Complete Network Power Products

for Business-Critical Continuity™

2008~2009 Catalog
6
2 8
3
5
11
2 7

9 9 4
4
5 1
Grid-to-chip protection for your critical investments
No other organization can match the
scope of Emerson Network Power’s
product offerings and service
reach, nor provide such complete
grid-to-chip protection to ensure
Business-Critical Continuity™
for your technology
investment.

Services
Emerson Network Power supports
these Centers of Expertise with the
largest global services organization in the
industry, delivering:
– Design, installation and startup
– Warranty service
1 – Preventive maintenance

2 – 24x7 remote monitoring


2 – Emergency service
– Site audits

1
11
6

10
10

11
9 5
8
3
6
Contents
A Full Spectrum of Products of Emerson
Network Power

DC POWER 1

OUTSIDE PLANT 16

AC POWER 23

RACKS & INTEGRATED CABINETS 41

PRECISION COOLING 43

MONITORING 48

EMBEDDED POWER 54
EMERSON NETWORK POWER.

THE GLOBAL LEADER IN ENABLING


BUSINESS-CRITICAL CONTINUITY.™

AC POWER

CONNECTIVITY

DC POWER

EMBEDDED COMPUTING

EMBEDDED POWER

DC POWER

MONITORING

OUTSIDE PLANT

POWER SWITCHING
& CONTROLS

PRECISION COOLING

RACKS & INTEGRATED


CABINETS

SERVICES

SURGE PROTECTION

Supporting voice and communications networks with

dependable DC power solutions. We’ve built on trusted

names-lorain®,Actura and PS-to create NetSure™

DCPower Solutions,the next-generation global technology

platform that delivers the most rigorous network-power

applications,with an unparalleled breadth DC power,

distribution,control and monitoring systems.

DC Power. Yet another way Emerson Network Power

enables Business-Critical Continuity™.

1
DC Power System

DC Power System
Configuration Matrix
Large system Medium System Medium System Small System

NetSure 801 PS48600-3/2900-X5 PS48250-1A/2900 PS48250-1B/2900 PS48250-1C/2900 PS48165/3200


Max. Power 348kW 34.8kW 14.5kW 14.5kW 14.5kW 9.6kW
Voltage -48V -48V -48V -48V -48V -48V
Max. Current 6000A 600A 250A 250A 250A 165A
Max. Number of Rectifiers 60 12 5 5 5 3
Rectifier Type R48-5800 R48-2900 R48-2900 R48-2900 R48-2900 R48-3200,R48-2900
Controller Type M810G M500F M501D M501D M501D M501D
600×600×1600
Dimension Multi-cabinet system 600×600×2000 600×600×2000 600×400×2000 600×400×700
or 584×327×132

Medium System Medium System Small System Small System Medium System

PS48360/1800 PS48300/1800-X6 PS48120/1800-X6 PS4875/25 PS24600/75 PSC48150/25


Max. Power 20.88kW 17.4kW 6.96kW 4.35kW 17.4kW 7.2kW
Voltage -48V -48V -48V -48V +24V -48V
Max. Current 360A 300A 120A 75A 600A 150A
Max. Number of Rectifiers 12 10 4 3 8 6
Rectifier Type R48-1800 R48-1800 R48-1800 HD4825-3 HD2475-2 C24/48-1200
Controller Type M501D M501D M501D PSM-A10 PSM-A11
Dimension 600×600×2000 600×600×1600 600×600×2000 450×260×700 600×600×2000 200×400×1460

2
Business-Critical Continuity™

NetSure 801
Stand-alone DC Power Series
-48VDC
up to 348kW

R48-5800

Applications
 Large and medium switching office
 Level-1 transmission backbone line
 GSM mobile switching office, mobile tandem exchange
 CDMA mobile switching office, mobile tandem exchange M810G
 DC Internet data center

System features
 Space saving, 116kW(2000A@58V) capacity one cabinet
 Capacity expandable up to 348kW(6000A@58V)
 Three-phase rectifiers (R48-5800) and SCU+(M810G) inside
 Wide AC input range, 260V to 530Vac, up to 600Vac endurance without damage
 System Efficiency high up to 93%
 Power factor high up to 0.99
 Output current Walk-in available
 Rectifiers and controller hot swappable
 Front access
 Top or bottom cabling
 Surge protection on AC, DC and signal side
 Modularized design for system and function unit
 TCP/IP, SNMP, web browser support
 Rectifier CE/UL approved
 Compliance with EN60590 and EN300386, ROHS
 Patented energy-saving mode

