MODULE GIL BASICS 5. Two types of insulators are available. An open type
when free passage of gas is required and cone or
GAS INSULATED TRANSMISSION LINES - GIL disk insulators where one gas compartment is
isolated from another.
A. Introduction 6. GIL bus is much more flexible than GIS bus. Since
GIL bus has evolved differently than bus used in Gas Insu- the insulators are totally enclosed and mechanically
lated Substations. GIS stations are a compact arrangement of decoupled from the enclosure flanges, the bus can
circuit breakers, disconnects, earthing switches, voltage and bend to accommodate changes in direction or
current transformers etc. Usually connections between these support misalignment.
active elements are only a few meters in length. Since the re-
quired electrical shapes for enclosures are often complicated, 18 meters Open Insulator
castings are used extensively for both active components and
for the flanges used on interconnecting bus. A typical GIS
bus section and elbow is shown in figure II-1.
Fig. II-1. GIS Bus section. Bolted contacts and cast elbow. Barrier Insulator Particle trap
Fig. II-2. GIL design factory assembled sections. Particle traps used exten-
sively with two types of insulators. Field welded or bolted joints are used for
section assembly. Elbows are an integral part of the shipping assembly.
700
Enclosure (mm)
600
500
400
up to 500 m 300
200
100
50 100 150 200 250
Conductor (mm)
When circuit lengths is longer (about 500 meters) it is
often more economical to pre-assemble the components at
Fig. II-4. Relationship between enclosure and conductor diameters for
site then install in longer sections. Mixtures of SF6 and ln(r2/r1)= 1 (best use of the dielectric space)
Nitrogen can also be used to reduce the overall SF6 content of
the system. Based on the required BIL performance of the system you
The GIL is shipped to site in 12-18 meter lengths. Typi- first select the required conductor diameter. Required enclo-
cally, 10 sections are assembled using welded joints for both sure diameter is then selected based on the log ratio of 1.
the conductor and enclosure connections. Pre-fabricated 180
meter sections of up to 500 m are then installed in their final
position. Conductor plug and socket contacts are used only as 2500
necessary to compensate for thermal expansion. 2000
The welding is done using an automatic welding machine.
BIL (kV)
1500
This guarantees good weld quality and a leak tight seals.
1000
B. Design 500
The dielectric design of GIL is based on a simple formula 0
for the electric field in a coaxial geometry. The electrical 50 100 150 200 250
stress (E) at any given radial point (r) in the system is Conductor diameter (mm)
determined by:
U Fig. II-5. BIL performance for various conductor diameters. (Assumes the
E= most economical ratio of conductor to enclosure diameter)
r
r2 ln 2
Figure II-5 covers the entire range of transmission systems
r1
from 115 kV through 800 kV.
Where U is the applied voltage, r2 and r1 are the enclosure
The choice of insulating gas or gas mixture will determine
and conductor radii respectively.
the allowable system dielectric stress. Small amounts of SF6
The most economical use of materials occur when the
in a Nitrogen base has very beneficial effects on the
conductor stress is minimized. This occurs when ln(r2/r1) =1.
dielectric performance. For long circuit lengths, SF6/N2
Most GIL designs in use today are based on log ratios
mixtures offer an environmentally friendly and economical
close to unity. Determining the overall dimensions for a
approach. Figure II-6 shows that a modest 15% SF6 content
specific voltage class is simply a matter of determining the
will double the power frequency breakdown voltage over
allowable voltage stress on the conductor.
pure Nitrogen at the same gas pressure.
While pure SF6 still offers the best dielectric performance
at a given gas density, 10-20% SF6/N2 systems operating at a
modest increases of pressure can perform with equal
dielectric ratings [II-21, II-22, II-23, II-24, II-25, II-27, II-
28].
3
400 5 % SF6/N2
2500 A.. The GIL went into service in 1975 and has been in
kV
300 Pure N2
service without interruption ever since, to deliver peak
energy into the southwestern 420 kV network in Germany.
200
With 700 meters of system length running through a
100 tunnel in the mountain, this GIL is still the longest appli-
cation at this voltage level in the world. Today at voltage
0
0 100 200 300 400 500 600 700 800 levels from 135 to 800 kV about 200 kilometers are installed
Pressure (kPa)
worldwide. The applications vary from inside high voltage
Fig. II-6. 60 Hz breakdown results for a 145 kV Coaxial Geometry with substations, power generation plants, areas with severe envi-
Enclosure/Conductor Dimensions of 241.3/88.9 mm. ronmental conditions and to solve specific routing, right of
way or access problems.
Since GIL systems are usually designed based on the re-
quired dielectric performance, each system will have an
inherent current carrying capacity. The current carrying
capacity exceeds that of a single conventional cable circuit
and can be matched to the capacities of overhead lines.
Figure II-7 shows typical current ratings based on enclosure
diameters.
(kA)
8
6
4
2
0
100 200 300 400 500 600 700
Enclosure diameter (mm)
Fig. II-7. Ampacity- open air system without solar radiation as a function of
enclosure diameter.
Fig. II-9. Schluchsee Hydro Pump Storage Plant.
