Certificate No, 06359/CODBAN Seesareee
‘ertficate No.
Date: September 1, 2020 SUCOFINDO
Issuing Office:
Jl. Urip Sumoharjo No. 90 A, Makaser 90232, Indonesia
‘Phonaacs: +8211 451600481706
Email makassar@sveatndo co
REPORT OF ANALYSIS
PRINCIPAL : PT. PERTAMINA (Persero)
Fuel Terminal Poso
TYPE OF SAMPLE Waste Water
TESTED FOR PH, Oil & Grease and TOC
DESCRIPTION OF SAMPLE Form : Liquid
Volume :£600 ml
Packing : Plastic Bottle
DATE RECEIVED : 24/08/2020
DATE OF ANALYZED : 24/08/2020 to 28/08/2020
SAMPLE MARK + Inlet Oil Catcher (S: 01° 23' 43.9" E: 120° 43° 02.6")
(Sample August)
Result:
Parameter Unit Result Method #)
pH : 6.90 4500-H" B
Oil & Grease mit <27 ‘SNI6989,10:2011
ToC mg/l 39.2 NI 06-6989.28:2005
‘#) Standard Method 23° Edition, 2017, APHA-AWWA-WEF
THE RESULT OF TESTING ANALYSIS ONLY REFERS TO THE SAMPLE SUBMITTED AS THE
SAMPLE WAS NOT TAKEN BY PT SUCOFINDO,
“Ts Cereatrport issued under our General Tem end Conditions, copy of which i avalabl von request or maybe aczessad at ww suet 016
Dept.-of Ins}
tion & Testing
7301032000863 Achmad
3619128
SCI-2007ACertificate No. 06360/CODBAN quseenon
‘ertificate No.
Date: September 1, 2020 NWA
; 4 SUCOFINDO
Issuing Ofc:
J Uri Sumoharo No. 80 A, Makasar £0232, Indonesia
Phone/Facs: +82 411 4516901451796
Email: mekassar@sucofindo.co.id
REPORT OF ANALYSIS
PRINCIPAL PT. PERTAMINA (Persero)
Fuel Terminal Poso
TYPE OF SAMPLE Waste Water
TESTED FOR pH, Oil & Grease and TOC
(KepMen LH No. 04.28.12 Tahun 2014)
DESCRIPTION OF SAMPLE Form : Liquid
Volume :£600 ml
Packing + Plastic Bottle
DATE RECEIVED : 24108/2020
DATE OF ANALYZED 24/08/2020 to 28/08/2020
SAMPLE MARK : 1, Outlet Oil Catcher 1 (S: 01° 23' 43.4" E: 120° 43' 02.6")
2, Sumur Pantau No. 4 (S: 01° 23° 44,7" E: 120° 43' 04.0")
(Sample August)
Result
Parameter Unit fi 5 ‘Treshold Limit Method
pH - 7.40 7.40 6.0-9.0 4500-4" B #)
Oil & Grease git <27 <27 25 SNI6989.10:2011
TOC’ g/t 3.45 <0.67 110 ‘SNI 06-6989.28:2005,
+#) Standard Method 23° Eaton, 2017, APHA-AWWA-WEF
THE RESULT OF TESTING ANALYSIS ONLY REFERS TO THE SAMPLE SUBMITTED AS THE
SAMPLE WAS NOT TAKEN BY PT SUCOFINDO,
This Cercaleopot is isued urder or General Tem end Contin, copy of whichis avalible upon requestor may te accessed at www succndaco.s
Dept. of inspectiory& Testing
7301032000863 Achmad
(mv
3619129
SC1-2007ACertificate No. 06361/CODBAN
Date: September 1, 2020
Ges
SUCOFINDO
Issuing Offa:
J. Usip Sumoharjo No. 90,8, Makasar 80232, Indonesia
Phone/Facs: +82 411 451800/451795
Email: makassar@sucofindo.coid
