CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0514

POWER QUALITY LEVEL IN 110 KV NETWORKS IN THE CZECH REPUBLIC

Frantisek KYSNAR Karel PROCHAZKA Antonin HERMAN


EGC CB, s.r.o. – Czech republic EGC CB, s.r.o. – Czech republic EGC CB, s.r.o. – Czech republic
fkysnar@egc-cb.cz kprochazka@egc-cb.cz aherman@egc-cb.cz

the points of delivery between TS and DS were evaluated in


ABSTRACT a uniform way so that they could be mutually compared. A
tool for the evaluation was the system for PQ archiving and
The Distribution Code (DC) of the Czech Republic evaluation used by two of the three electricity distributors in
prescribes to all electricity distributors in the country to the Czech Republic (ČEZ Distribuce, a.s. and E.ON ČR,
monitor the parameters of electricity quality (PQ) at the s.r.o.). The data from the points of DS being evaluated were
points of delivery between the transmission system (TS) and provided in the form of data base graphics (7 areas out of 8
the distribution system (DS) on the 110 kV side. Class A areas), only one area provided the data in the form of txt
electricity quality analysers have been installed at these export. The total number of 62 points of delivery has been
points since 01.01.2006. The total number of 62 points of evaluated during this campaign since 2006.
delivery is equipped with this PQ monitoring now. Beside The results presented below are oriented on binding and
this whole-state PQ monitoring there has been also indicative characteristics of the voltage (voltage dips, swells
installed a regional PQ monitoring at MV level, namely in and interruptions). In order to prevent distortion of the
two regions of the Czech Republic. The paper deals with the evaluation, the weeks influenced by planned supply
results of one of them. interruptions were excluded from the evaluation. A separate
evaluation was elaborated for each point of delivery.
INTRODUCTION However, the presentation of these results exceeds the
A permanent PQ monitoring enables us to monitor the scope of this paper. Only summarizing results will be given
fluctuation of the level of characteristic voltage quantities here.
and of other monitored parameters in individual weeks Evaluation of binding voltage characteristics
during the year. Thanks to the monitoring at lower voltage
The results of the whole-state PQ evaluation at the points of
levels we can monitor even more detailed analyses in
delivery are illustrated by Fig. 1 – 3 showing the
relation to TR IEC 61000-3-6 and TR IEC 61000-3-7. In the
distribution of evaluated quantities for the year 2007.
case of flicker it is not only possible to process the Pst/Plt
Fig. 1 presents the distribution of the operated voltage level
ratios but also to assess the coefficients of the transfer of
for Umin95min and Umax95. It follows from this
flicker from 110 kV level into MV.
Fundamental information about the corresponding systems distribution that the operated voltage level is maintained
for the evaluation and archiving of the results of PQ very near to the upper limit of the permitted band of
measurements, also defined in DC, was presented in [1]. movement. Consequently, it happens not infrequently that
However, most distribution network operators (DNOs) go this permitted limit is exceeded.
over the obligation set by DC – the system for PQ archiving
and evaluation is interconnected with other utility systems,
e. g. SAP, GIS, SCADA, calculation system, etc. In the case
of interconnection with calculation systems these systems
are thus provided with information for making the
calculations more precise. The present structure of this
system of the major electricity distributor in the Czech
Republic is described in a separate chapter of this paper.
The sense of a whole-year monitoring of frequency in our
interconnected systems is also discussed. Regarding the
interval of aggregation, the matter concerns the parameter
with high demands on PQ measurement, archiving and
evaluation but with a minimum stating capability.
Figure 1
EVALUATION OF THE LEVEL OF
The distribution of the level of Pst and Plt can be seen in
ELECTRICITY QUALITY AT THE POINTS OF Fig. 2. It is evident from this distribution that there exist the
DELIVERY BETWEEN TS AND DS points of delivery between TS and DS which – by the
The measurements of the quality of electricity (PQ) from measured level of flicker – exceed the permitted values.
This is caused by the character of the dominant

CIRED2009 Session 2 Paper No 0514


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0514

consumption in the given 110 kV nodal area (ironworks,


etc.).