3
DC Power System

Affiliated Cabinet
AC distribution cabinet

Features
 Local large LCD display
 Dual mains auto/manual switchover
 Front access, Top / bottom cabling
 DC emergency lighting available
 Expandable up to f ive AC cabinets
 Lightning proof and electric Compliance with IEC
 ROHS Compatible

AC distribution cabinet

DC distribution cabinet

Features
 Independent monitoring unit for decentralized supply
 Local large LCD display
 Front access, Top / bottom cabling
 DC emergency lighting available
 Expandable up to 8 DC cabinets
 Lightning proof and electric Compliance with IEC
 ROHS Compatible

DC distribution cabinet

4
Business-Critical Continuity™

PD48/2000HF
High Ohmic Power Distribution Cabinet

Features
 Up to 120 branches high/low ohmic output
 Local large LCD display
 Front access
 Lightning proof and electric Compliance with IEC
 ROHS Compatible

PD48/2000HF

PD48/1200BFH
Integrated AC/DC Distribution Cabinet

Features
 AC.DC distribution unit in one cabinet
 Space saving
 Local large LCD display
 Dual mains auto/manual switchover
 Front access
 Lightning proof and electric Compliance with IEC
 ROHS Compatible

Dimensions And Weight


Cabinet Cabinet / module capacity W×D×H, mm Weight (kg)
Rack1000-6 Cabinet 1000A 600×600×2000 140(exclude rectifier)
Rectifier Rack
Rack2000-6 Cabinet 2000A 600×600×2000 180(exclude rectifier)
PD380/400AFH-6/X1 400A 800×600×2000 240
AC Cabinet PD380/630AFH-6/X1 630A 800×600×2000 240 Manual switchover
PD380/630AFA 630A 800×600×2000 250 Automatic switchover
PD48/1600DF-6/X1 1600A 800×600×2000 280
DC Cabinet
PD48/2500DF-6/X1 2500A 800×600×2000 290 PD48/1200BFH
DC High Ohmic
PD48/2000HF 2000A 800×600×2000 320
Distribution Cabinet
Integrated AC/DC
PD48/1200BFH 1200A 800×600×2000 320
Distribution Cabinet
Rectifier R48-5800 5800W 244×372×88 7.8
Controller M810G / 243.5×161×88 2


DC Power System

PS48600-3/2900-X5
Integrative DC Power Series
-48VDC
up to 34.8kW

Applications
 2G, 3G mobile base stations
 Medium exchanges, rural telecom networks and access networks
PS48600-3/2900-X5
 Transmission relay stations
 Microwave/satellite communications stations

Features
 Capacity up to 34.8kW (600A @ 58V)
 Rectifiers R48-2900(2900W)and SCU inside
 Wide input voltage range (85 to 290Vac), up to 415Vac endurance without damage
 Efficiency high up to 93%
 Power factor high up to 0.99
 Output current Walk-in available
R48-2900  Patented energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Rectifiers and controller hot swappable
 Front access
 Top or bottom cabling
 Rectifier CE/UL approval
 Compliance with RoHS

M500F Dimensions And Weight


model W×D×H, mm Weight (kg)
Cabinet PS48600-3/2900-X5 600×600×2000 140(rectifier excluded)
Rectifier R48-2900 85.5×287×132.5 3.5
Controller M500F

6
Business-Critical Continuity™

PS48250-1A/2900
PS48250-1B/2900
PS48250-1C/2900
(ACTURA Flex 48330)
Integrative DC Power Series
-48VDC
up to 14.5kW

Applications
 2G, 3G mobile base stations
 Medium exchanges, rural telecom networks and access networks
PS48250-1A/2900
 Transmission relay stations
 Microwave/satellite communications stations

