With a resistive stabilizer such as stainless steel materials. However, this is not an issue in a transformer
3
Supercond. Sci. Technol. 23 (2010) 014025 E F Pleva et al
4
Supercond. Sci. Technol. 23 (2010) 014025 E F Pleva et al
Table 1. Comparison of required conductor properties with current and more compact, and would reduce both core no-load losses
available values. and conductor load losses. To handle insulating, winding, and
Conductor property Required value Current value fault forces as well as heating generated in faults, 1 mm or
−1 −1 more of extra stabilizer must be bonded to the YBCO-CC.
Price ($ kA m ) 20 400–500
Available width 6–12 in 0.1 mm 3, 4, 4.4, 6, 12 The conductor must be smooth with rounded corners for high-
(mm) increments voltage integrity. Piece lengths on the order of 400 m for the
Winding magnetic 0.3 2 high-voltage winding and 20 m for the low-voltage winding are
field (T) required. Table 1 compares current commercial offerings by
AC loss (mW m−1 ) 40–50 (average in Winding-dependent US suppliers with these requirements [25–27]. Available piece
winding)
Stabilizer thickness 1 0.35
lengths, widths, and field capabilities meet the requirements
(mm) for prototype test units. Measurements of ac loss are highly
Piece length (m) 400 1000 dependent on winding design, but preliminary results on test
coils appear to be acceptable. The main requirement for
prototype units that still needs to be satisfied is the provision
determine a total lifetime cost of ownership. These loss penalty of thicker stabilizer material.
costs vary greatly among various utility companies, but typical
values are $1250 kW−1 for load losses and $2500 kW−1 for
References
no-load losses. The calculations show that if the YBCO-
CC costs $20 kA−1 m−1 and cryogenic refrigerator costs are [1] Zueger H 1998 Cryogenics 38 1169–72
half the current values, the HTS and conventional lifetime [2] Jelinek Z et al 2003 IEEE Trans. Appl. Supercond. 13 2310–2
costs of ownership are comparable. Note that the required [3] Godeke A et al 2001 IEEE Trans. Appl. Supercond. 11 1570–3
YBCO-CC price is less than 5% of current prices. The current [4] Kummeth P et al 2000 Supercond. Sci. Technol. 13 503–5
[5] Kamijo H et al 2007 IEEE Trans. Appl. Supercond.
prices are so far not very sensitive to purchased lot sizes 17 1927–30
because price reductions are brought about more by increases [6] Bohno T et al 2005 Physica C 426–431 1402–7
in the manufacturer’s total production volume, not the size [7] Wang Y et al 2006 IEEE Trans. Appl. Supercond. 16 1477–80
of individual lots. The price is expected to fall an order of [8] Kim S et al 2005 IEEE Trans. Appl. Supercond. 15 2214–7
magnitude to about $50 kA−1 m−1 during the next decade. [9] Weber C et al 2005 IEEE Trans. Appl. Supercond. 15 2210–3
[10] van der Laan D C et al 2008 Supercond. Sci. Technol.
Even at this price level, HTS transformers may be competitive 21 115002–7
with conventional units in certain applications where their [11] Amemiya N et al 2004 Supercond. Sci. Technol. 17 1464–71
additional advantages are most important. As mentioned in [12] Duckworth R et al 2009 IEEE Trans. Appl. Supercond.
section 1, these include higher efficiency, greatly reduced fire 19 3327–31
and environmental hazards due to the lack of flammable oil, [13] Lee J et al 2009 IEEE Trans. Appl. Supercond. 19 3340–3
[14] Majoros M et al 2009 IEEE Trans. Appl. Supercond.
reduced weight and size, overload operation with no loss of 19 3352–5
life, and fault current limiting capability. [15] Funaki S et al 2009 IEEE Trans. Appl. Supercond. 19 3168–71
[16] Chen J et al 2009 IEEE Trans. Appl. Supercond. 19 3254–7
5. Summary [17] Pomar A et al 2009 IEEE Trans. Appl. Supercond. 19 3258–61
[18] Yoshida Y et al 2009 IEEE Trans. Appl. Supercond. 19 3262–5
The foregoing investigations show that for HTS transformers to [19] Wee S et al 2009 IEEE Trans. Appl. Supercond. 19 3266–9
be cost-competitive with conventional units, a conductor price [20] Haugan T et al 2009 IEEE Trans. Appl. Supercond. 19 3270–4
[21] Miura M et al 2009 IEEE Trans. Appl. Supercond. 19 3275–8
reduction to less than 5% of current levels is needed, as well
[22] Namba M et al 2009 IEEE Trans. Appl. Supercond. 19 3495–8
as a 50% reduction in current cryocooler costs. The minimum [23] Verebelyi D et al 2003 Supercond. Sci. Technol. 16 1158–61
YBCO-CC critical current in the windings must be above the [24] Rey C M et al 2009 IEEE Trans. Appl. Supercond. 19 2317–20
transformer’s peak current in overload operation. Conductor [25] See 2009 DOE Peer Review presentations at http://www.
should be available in custom widths to properly match the htspeerreview.com/agenda.html
[26] See American Superconductor site at http://www.amsc.com/
unit’s rated peak current. The conductor must operate in a
products/htswire/2GWireTechnology.html
maximum peak ac field of a few tenths of a tesla. Reduction [27] See SuperPower site at http://www.superpower-inc.com/
of ac losses would allow the transformer core to be lighter content/products