C. History of GIL design
The first Gas Insulated Transmission line installed in the Typical applications of GIL are links within power plants
US was at the PSEG Hudson Generating station in New to connect the high voltage transformer with the high voltage
Jersey in 1972. The 242 kV, 1600 amp system is rated 900 switchgear, within cavern power plants to connect high
kV BIL. The GIL is direct buried connecting the AIS voltage transformers in the cavern with the overhead line on
substation equipment to a transformer located remote from the outside, to connect gas-insulated substations (GIS) with
the substation. This installation is still energized and in use overhead lines or transformers, as a bus connecting
today. components within gas-insulated substations or as stand
alone installations of GIL for resolving specific
environmental, routing, access or right of way issues. Circuit
lengths can vary from 10 meters to kilometers in length. The
applications are carried out under all different climate
conditions from the low temperature in Canada to the high
ambient temperatures in Saudi Arabia or Singapore, or severe
conditions in Europe or in South Africa. The GIL
transmission system is independent from environmental
conditions because the complete high voltage system
including insulators is completely sealed inside the aluminum
enclosure.
Fig. II-8. 242 kV GIL being installed in the PSEG Hudson generating station.
New Jersey. 1972. View looking back from the SF6-Air bushings.
4
Fig. II-23. 2 GIL Circuits 420 kV 3150 Amps. Geneva Airport in Switzerland.
Fig. II-22. Backfill being added to the trench. Note the natural curvature of the The principles of the installation procedure used in Geneva is
GIL following the landscape contour. shown in Figure II-24.
Fig. II-27. 550 kV GIL crossing under two 242 kV transmission lines.
Fig. II-25. trench mounted 550 kV GIL. Field welded construction. GIL
transitions from a trench with steel grating covers to a concrete road crossing.
OHL GIL
550kV Flanged
550kV Welded
1.00
362kV Flanged
0.90
362kV Welded Fig. II-32. Magnetic fields for GIL in µT
Normalized cost
0.80
0.70
0.60
0.50
0.40
0 500 1000 1500 2000 2500 3000
3 phase Circuit length (meters)
Results of an internal arc of 63kA for 300 ms on a 420 kV GIL. There are no K. References
external effects. The system retains gas pressure and all arc byproducts are [II-1] H. Koch, A. Schuette: Gas-insulated Transmission Lines for high
contained within the enclosure. power transmission over long distances, EPSR, Hongkong, 12/97
[II-2] H. Koch: Underground gas-insulated cables show promise, Modern
Power Systems, London, 05/97
[II-3] G. Baer, A. Diessner, G. Luxa: 420 kV SF6-Insulated Tubular Bus
for the Wehr Pumped-Storage Plant, Electric Tests, IEEE
Transactions on Power Apparatus and Systems, Vol. PAS-95, No. 2
March/April 1976
[II-4] Henningsen, C. G.; Kaul, G.; Koch, H.; Schuette, A.; Plath, R:
Electrical and Mechanical Long-Time Behavior of Gas-Insulated
Transmission Lines, CIGRE 2000
[II-5] Koch, H. et al.: N2/SF6 gas-insulated line of a new GIL generation in
service, CIGRE Session 2002, Paris
[II-6] O. Völcker, H. Koch: Insulation co-ordination for gas-insulated
transmission lines (GIL), IEEE Transactions, to be published in 2000
[II-7] IEC 61640 "Rigid high-voltage, gas-insulated transmission lines for
rated voltages of 72.5 kV and above"
[II-8] U. Schichler, J. Gorablenkow, A. Diessner: UHF PD Detection in
GIS Substations During On-Site Testing, 8th Int. Conf. on Dielectric
Materials, Measurements and Application, Edinburgh, 2000, pp. 139-
144
[II-9] G. Schöffner, W. Boeck, R. Graf, A. Diessner: Attenuation of UHF
Signals in GIL, 12th Int. Symp. on High Voltage Eng., Bangalore,
2001, No.4-57, pp. 453-456
[II-10] A. Schuette: Gas-Insulated Transmission Lines, Siemens, Power
Engineering Guide, 1997
[II-11] IEC 60480 "Guide to the checking of sulphur hexafluoride (SF6)
taken from electrical equipment"
Fig. II-35. Result of an internal fault of 50 kA for 300 ms on an XLPE cable. [II-12] IEC 61634 "High-voltage switchgear and controlgear - Use and
There was a release of toxic gases and damage to adjacent cable circuits. handling of sulphur hexafluoride (SF6) in high-voltage switchgear
and controlgear"
The inherent safety of GIL allows it to be brought into [II-13] Cigre Working Group 23.02, Task Force 01: Guide for SF6 mixtures,
Cigre Brochure 163, 2000
street or railway tunnels, and on to bridges No flammable [II-14] L.G. Christophorou, L.R. van Brunt: SF6 - N2 Mixtures, IEEE Trans.
materials are used to build a GIL. This makes the use in Dielectr. Electr. Insul. 2 (5) 1995, pp. 952-1003
tunnels safer and more economical. [II-15] H. Knobloch: The Comparison of Arc-Extinguishing Capability of
Sulphur Hexafluoride (SF6) with Alternative Gases in High-Voltage
J. Conclusions Circuit Breakers, 8th Int. Symp. on Gaseous Dielectrics, Virginia
Beach, USA, 1998
GIL has a long and reliable history. The flexibility of the de-
signs allow it to be installed in a variety of locations.
12