DORMA TL
DORMA TL
2 TL GB
DORMA TL Door Terminal
Key-operated switch-and-
contact system
for alarm acknowledgement
and system Illuminated red
arming/disarming emergency-open pushbutton
with positive release action
(to EN 60947-5-1)
Hinge mechanism
for easy installation
Control and
interface boards
for different installation
options
4 TL GB
DORMA TS
TL-G
93 Door Terminal
Gleitschienen-
Türschließersystem
Note
According to the “Guidelines
on electric locking systems
for doors used in emergency
exits and escape routes”
(EltVTR) issued by the
TL-UK German Institute for
Building Technology (DIBt),
Berlin, the emergency push-
button for release/emergency
TL-G opening of door must be not
be installed at a height of
more than 1200 mm above
TL-BR finished floor level. A height
of 850 mm is recommended.
ø 5,5
311
260
258
195
TL
45
850 - 1200 mm
34
45
48
33
90 85 63
83
6 TL GB
Specification text Order No.
TL-UK 113
Zinc-plated recess box for flush installation of the door
terminal, with attachment collars as wall anchors.
Adjustable baseplate for correction of vertical installation
tolerances. Prepared for cable entry at front and rear. 311
331
Dimensions (W x H x D): approx. 113 x 311 x 77 mm. 56510512 TL-UK
TL-BR
Trim, adjustable for adaptation to depth of installation. Dimen-
77
sions (W x H x D): approx. 130 x 331 x 4 mm. Surface finish:
0
13
Y TL-BR 08 yellow green fluorescent 56510408 TL-BR 4
Y TL-BR 11 white powder-coated (similar to RAL 9016) 56510411
Y TL-BR 04 stainless steel, ”Design“ finish 56510404
TL-Z 04
Spare lens for transparent cover of emergency pushbutton
TL-G 3xx/5xx. Breakable safety glass with protective film
Supplied in packs of 5 56510400 TL-Z04
TL-Z 03
Single Europrofile cylinder with 3 keys, with adjustable
locking cam (lever), suitable for use with DORMA TL-G, TE,
ST and lockable sheet steel enclosures for the RZ 12 N, 5
10,
NT 1224 N, SVP-S 25 (not suitable for master key or keyed 30
TL GB 7
DORMA TL-S8 Control and
Interface Board
X9
X7 R35
∞/3 min.
R36
S1 A B
S2 A B
S3 A B
X3 X1
X6
R54
X5 X8
X2
T 800mA
X3
F1
16 17 15 3 4 5 6 7 8 6 7 8 3 20
X2
X1 + - 2 5 4 1 3 18 41 42 26 27 41 42
3,3 kΩ
Recommended cabling
Power supply: NYM-I 3 x 1.5
System cabling: I-Y (ST) Y 4 x 2 x 0.6
RM RM
RZ 01 oder
NT 1224 oder
AS or BL RZ 01 AS or BL NT 1224 N (+ AP 3034)
230 V AC +/-10 %
230 V AC +/-10 %
or
or
24 V DC 0.5 A
by others 24 V DC 0.5 A
by others
TS TV TG/TE TS TV TG/TE
GMA/BMA GMA/BMA
PFS PFS
EMA
12 TL GB
Terminal assignment and functions
X2
16 C Floating (no-volt) contact responsive to hazard alert,
PFS 17 NC anti-tamper or fire alarm signals
15 NO (e.g. for video operation)
3 GND
4 + 24 V DC Message “Door locked and anti-tamper protected” (constant signal, LED red)
Message “Attempted door abuse/lever handle operated” (pulsed signal up to 10 sec.
after the event, LED flashing red)
TL GB 13
DORMA TL-S8 Control and
Interface Board
TL-S8
Control and interface board for operation in conjunction with
the RZ 01/NT 1224 power supply units or 24 V DC (+/– 10 %)
power supply source by others.