Figure 3

Figure 2
Evaluation of indicative voltage characteristics
Fig. 3 shows the distribution of THDu. As it follows from Events connected with a planned diverting of the supply of
this distribution, this quantity moves below the permitted DS into another point (electricity supply was not
limit value in most cases. interrupted) were excluded from the evaluation of indicative
The voltage unbalance moves very considerably below the voltage characteristics.
limit value at these points of DS. For that reason, its A summarizing evaluation of indicative voltage
distribution is not presented here. characteristics is given in the following Tables 1 – 3. Events
caused by the wind calamity at the beginning of the year
2007 were excluded from the evaluation.

Ur[%]/t[s] 0,01 0,1 0,2 0,5 1 3 20 60 180 Total Average


<=t< <=t< <=t<0,5 <=t< <=t< <=t< <=t< <=t< <=t
0,1 0,2 1 3 20 60 180
85<=Ur<90 280 26 7 8 2 0 0 0 0 323 7,30
70<=Ur<85 342 121 18 11 0 0 0 0 0 492 11,12
40<=Ur<70 139 83 13 4 0 1 0 0 0 240 5,43
5<=Ur<40 10 4 8 0 0 1 2 3 4 32 0,72
Total 771 234 46 23 2 2 2 3 4 1087 24,58
Average 17,43 5,29 1,04 0,52 0,05 0,05 0,05 0,07 0,09 24,58

Urest[%]/t[s] 0<=t<1 1<=t<60 60<=t Total Average


115<=Urest<120 43 5 9 57 1,29
120<=Urest<140 15 3 3 21 0,47
140<=Urest<160 4 0 1 5 0,11
160<=Urest<200 3 2 0 5 0,11
200<=Urest 0 1 0 1 0,02
Total 65 11 13 89 2,01
Average 1,47 0,25 0,29 2,01

Urest[%]/t[s] 0<=t<1 1<=t<180 180<=t Total Average


0<=Urest<5 19 13 85 117 2,65
Total 19 13 85 117 2,65
Average 0,43 0,29 1,92 2,65

CIRED2009 Session 2 Paper No 0514


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0514

Areas supplied from 220 kV and 400 kV networks were could appear in future.
compared during the processing of available data with The objective of this analysis was to inform individual
regard to recorded events. The comparison of 220 kV and DNOs about a possible future risk of payments for the
400 kV voltage levels revealed no principal difference. In supply of electricity outside the set limits for voltage
400/110 kV nodes the number of voltage dips is higher by magnitude.
1.3 (6% approximately), the number of voltage swells is Sums according to areas and voltage levels (220/110,
lower by 0.6 and the number of interruptions is lower by 1.3 400/110 kV) were calculated. So that the results could be
on the average. Recorded events at the points of delivery compared, average values for one point of delivery and the
with a higher operated value of the supply voltage included year (52 weeks) were assessed. The percentage of weeks
a great number of recorded events with voltage magnitude being evaluated during the year is given in column
in the range from 110% to 115%. However, the table for the “Utilization”. The coefficient for assessing the average
specification of frequency of occurrence of swells of the value was calculated as a reciprocal value of the product of
supply voltage starts to read up these events not until since the utilization and of the number of the points of delivery in
115%. Consequently, events recorded in the range from the given group (area, voltage level). Events caused by the
110% to 115% are not given in any frequency items of wind calamity at the beginning of the year 2007 are not
tables for the evaluation of events. excluded from this analysis.
As the matter concerns no small number of events, the The performed evaluation was distributed into individual
events exceeding 110% Un but not exceeding 115% Un regions of the Czech Republic.
were read up also for the reason that justified claims of
customers and requirements for financial compensations

Area 0<=t<1 1<=t<60 60<=t Total Utilization [%] Coefficient Average


Area 1 116 212 926 1254 66 0,152 190,1
Area 2 37 19 262 318 67 0,166 52,8
Area 3 21 4 137 162 77 0,162 26,2
Area 4 42 12 465 519 66 0,168 87,1
Area 5 2 2 3 7 50 0,331 2,3
Area 6 28 13 1203 1244 78 0,117 145,7
Area 7 6 0 1 7 87 0,230 1,6
Area 8 3326 0 0 3326 89 0,280 929,8
Total 220 kV 3340 47 965 4352 66 0,075 327,5
Total 400 kV 238 215 2032 2485 74 0,032 80,3
Total 3578 262 2997 6837 71 0,023 154,6

