~25 kv - - O O Attribution
OEMs use aramid papers which thermal index is 220℃
1)Safety and other insulation materials also have higher thermal
The VPI transformer has no flammable liquid or any index than required in 180℃ insulation system.
other liquid insulation materials, so that there is no Therefore actual insulation system can tolerate higher
pollution from leaks. High temperature insulation hottest temperature, which result in higher reliability of
materials and aramid paper that have high LOI(Limiting transformers. In addition, this transformer can provide
Oxygen Index) meaning less flammable are adopted as a additional capacity without shortening life span when
primary insulation material in windings. It has least solid peak load exceeds a rated capacity of transformer.
insulation materials among dry type transformers in core Transformer engineers should take into consideration
and coil assembly, which result in less smoke and flame. that insulation materials must be capable of withstanding
A fire behavior test(F1) with a VPI transformer shows the hottest temperature within the winding.
safety aspect in case of fire in terms of low temperature With respect to the life expectancy of transformers,
of smoke, low smoke level and minimum burn time after VDTs have been installed at nuclear power plants for
removal of flame during a fire behavior test based on class1E application (application related to the direct
IEC 60076-11. control of the nuclear reactors) that requires 40 years of
Followings are a summary of test result. life span and capabilities such as surviving steam line
breaks over the transformers, radiation exposure and
.the sample spec: 3phase, 1600 kVA, 10kV/430-233 V seismic events.
.Low levels of smoke (54.3% OTF vs. 20% limit)
.Low temperature of off gasses (maximum 290℃ 3)Environmental impact
vs.420K limit) The materials, processes, energy in transformer
.immediate fire extinction after removal of flame production have some impacts on the environment. This
.Lost weight 3.6 kg out of 618 kg after the test fact forces users to consider integrating environmental
Note) OTF(Optical Transmission factor) represents impact in selection, operation and disposal of trans -
volume of smoke during a fire behavior test. The higher formers when they evaluate and purchase them among
OTF means more light transmission and less smoke. several types of transformers . If we look at the VPI
transformer in light of environmental footprint, firstly it
2)Reliability consumes less silicon steel and copper or aluminum
The thermal classification of transformers represents the conductor due to it’s compact size and light weight,
highest temperature the electrical winding can accept which contributes for energy saving and green
while operating at the highest load condition (hot spot) environment. Production of steel, copper and aluminum
and should have insulating materials which at least entails expensive fossil fuel consumption resulting in air
match this rating. and water pollution. Secondly, all materials and
Highest temperature = average winding rise(K) + max. processes to build up VPI transformers have minimal
ambient + hot spot allowance impact to environment and the human body. Thirdly it
doesn’t require replacement of insulation oil to maintain
This means that the insulation system must be rated to transformers, which may cause environmental impact.
match the hottest temperature of the winding, not just the Lastly, when it comes to dispose transformers, salvage of
average winding temperature. active materials in VPI transformers is a lot easier than
other transformers because there is no insulation fluid
Table III Temperature class of insulation system based on and no thick and bulky resin layer around coils. It has
IEC60076-11 low volumes of insulation materials that eliminate the
Temp. Avg.wind. Max. Hot spot Hottest burden of disposal of large amount of resin and
class rise amb.al allowance temp. insulation fluid. Major insulation material of aramid
F 100 40 15 155 papers in VPI transformers can be disposed by burning
H 125 40 15 180 or burying. It does not emit toxicity to contaminate soil
220 150 40 30 220 and air (inert to the environment). Therefore aramid
papers can be recycled for fuel as an energy source,
which was certified by European cement plant operators.
But some studies in the United States indicate that the
hottest spot differential may be higher than projected in 4)Climatic and environmental behavior
the standard, depending on coil design and shape. VPI transformers have operated without any troubles
Potentially it is as much as 10 to 20 k higher than hot under harsh environment, which was also proved by
spot allowance stipulated by a standard. Harmonic numerous tests. Recently VPI transformer tests
loading also results in increased temperature of the conducted by CESI with IEC 60076-11 produced the
windings/hottest spot. These facts together require down- following results.
rating of the temperature class or up-rating of the
insulation materials. Otherwise, transformers may have a 1.Climatic test(C2)
premature failure due to insulation degradation in The transformer was placed in a test chamber in which
windings caused by excessive temperature rise above the ambient temperature was gradually decreased to –
hottest temperatures shown in Table III. Transformer 25℃ in 8 hours and this temperature was maintained for
12 hours. After the 12 hours have elapsed, a DC current operate without outage at high humid conditions. If a dry
equal to 2 times the rated current was circulated in the type transformer including a VPI or cast resin
high voltage coils until they reached the thermal steady transformer is energized after long storage period under
state (165℃ which is ambient temperature plus 125℃ high humidity, it is recommended either to wipe dirt and
/winding temperature rise of class H transformer). After moisture or to energize without loading before placing a
this test, coils should not have crack and pass dielectric load on transformer.
routine tests and partial discharge test. The summary of Under dust and dirt conditions(high pollution) rather than
test result is as follows. high humidity condition, VPI transformers have also
demonstrated it’s high performance, because the coil
-passed a separate source AC withstand voltage test at structure is well constructed to separate each disk, which
0.8 time of standard value for 60 seconds will not allow cumulative dust collection between disks.