Designed for connection of max. two TV electro-mechanical
locking elements, ST key switch or access control system by
others, TG/TE monitoring and control unit, BL flashing lamp
or AS external alarm siren, hazard warning system (GMA)
and/or fire alarm system (BMA), or RM smoke detector
for activation via floating (no-volt) NC contact, and an
emergency escape lever handle or panic bar contact.
Emergency unlocking via floating (no-volt) PFS switching
output, also suitable for operation of CCTV etc.
Optional activation of the integral brief and permanent
disarming functions via key switch and contact control.
Integral and immediate automatic re-arming of system via
potentiometer (timing adjustable between 3 and 180
seconds at short timer following authorised passage; on
expiry of short timer setting, open door monitoring function
begins between 1 and 180 seconds; no delay on power
return after power failure). Variable audible alarms to signal
door opening time exceeded, attempted sabotage and door
abuse, emergency or panic alarm and fire alarm with optio-
nal local and/or central alarm trip. Automatic deactivation of
local alarm after 180 seconds. Integrated differential anti-
tamper circuit monitoring for short-circuiting or interruption
with floating output for connection to an intruder alarm
system (EMA). For installation in the DORMA TL-G door
terminal; push-on interface for the control and display
functions. Volume control, > 100 dB, with option of internal/
external oscillator for differentiated audible alarms.
Power supply: 24 V DC, +/– 10 % stabilised
Current consumption max.: approx. 140 mA
approx. 170 mA (alarm emission)
Contact rating: 24 V DC, 0.5 A inductive
1.0 A ohmic 56030080 TL-S8
DORMA ZM 104
Expansion module for interfacing the DORMA emergency
exit control system with DORMA SVP 3xxx/4xxx DORMA SVP
motor and switch-monitored emergency escape locks with
automatic locking action; for push-on fitting to DORMA
TL-S8 control and interface board. Allows passage by
authorised personnel by simple activation of the lock
cylinder, with automatic subsequent locking and activation
of the emergency exit control system after the door closes
and the deactivation period runs out.
With DORMA SVP 3xxx emergency escape motor locks,
remote release of door possible via TE 32/34 control panel
module connected to remote monitoring/control system or
via access control system.
Power supply data: 24 V DC, +/– 10 %
Current consumption max.: 20 mA 56910400 ZM104
14
TL GB
DORMA emergency Safety information
exit control system
DORMA emergency exit control systems have been developed If, during building occupancy, there is a constantly manned
and manufactured in accordance with the state of the art control centre with a direct view of the emergency escape
and generally recognised safety regulations. doors, the release operation can, instead, be performed from
The systems comply with German code of practice this position.
“Guidelines on electric locking systems for doors used in
The properties and characteristics of the fire and smoke
emergency exits and escape routes” (EltVTR, December
check doors (fire resistance time, smoke retention/sealing
1997 edition) published in bulletin 5/98 of the German
function and automatic closing action) must not be impaired
Institute for Building Technology (DIBt), Berlin, and also
by the installation of the electro-mechanical locking device.
draft standard prEN 13637. Their suitability has been verified
by the MPA NRW (Material Testing Authority) Dortmund and In Germany, modifications made to fire doors/barriers rendered
the VdS (Association of Property Insurers) Cologne. necessary for installation of the electro-mechanical locking
device, which go beyond the permissible modifications cited
The installer and owner/operator must ensure in bulletin 1/1996 of the DIBt, require general approval from
compliance with the following requirements as these the building inspectorate responsible and also individual
devices must not be allowed to prevent the unhindered approval from the local building authority. Similar regulations
escape of persons in the event of an emergency. apply in other countries and compliance with these is
mandatory.
Planning and installation The keys for the door terminal and emergency exit control
An emergency exit control system consists at least of the box must be kept secure. Keys for products not operating on
following components: Door terminal (TL-G and TL-S), protective low voltage may only be handed over to suitably
emergency escape control unit (RZ) and electro-mechanical qualified electricians.
locking element (TV).
15
TL GB
DORMA GmbH + Co. KG
Postfach 40 09
58247 Ennepetal
Germany
Tel. + 49 (0) 23 33/793-0
Fax + 49 (0) 23 33/79 34 95
www.dorma.com