Technical Support Department

Protec house, Churchill way, Nelson, Lancs. BB9 6RT. England.


Tel: (01282) 717444 e-mail : technical@protec.co.uk

Number 298
TO: ALL Service Engineers Ref: Techbul298
CC –Technical Support Department Date: 3rd Sept 2010

FROM: Gawin Davies

SUBJECT: X400 Operating system software Ver 6.19

X400 Operating System software Ver 6.19


Please be advised that the X400 ‘Operating system’ software has been enhanced from version
6.18 to version 6.19. This technical bulletin details the enhancements made to the software.

1.0 Fire operating system changes - Version 6.19


1. Download error 4000 - Download error 4000 generated if trying to run a 5000 loop card on
a PICless SSU.
2. Override output group – Issue with Override Output Group that was introduced at version
6.18, now rectified.
3. NBU - An95 NBU to use the correct panel number for status events now rectified.
4. Zone Disablement - Added En54-2 A1 changes including showing a zone disablement if all
devices in the zone are disabled individually.
5. Silence log –Potential of silence logo disappearing, now rectified.
6. Node test - re-instated for fault events (removed in V6.18).
7. 6000 Hush ZAI - processing modified to take account of the Hushed and Isolated events.
8. Device Graph - Fixed gaps in analogue value graph when 6000 OpHtCO re-appears after it
has been missing.
9. Device Graph - Fixed CO value on analogue value graph when 6000 OpHtCO device is
missing.
10. Device Graph - Restored value on analogue value graph for digital devices with a single
channel.
11. Class device isolate - Added class device isolate changes as standard
12. Missed event processing - Added Fire text to the missed event processing
13. Text requests - Added storage of fire and fault text on DCNs to reduce the number of text
requests

2.0 Software Updating Procedure

WARNING !
SOFTWARE UPGRADE PROCEDURE
Do NOT install this version without checking that all compatibility requirements have been met. This
version is NOT compatible with previous versions and will require a minimum software monitor
version 1.64. All RDNs, LCDs and Mimics will require version 3.38 or above.

Technical Bulletin No 298 Page 1 of 2


Technical Support Department
Protec house, Churchill way, Nelson, Lancs. BB9 6RT. England.
Tel: (01282) 717444 e-mail : technical@protec.co.uk

3.0 Software location


The Fire operating system software version 6.19, are now available on the “Engineers link” of
the Protec Fire Detection plc web site.

4.0 Compatible software table

Compatibility Guide Recommended Other suitable


Version Versions
Fire System
Fire Operating System 6.19 None
Prison System (GA)
General Alarm Operating System 6.19A None
Prison System (Cell Call)
Cell Call Operating System 6.19C None
WODU 3.38C None
An95 / X400 NBU System
NBU DCN Operating System 6.19N None
Monitor
Monitor EPROM for DCN mk2 1.64 None
Monitor EPROM for DCN mk1 1.64 None
Monitor Eprom for LPN 1.64 None
Monitor Eprom for PICless LPN 1.64 None
LCD / RDN
LCD / RDN 3.38 None
Nodefile
Nodefile 26 None
Loop driver Cards
6000 Series loop driver (Protec) 3.14 3.11+
5000 Series loop driver (Nittan) 8.17 1.02
4000 Series loop driver (Apollo) 1.01 None
Misc
Local IO Controller 3 2
LDU 9 6 to 8
X400 Commissioning software 4.23.6.8 None

Should you require any further technical advice regarding this subject, please contact a member
of the ‘Technical Support team’ on ext (01282) 717444, who will be pleased to provide you with
the necessary advice.