“OIL-LESS” SCROLL AIR WITH DESICCANT AIR TREATMENT

Furnish and install, where shown on the drawing a prefabricated oil-less scroll air with
desiccant air treatment system as manufactured by Amico Source.

AIR COMPRESSOR SYSTEM COMPRESSOR MOTOR


The medical air system must meet or exceed the requirements of NFPA 99. The package The motor shall be a continuous duty, 3600 RPM, TEFC NEMA construction motor.
shall include oil-less scroll air compressors and associated equipment, one ASME air
receiver and one control panel. The only field connections required will be system intake, COMPRESSOR ACCESORIES
exhaust and power connection at the control panel. All components shall be completely The system shall include individual compressor inline intake filter, discharge check valve,
pre-piped and pre-wired to single-point service connections. All interconnecting piping and safety relief valve, intake and discharge flexible connectors, isolation valve, air cooled
wiring shall be completed and operationally tested prior to shipment. Provide liquid tight after-cooler, high discharge temperature shut down switches on each discharge, pressure
conduit, fittings and junction boxes for all control and power wiring. control switches, as well as medical grade demand check valve for gauge and switches.

The system shall include individual compressor inline intake filters, discharge check valves DRYER / FILTER / REGULATOR SYSTEM
of bronze construction, safety relief valves, intake and discharge flexible connectors, An integral air treatment system with purge saving feature NFPA 99 compliant assembly
isolation valves, air cooled after coolers for each compressor, high discharge temperature featuring dual desiccant air dryers, dual pre-filters, after-filters, pressure regulator valves,
shut down switches, pressure control switches, as well as medical grade demand check dew point monitor, CO monitor and system safety valves. It is requires to meet and
valve for gauge and switches. The system shall include an air receiver of ASME exceed the current code requirements shall be completely pre-piped and pre-wired to
construction rated for 200 PSI MWP service. The air receiver shall be equipped with a single-point service connections.
pressure gauge, safety relief valve, 3 valve by-pass, water gauge and automatic electronic
tank drain with manual override. The inside of the tank shall be coated for rust protection. There shall be two identical banks of air treatment equipment, piped in parallel and
provided with valves to by-pass either bank for filter element replacement, maintenance
CONTROL PANEL and repair work while still treating medical compressed air through the other set. Each
The system shall include a UL listed control panel in a NEMA 12 enclosure with the bank consists of three stages of treatment. The first stage is a prime efficiency coalescer
following accessories for each pump: with filter differential gauge and electronic solenoid auto drain valve. The second stage is
a desiccant heatless air dryer, equipped with purge control. Pressure dew point of -40oF
Externally operable circuit breaker with door interlock, control circuit transformer with is attained by directing the flow of saturated compressed air. The dry compressed air is
fused primary and secondary circuits, H-O-A switch, magnetic starter with 3 leg overload discharged from the “on line” tower into the third stage. The third stage is a prime
protection, hour meter and motor running light. Provide audible and visual local alarm for efficiency particulate after-filter with differential manual drain. Downstream pressure
the following: compressor temperature malfunction and reserve compressor in use. regulators will maintain constant discharge pressure of 55 PSIG (field adjustable).
Provide manual reset for thermal malfunction shutdown. All control and alarm functions
shall remain energized while any compressor in the system remains electrically on-line. AIR RECEIVER
The lag compressor shall be able to start automatically if the lead compressor fails to The air receiver shall be of ASME construction. The receiver shall be rated for full
operate. Alarm contacts should be provided for remote annunciation for all alarm points. compressor service and shall be equipped with a gauge and manual valve drain. It should
be rated for a minimum of 200 PSIG design pressure.
AIR COMPRESSOR
The compressors will be belt driven oil-less rotary scroll, single stage, air-cooled STATEMENT OF WARRANTY
construction with absolutely no oil needed for operation. Each compressor will Be Amico Source warrants its Air Systems are to be free of defects in material and
equipped with isolation valve, check valve, safety valve, electric motor, belts, belt guard, workmanship under normal use for a period not to exceed thirty (30) months from date of
air cooled after cooler with separator, T.M.P.D. (Thermal malfunction protection device) shipment, or twenty four (24) months from date of start-up.
and serviceable bearings completely separate of air chamber extending compressor. The
pump shall have the capacity at 120 PSIG. The service of a factory trained representative shall be made available at the jobsite to
check installation, start-up and instruct operating personnel in the proper operation and
maintenance.