Features
 Capacity up to 14.5kW (250A @ 58V)
 Rectifiers R48-2900(2900W)and SCU inside
 Super flexible configuration
 Wide input voltage range (85 to 290Vac), up to 415Vac endurance without damage
 Efficiency high up to 93%
 Power factor high up to 0.99
 Output current Walk-in available
 Patented energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side PS48250-1B/2900
 Rectifiers and controller hot swappable
 Front access
 Top cabling
 Inner 660Ah battery shelves optional
 Rectifier CE/UL approval
 Compliance with RoHS

Dimensions And Weight PS48250-1C/2900


model W×D×H, mm Weight (kg)
PS48250-1A/2900 600×600×2000 135(rectifier excluded)
Cabinet PS48250-1B/2900 600×400×2000 125(rectifier excluded)
PS48250-1C/2900 600×400×700 60 (rectifier excluded)
Rectifier R48-2900 85.5×287×132.5 3.5
Controller M500F

7
DC Power System

PS48165/3200
(ACTURA OPTIMA 48200)
Integrative DC Power Series
-48VDC
up to 9.6kW

Applications
 2G, 3G mobile base stations
 Medium exchanges, rural telecom networks and access networks
 Transmission relay stations
 Microwave/satellite communications stations
PS48165/3200 mode1

Features
 Capacity up to 9.6kW (165A @ 58V)
 Rectifiers R48-3200(3200W)and SCU inside
 Wide input voltage range (85 to 290Vac), up to 415Vac endurance without damage
 Efficiency high up to 93%
 Power factor high up to 0.99
 Output current Walk-in available
 Patented energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Rectifiers and controller hot swappable
PS48165/3200 mode2  Top cabling
 Inner dual battery shelves optional
 Rectifier CE/UL approval
 Compliance with RoHS

PS48165/3200 mode3
Dimensions And Weight
model W×D×H, mm Weight (kg) Distribution Unit Location
PS48165/3200 mode 1 600×600×1600 75(rectifier excluded) Top
Cabinet
PS48165/3200 mode 2 600×400×1600 65(rectifier excluded) rear
Subrack PS48165/3200 mode 3 584×327×132 20(rectifier excluded)

8
Business-Critical Continuity™

PS48360/1800
(ACTURA Flex 48420)
Integrative DC Power Series
-48VDC
up to 20.8kW

Applications
 2G, 3G mobile base stations R48-1800
 Medium exchanges, rural telecom networks and access networks
 Transmission relay stations
 Microwave/satellite communications stations

Features
 Capacity up to 20.8kW (360A @ 58V)
 Rectifiers R48-1800(1740W)and SCU inside
 Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage M501D
 Efficiency high up to 92%
 Power factor high up to 0.99
 Output current Walk-in available
 Patented energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Rectifiers and controller hot swappable
 Front access
 Top cabling
 Inner 660Ah battery shelves optional
 Rectifier CE/UL approval
 Compliance with RoHS

Dimensions And Weight PS48360/1800


model W×D×H, mm Weight (kg)
PS48360/1800-X1 600×600×2000 135(rectifier excluded)
Cabinet PS48360/1800-X2 600×400×2000 125(rectifier excluded)
PS48360/1800-X3 600×600×1800 100(rectifier excluded)


DC Power System

PS48300/1800-X6
Integrative DC Power Series
-48VDC
up to 14.7kW
Applications
 2G, 3G mobile base stations
 Medium exchanges, rural telecom networks and access networks
 Transmission relay stations
 Microwave/satellite communications stations

PS48300/1800-X6 Features
 Capacity up to 14.7kW (300A @ 58V)
 Rectifiers R48-1800(1740W)and SCU inside
 Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
 Efficiency high up to 92%
 Power factor high up to 0.99
 Output current Walk-in available
 Patented energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Rectifiers and controller hot swappable
 Front access
M501D  Top/Bottom cabling
 Rectifier CE/UL approval
 Compliance with RoHS

Dimensions And Weight


model W×D×H, mm Weight (kg)
Cabinet PS48300/1800-X6 600×600×1600 130(rectifier excluded)

R48-1800

10
Business-Critical Continuity™

PS48120/1800-X6
Integrative DC Power Series
-48VDC
up to 6.96kW
Applications
 2G, 3G mobile base stations
 small exchanges, rural telecom networks and access networks
 Transmission relay stations
 Microwave/satellite communications stations
 Railway stations

