4.1 Factory testing
All individual components are factory tested before
-150
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
kV
0
= ~
100
to ensure that the interface to MACH 2TM was
50 identical to the real system. A model of the HVDC
Light was also set up in order to get a complete
kV
-50
1.2
0.2
0
5 10 15 20 25
Harmonic order
0.5
0.4
system. 0.3
station.
• High voltage dc energization.
Figure 9 Harmonic motor voltage and current
• Operation without motor.
• Spin test. The harmonics were measured as part of the
• Commissioning of complete compressor commissioning and proved to be well below the
train. design criteria. Above are two curves showing
A special operation mode used during voltages and currents harmonic content for a typical
commissioning was developed to enable operation normal operating mode.
of the converters and dc cable without connecting
One can observe that dominant harmonic is 5th in operation is that the system work as expected where
motor current and 7th in motor voltage. This is due especially the new technologies have worked
to that the voltage harmonic generation from the extremely well and the problems that were
converter and motor are in phase for the 7th encountered, and corrected, were all related to
harmonic while they are in opposite phase for 5th. interface issues. The important lesson learned is
that extensive qualification programs and testing
5 First year in operation both factory testing and on site commissioning is
The electrical drive system that Statoil and ABB the key if new technology should be successfully
have developed has operated according to all introduced.
expectations. Some modifications have been
implemented after commissioning. These
modifications relate to situations regarding:
• Platform black-out
• Emergency or process shut down and start
up
• Alarm presentations to the operators
The wide field of state-of-the-art equipment and Figure 10 Troll A with two electrical drives installed.
control systems required an extensive training
programme. This was prepared by Statoil, together Foto: Dag Myrestrand, Statoil
with ABB, both in Sweden and Norway. Dedicated The technology using HVDC Light now makes it
training was later carried out for operators and possible to supply electric power from shore to
maintenance teams at Kollsnes and Troll A. Still, offshore installations.
continued training will always be a field of
necessity, where adapted competence should be Using a HVDC Light transmission system as a long
given to selected, small groups. This should be a distance electrical drive system and adapting it to
continued activity. special requirements arising from offshore gas
production has shown to be possible.
Based on experiences and statements from Statoil’s
onshore/offshore operators and discipline 9. References
specialists the EDS’ have performed exceptionally [1] Hörle N, Eriksson K, Maeland A, Nestli T:
well from day 1 with no shutdowns of the EDS Electrical supply for offshore installations made
system after ½ year of operation. The new motor possible by use of VSC technology.
drives, developed from the state-of-the-art network [2] Hyttinen M, Lamell J-O, Nestli T; New
systems with HVDC Light / Motorformer application of voltage source converter (VSC)
technology, has proved to gratify even the HVDC to be installed on the gas platform Troll A.
pessimists. [3] Asplund, Eriksson, Jiang, Lindberg, Pålsson,
Svensson: DC transmission based on voltage source
6. Conclusions converters, Cigré SC14 Session, Paris,
Voltage source converter (HVDC Light) and cable [4] M. Leijon et al., “Breaking conventions in
wound Motorformer are novel technologies, which electrical power plants”, in CIGRE Session Report,
have been designed to operate as an electric drive 11/37-03, Paris, 30 August - 5 September, 1998.
system, have been installed, commissioned and [5] M. Leijon, “Powerformer - A radically new
operated on the offshore platform in Troll. The rotating machine”, ABB Review, no. 2, 1998, pp.
conclusion from commissioning and first year in 21-26.