As can be seen, distribution networks supplied from the monitoring carried out in the Czech Republic is relatively
220 kV level are operated at the upper limit of the voltage extensive. That is the reason why no small requirements are
more frequently than networks supplied from 400 kV nodes. imposed on the system of archiving and evaluating the
The highest number of voltage swells in the category 110% quality of electricity, both from the side of users themselves
to 115% was recorded in Area 8. Their duration was up to 1 and from the side of cooperating systems which serve for
s in most cases. The risk of exceeding 110% Un is the securing a full functionality of the system for PQ archiving
greatest in Area 6, Area 1 and Area 4 where a high level of and evaluation or, on the contrary, they use routine analyses
the operated voltage is maintained permanently and some of provided by this archiving system for securing their own
voltage swells were longer than 1 minute. full functionality.
A detailed description of such a system exceeds the scope
SYSTEM FOR PQ ARCHIVING AND of this paper and, therefore, we shall point out only the main
EVALUATION interconnections realized in the concrete case.
It can be seen from the following Figure 4 that
At CIRED Conference in Vienna held in 2007 we already interconnection with SAP (PM module), GIS and with the
presented, in paper [1], a general scheme of the system for calculation system is realized at present. Interconnection
archiving and evaluating the electricity quality parameters with the control system is under preparation now. The
which has been laid down into DC the Czech Republic. In interconnection with SAP and GIS is an example of a
the present paper we would like to get you acquainted with mutual transferring of information where the information
a concrete practical application of this system by one of transferred from the archiving system into these systems is
major electricity distributors in our country. purely informative. On the other hand, the interconnection
As it is evident from the above-described analyses, the PQ between the archiving system and the calculation system

CIRED2009 Session 2 Paper No 0514


CIRED 20th International Conference on Electricity Distribution Prague, 8-11 June 2009

Paper 0514

serves only for the needs of the calculation system which provides information about the planned diverting of supply
uses the information from routine analyses of the archiving and/or information about planned and failure supply
system for making its own calculations more precise. interruptions with attention being paid to securing the
The interconnection with the SCADA system is very continuity of electricity distribution.
important for the archiving system itself. It is decisive for
choosing a supply point for the locality of measurement, it

Figure 4

the above-mentioned standard [2] – they are not significant.


MONITORING OF FREQUENCY
CONCLUSION
One of problems which had to be solved within the
realization of the system for PQ archiving and evaluation The paper presents the level of binding characteristic
was to choose a convenient algorithm for storing quantities of voltage quality in 110 kV networks in the
information about the development of frequency. There Czech Republic. But it is also devoted to a summarizing
were two reasons for this: to prevent overloading of the evaluation of indicative voltage characteristics (voltage
archiving system due to the extent of monitoring and to dips, swells and interruptions) including the analysis of
secure that this approach might be a full-value one for the impacts of calamity events. Frequencies of occurrence of
possible evaluation of frequency. these indicative voltage characteristics for the points of
The EN 50160 standard [2] prescribes the requirement to delivery supplied from 220 kV and 400 kV networks are
evaluate the frequency from 10 s RMS values with one year also compared.
as the interval of evaluation for the interconnected system. The paper deals with administration of huge amount of
This is also the case of the distribution system of the Czech collected measured data i.e. mode of processing, archiving
Republic. So as to prevent overloading of the data store and also its possible usage by other systems. It also includes
with a great quantity of intervals with a minimum stating block diagram presentation of using the system by one of
capability, the archiving system archives only the result of the main Czech distributors.
the statistics for individual weeks. A question remains
whether it is necessary to require such an interval of REFERENCES
evaluation when other voltage characteristics are evaluated
in relation to a weekly period of measurement. At this [1] Karel PROCHAZKA, Frantisek KYSNAR, 2007,
moment we consider the given problem from the point of Systems of measuring, evaluating, and archiving the
view of the permanent PQ monitoring at HV level. parameters of the power quality in the distribution systems
However, when considering this problem in connection with in the Czech Republic, Proceedings of CIRED 2007, Paper
lower voltage levels where the PQ monitoring is realized 0093
only within regular measuring campaigns or as a reaction to [2] EN 50160:2007 Voltage characteristics of
claims concerning the quality, then the yearly interval of the Electricity supplied by Public Distribution Systems
evaluation of frequency loses importance. The measured
values have only informative character and – with regard to

CIRED2009 Session 2 Paper No 0514