Features PS48120/1800-X6
 Capacity up to 6.96kW (120A @ 58V)
 Rectifiers R48-1800(1740W)and SCU inside
 Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
 Efficiency high up to 92%
 Power factor high up to 0.99
 Output current Walk-in available
 Patented energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Rectifiers and controller hot swappable
 Front access
 Top/Bottom cabling M501D
 Inner 330Ah battery shelves optional
 Rectifier CE/UL approval
 Compliance with RoHS

Dimensions And Weight


model W×D×H, mm Weight (kg)
Cabinet PS48120/1800-X6 600×600×2000 110(rectifier excluded)

R48-1800

11
DC Power System

PS4875/25
Wall-mounted Integrative DC Power Series
-48VDC
up to 4.35kW
Applications
 2G, 3G mobile base stations
 Small exchanges, rural telecom networks and access networks
 Transmission relay stations
 Microwave/satellite communications stations
PS4875/25
 Railway stations

Features
 Capacity up to 4.35kW (75A @ 58V)
 Rectifiers HD4825-3(1450W)inside
 Wall-mounted for space saving
 Wide input voltage range (90 to 290Vac), up to 415Vac endurance without damage
 Efficiency high up to 90%
 Power factor high up to 0.99
 Output current Walk-in available
 Patented energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Rectifiers and controller hot swappable
 Front access
 Top cabling
 Rectifier CE approval
 Compliance with RoHS

Dimensions And Weight


model W×D×H, mm Weight (kg)
Cabinet PS4875/25 450×260×700 40(rectifier excluded)

12
Business-Critical Continuity™

PS4890/800 (ACTURA 48201)


Subrack DC Power Series
-48VDC
up to 4.8kW
Applications
 2G, 3G mobile base stations
 small access networks
 Microwave/satellite communications stations

Features
 19” Subrack system
 Capacity up to 2.4kW one subrack, 4.8kW dual subracks
 Rectifiers R48-800(800W)and SCU inside
 Wide input voltage range (85 to 300Vac)
 Efficiency high up to 91%
 Power factor high up to 0.99
 Output current Walk-in available
 Patented energy-saving mode available
 Intelligent monitoring and remote control
 BLVD, LLVD optional
 Rectifiers and controller hot swappable
 Rectifier CE/UL approval
 Compliance with RoHS

Dimensions And Weight


model W×D×H, mm Weight (kg)
PS4890/800 single subrack 485×345×90 8.8(rectifier excluded)
PS4890/800 dual subracks 485×345×180 17.9(rectifier excluded)

13
DC Power System

PS24600/75
Integrative DC Power Series
+24VDC
up to 17.4kW
Applications
 2G, 3G mobile base stations
 Medium exchanges, rural telecom networks and access networks
 Transmission relay stations
 Microwave/satellite communications stations

PS24600/75 Key Features


 Capacity up to 17.4kW (600A @29V)
 Rectifiers HD2475-2(2175W)inside
 Wide input voltage range (120 to 290Vac), up to 415Vac endurance without damage
 Efficiency high up to 88%
 Power factor high up to 0.99
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Rectifiers and controller hot swappable
 Front access
 Top or bottom cabling
 Rectifier CE approval
 Compliance with RoHS

Dimensions And Weight


model W×D×H, mm Weight (kg)
Cabinet PS48600-3/2900-X5 600×600×2000 158(rectifier excluded)
Rectifier HD2475-2 105×400×245 8
Controller PSM-A11

14
Business-Critical Continuity™

PSC48150/25
Integrative DC Power Series
+24Vdc/-48Vdc, 7.2kW

Applications
 2G, 3G mobile base stations
 Medium exchanges
 Transmission relay stations
 Microwave/satellite communications stations

Features
 +24V/-48V DC/DC system
 Capacity up to 7.2kW
 Wide DC input voltage range: 21V~29V
 DC/DC module(1200W)inside PSC48150/25
 DC/DC converter Hot-swappable
 Extremely low radiation, meeting
 Relay output for alarm port
 Complete lightning proof in input and output rated at 5KA(8/20us)
 Complete fault protection functions
 Optional remote monitor and control
 Front access
 Compliance with RoHS