REPORT OF ANALYSIS
PRINCIPAL PT. PERTAMINA (Persero)
Fuel Terminal Poso
TYPE OF SAMPLE Waste Water
TESTED FOR Physical & Chemical
(Permen LHK No. 68/2016, Limbah Cair Kegiatan Domestik)
DESCRIPTION OF SAMPLE Form : Liquid
Volume £600 mi
Packing : Plastic Bottle
DATE RECEIVED 24/08/2020
DATE OF ANALYZED 24/08/2020 to 28/08/2020
SAMPLE MARK Inlet Air Limbah Domestik
(Sample August)
Result:
Parameters Units Its ‘Treshold Limit Method
Physical
Total Suspended Solid, TSS mgt 2 30 2540 D #)
Chemical :
PH “i 7.22 6.0-9.0 4500-H"B #)
cop mg/L <1,09 100 SNI 6989.2:2019
BOD mg/L 0.88 30. 5210 B #)
Oil & Grease mg/L 3.2 5 5520 C #)
Ammonia, NH3-N- mg/L 0.56 10 4500-NH3-C
Total Coliform Quantity/100mL 250 3000 SNI 01-2332.1-2006
TOC mg/L 43.1 110° ‘SNI 06-6989.28:2005
“) Permen LH No. 19 Tahun 2010
#) Standard Method 23” Ealtion, 2017, APHA-AWWA-WEF
THE RESULT OF TESTING ANALYSIS ONLY REFERS TO THE SAMPLE SUBMITTED AS THE
SAMPLE WAS NOT TAKEN BY PT SUCOFINDO,
‘This Cerficarepo issued under our Generel Tes and Conditions, copy of wii avalab pen request or maybe accessed at ww suotndo oid
7301032000863
3619130
SCI-2007A
Dept. of Inspection & Testing
‘AchmadCertificate No. 06362/CODBAN
Date: September 1, 2020
SUCOFINDO:
Issuing Offce:
J Urip Sumoharo No. 90 A, Makasar 60232, Indonesia.
Phonelacs: +82 411 451890/451795
Email: makassar@sucofindo.co.id
REPORT OF ANALYSIS.
PRINCIPAL PT, PERTAMINA (Persero)
Fuel Terminal Poso
TYPE OF SAMPLE Waste Water
TESTED FOR Physical & Chemical
(Permen LHK No. 68/2016, Limbah Cair Kegiatan Domestik)
DESCRIPTION OF SAMPLE Form Liquid
Volume £600mi
Packing Plastic Bottle
DATE RECEIVED 2410812020
DATE OF ANALYZED 24/08/2020 to 28/08/2020
SAMPLE MARK Outlet Air Limbah Domestik
(Sample August)
Result:
Parameters Units Results | Treshold Limit Method
Physical
Total Suspended Solid, TSS mgt 6 30 25400 #)
Chemical :
pH - 7.78 6.0- 9.0 4500-H"B #)
cop mf <1.09 100) ‘SNI 6980.2:2019
BOD. mf 0.98 30 5210.8 #)
Oil & Grease mg/l 27 5 5520 C #)
“Ammonia, NH3-N mg 0.56 10 “4500-NHs-C
Total Coliform Quantity! 00m 350 3000 SNI01-2332.1-2006
TOC molt <067 110" 'SNI 06-6989,.28:2005,
») Permen LH No. 19 Tajun 2070
+#) Standard Method 23° Edition, 2017, APHA-AWWA-WEF
THE RESULT OF TESTING ANALYSIS ONLY REFERS TO THE SAMPLE SUBMITTED AS THE
‘SAMPLE WAS NOT TAKEN BY PT SUCOFINDO,
‘This Cericarepot is ssed under ou Generel Tem and Condon, copy of wich avaable upon request or maybe accessed al www svctndo cod
7301032000863
19131
8CI-2007A
Dept. of Inspection § Testing
ef
Achmad