Anda di halaman 1dari 9

FIRE PROTECTION ENGINEERS

EDJ 250/7
EXCEL SERIES

FIRE PUMP SUBMITTAL

SAUDI FACTORY FOR FIRE EQUIPMENT.


P.O. Box 4441, Riyadh 14334, K.S.A.
Tel. No. 966-1-265 0070, Fax No. 966-1-265 21 90,
E-mail : riyadh@sffeco.com.sa, website : www.sffeco.com
SAUDI FACTORY FOR FIRE EQUIPMENT Co.

SECTION 1

DESCRIPTION
Fire Pump Division

SFFECO FIRE PUMPS

PRODUCT : EDJ 250/7

DESCRIPTION :

The SFFECO EDJ 250/7 Excel Series is a package type fire pump consisting of an electric
motor-driven duty pump, diesel engine-driven standby pump, jockey pump, combined
controller , mounted in a common base plate. Nominal performance rating is 250 GPM @ 7
BAR. The package is complete with discharge valves, and accessories.

DUTY PUMP DETAIL :

Brand : G-MAX Pumps


Model : GHS 850/500/200
Type : Horizontal-End Suction
Rated Flow : 250 GPM
Rated Head : 7 BAR
Impeller Size : 200 mm
Suction/Discharge : 65mm/50mm

MOTOR DETAIL :

Brand : HITEC,
Series/Model : HM 180 M-3
Rated Speed : 3500 RPM
Performance Rating : 30 Hp / 3 Ph / 60 Hz - 220 /380 Vac

STANDBY PUMP DETAIL:

Brand : G-MAX Pumps


Model : GHR 650/500/260
Type : Horizontal-End Suction
Rated Flow : 250 GPM
Rated Head : 7 BAR
Impeller Size : 245 mm
Suction/Discharge : 65mm/50mm

ENGINE DETAIL :

Brand : MEGAFORCE,
Series/Model : MFS-25
Power : 25 HP
Rated Speed : 2900 RPM
Cooling System : Radiator

Saudi Factory for Fire Equipment Co.


P .O. Box 4441, Riyadh 14334, K.S.A.; Tel. No. 966-1-265-0070; Fax No. 966-1-265-2190
Visit www.sffeco.com
Fire Pump Division

SFFECO FIRE PUMPS

PRODUCT : EDJ 250/7

JOCKEY PUMP DETAIL:

Brand : G -MAX Pumps


Series/Model : GVS4-60
Rated Flow : 15 GPM
Rated Head 7 BAR
Horsepower : 3HP
Motor Detail : 220 / 380Vac / 3 Ph / 60 Hz / 3500 Rpm
Suction/Discharge : 32 mm

CONTROLLER DETAIL:

Make : SFFECO, K.S.A.


Model : Type A
Operation : Combined Automatic and Manual
Enclosure : General Purpose
Mounting : Pump chassis mounted
Method of Start : DOL
Means of Activation : Pressure Switch, Selector Switch
Power Supply Detail : 380 Vac, 60 Hz, 3 Ph, 12Vdc

SYSTEM VALVES & ACCESSORIES DETAIL:

Gate Valves : 2.5" dia., flanged, LIFECO


Check Valves : 2.5" dia., flanged, LIFECO
Rubber Expansion Joints : 2.5" dia., flanged, LIFECO
Header Pipe : 4" dia., Black Steel
Pressure Switches : Range 1-20 Bar (15-290 Psig), ALCO
Pressure Gauge : 2" dial, range 0 - 400 Psi, LIFECO

Saudi Factory for Fire Equipment Co.


P.O. Box4441, Riyadh 14334, K.S.A.; Tel. No. 966-1-265-0070; Fax No. 966-1-265-2190
Visit www.sffeco.com
SAUDI FACTORY FOR FIRE EQUIPMENT Co.

SECTION 2

THE PUMP

FIRE PROTECTION CONTRACTOR


ISO 9001 COMPANY
Stainless Steel Centrifugal Pumps
To avoid cavitation, make sure that there is a Electrical Data
minimum pressure on the suction side of the
pump. The maximum suction lift "H" in Mounting Up to 4kW: V18
meters head can be calculated as follows Designation From 5.5 kW: V1
Insulation Class F
H = Pb X 10.2 - NPSH - Hf - Hv - Hs Efficiency class Eff.2
Eff.1 - on request
Pb = Barometric pressure in bar.
(Barometric pressure can be set to Enclosure class IP 55
1 bar.) In closed systems, Pb indicates IP 44 & IP 54 - on request
the system pressure in bar. 50Hz 3 x 200 - 220 / 346 - 380V,±10%
standard voltages 3 x 220 - 240 / 380 - 415V.
3 x 380 - 415 ∆V
NPSH = Net Positive Suction Head in meters
1 x 220-230 / 240 V
head.
(To be read from the NPSH curve at 60Hz 3 x 460 / 220 V.
the highest flow the pump will be standard voltages
delivering.)

Hf = Friction loss in suction pipe in meters Motor protection


head.
(At the highest flow the pump will Single phase motors have a built in thermal
be delivering). overload switch
Three phase motors must be connected to a
motor starter in accordance with local
Hv = Vapor pressure in meters head.
regulations
(To be read from the vapor pressure
Three phase motors from 3 kW and upwards
scale. “Hv” depends on the liquid
have a built-in thermostat (PTC) according to
temperature "Tm")
DIN 44 082.

Hs = Safety margin = minimum 0.5 meters


head.
Ambient temperature
(To be read from the vapor pressure
scale. Maximum +40˚C
“Hv” depends on the liquid If the ambient temperature exceeds +40˚C or
temperature “Tm”) if the motor is located 1000 meters above
sea level, the motor output (P2) must be
reduced due to the low density and
If the "H" calculated is positive, the pump can
consequently low cooling effect of the air. In
operate at a suction lift of maximum "H"
such cases, it may be necessary to use a
meters head.
motor with a higher output.

If the "H" calculated is negative, an inlet


pressure of minimum "H" meters head is P2

required. [%]

100

90

c. Motor 80

70

The motor is totally enclosed, fan-cooled, 2- 60

pole with principal dimensions in accordance 50

with the EN standards 20 25 30 35 40 45 50 55 60 65 70 75 80


t[˚C]
1000 2250 3500 m
Electrical tolerances according to EN 60034