-passed an induced voltage test at 0.8 times of standard Properly designed coils have also enough cooling space
value at 150HZ for 40 seconds in LV, gap between LV /HV and HV, to ensure effective
-passed a partial discharge test at 1.3 times rated voltage cooling even at harsh environments such as cement
(<1.5 PC vs. 50PC limit) plants and mines. One ASEAN power utility has
-passed verification of the energizing at 1.1 times rated operated several VDTs for more than 18 years without
voltage at 50HZ for 5 min (during the voltage application, any maintenance at all, though a thick layer of dust
no flashover occurred, visual inspection did not show covered the windings.
any serious tracking)
5)Short circuit withstand
If any air bubbles develop within windings, there will be Design principles utilized for VPI transformers minimize
high stress on the air and partial discharge will develop. axial and radial mechanical forces in case of short circuit
It may cause insulation breakdown resulting in accident. In addition, VPI process with resin enhances
transformer failure. The test result of partial discharge mechanical strength of coils with the disk structure in
proved that there was no air bubble inside a resin layer in HV coils that hold windings robustly. One recent short
the VPI transformer. circuit test with a VPI transformer conducted at KERI
In fact, VPI transformers have no concern with crack on (Korea Electrotechnology Research Institute) showed
high voltage or low voltage coils since resin layer on extraordinary test results. The transformer could
windings is very thin (less than 0.5mm thick). This withstand 4 seconds duration of short circuit current.
feature enable VPI transformers to fit the demand from This was first trial to apply a short circuit current beyond
customers who install transformers at places with highly 2 seconds which had applied to transformers mostly
fluctuating temperature. Even on assumption that it crack, based on IEC standard. The variation of % impedance
it does not cause a failure of winding due to reliable after short circuit test was about + 0.2% vs. 7.5%
insulation on conductors. This fact illustrates that VPI tolerance. This result proved that there was no
transformers are superior to the transformers that rely on deformation at all in HV/LV coils.
thick epoxy resin layer for dielectric strength which may
crack by temperature variation. 6)Overload capacity
Based on IEC 60076-11, the average winding rise is
2)Environmental test(E2) 125℃ and highest permissible hot spot temperature is
The transformer was placed in a test chamber in which 220℃ for class H. In this case, there is temperature
temperature and humidity are kept under control. The margin which is 30℃ differential between the highest
transformer was kept in air having a relative humidity hot spot temperature(220℃) of class H transformer and
above 93% for not less than 6 hours without being
the highest hot spot temperature(250℃) of class 220
energized, which ensure condensation on transformer.
insulation class that typical class H VPI transformers
After condensation, the transformer was in the climatic
adopt.
chamber for 144 hours. The temperature of the climatic
chamber shall be held at (50±3)℃ and relative
Table IV Highest permissible hotspot temperature of IEC
humidity held at (90±5)%. The summary of test result 60905
with the VPI transformer is as follows. Insulation Rated Highest Average Ambient
class hot spot permissible winding temp. for
-passed a separate source voltage withstand test at 0.8 temp.℃ hot spot temp.℃ insulation
time of standard value for 60 seconds temp.℃ life
-passed an induced voltage test at 0.8 times of standard
155(F) 145 190 100 20
value at 150HZ for 40 seconds
180(H) 175 220 125 20
(during the voltage application, no flashover occurred,
220 210 250 150 20
visual inspection did not show any serious tracking)
Note) Ambient temperature for insulation life calculation
This test had proved that windings were well protected is 20℃.
against harsh environments such as moisture and dust by
VPI processing. Many tests and historical cases at This contributes to higher overloading capability or
operation sites have proved that VDTs were safe to additional capacity over the rated capacity. For certain
cases, one can put dual ratings on the name plate for Figure II Loss evaluation comparison among dry type
flexible operation either with lower load loss or higher transformers
capacity. When we refer to ANSI standard that provides a
guidance of steady state loading on the basis of test
temperature rise, users can calculate the additional
capacity of dry type transformers without compromising
life span. For instance, if one 1000KVA VPI transformer
has 100℃ test temperature rise, the additional rating can
be calculated with Table V.