Dimensions And Weight


model W×D×H, mm Weight (kg)
Cabinet PSC48150/25 200×400×1460 45(rectifier excluded)
DC/DC converter C24/48-1200 85.5×287×132.5 2.5

1
EMERSON NETWORK POWER.

THE GLOBAL LEADER IN ENABLING


BUSINESS-CRITICAL CONTINUITY.™

AC POWER

CONNECTIVITY

DC POWER

EMBEDDED COMPUTING

EMBEDDED POWER

OUTSIDE PLANT

MONITORING

OUTSIDE PLANT

POWER SWITCHING
& CONTROLS

PRECISION COOLING

RACKS & INTEGRATED


CABINETS

SERVICES

SURGE PROTECTION

Protecting and moving voice,video and data from the

central office closer to the subscriber. We deliver a full line of

enclosures,cabinets and shelters that meet the networked

world’s demands for high speed without interruption,

from MESA® and DEC integrated enclosure solutions to

Emerson Network Power ES, EC, EPC outdoor power solutions

to cross-connects to ProFORM® distribution terminals to

NetSpanTM Integrated FTTx Solutions.

OUTSIDE PLANT. Yet another way Emerson Network power

enables Business-Critical Continuity™.

16
Business-Critical Continuity™

EPC48180/1800-FA
-48VDC Outdoor Power Cabinet

Applications
 Outdoor stations of GSM, UMTS, CDMA
 Fiber optic transmission systems
 Digital loop carriers

Features
 Capacity up to 10.44kW (180A @ 58V) EPC48180/1800-FA
 Totally front access in favor of space-saving
 Forced vent cooling system
 Patent design of Isolated air channel for safe operation
 IP55 for equipment chamber
 Forced vent cooling for battery chambers
 Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
 Rectifiers R48-1800(1740W) and SCU inside
 Efficiency high up to 92%
 Power factor high up to 0.99
 Output current Walk-in available
 Perfect fan speed control for energy-saving
 Patent energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Class B+C lightning protection optional
 Rectifiers and controller hot swappable
 Inner dual 330Ah battery Chambers
 Rectifier CE/UL approval
 Compliance with EN60950 and IEC60950, RoHS
 H-mast platform installation available

Dimensions And Weight


model W×D×H, mm Weight (kg)
Cabinet EPC48180/1800-FA 700×700×1700 150(rectifiers and batteries excluded)

17
Outside Plant

EPC48120/1800-F
-48VDC Outdoor Power Cabinet

Applications
 Outdoor stations of GSM, UMTS, CDMA
 Fiber optic transmission systems
 Digital loop carriers

Features
EPC48120/1800-F
 Capacity up to 6.96kW (120A @ 58V)
 Totally front access in favor of space-saving
 Forced vent cooling system
 IP45 for equipment chamber
 Patent design of Isolated air channel for safe operation
 Forced vent cooling for battery chambers
 Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
 Rectifiers R48-1800(1740W)and SCU inside
 Efficiency high up to 92%
 Power factor high up to 0.99
 Output current Walk-in available
 Perfect fan speed control for energy-saving
 Patent energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Class B+C lightning protection optional
 Rectifiers and controller hot swappable
 Inner dual 330Ah battery Chambers
 Rectifier CE/UL approval
 Compliance with EN60950 and IEC60950, RoHS
 H-mast platform installation available

Dimensions And Weight


model W×D×H, mm Weight (kg)
Cabinet EPC48120/1800-F 600×630×1500 140(rectifiers and batteries excluded)

18
Business-Critical Continuity™

EPC48120/1800-HA(B)
-48VDC Outdoor Power Cabinet

Applications
 Outdoor stations of GSM, UMTS, CDMA
 Fiber optic transmission systems
 Digital loop carriers

Features
 Capacity up to 6.96kW (120A @ 58V)
 Totally front access in favor of space-saving
EPC48120/1800-HA
 Heat-exchange cooling system
 IP55 for equipment chamber
 Wide operation temperature, -40~+45℃ optional
 Patent design of Isolated air channel for safe operation
 Forced vent cooling for battery chambers
 Wide input voltage range (85 to 300Vac), up to 415Vac endurance without damage
 Rectifiers R48-1800(1740W)and SCU inside
 Efficiency high up to 92%
 Power factor high up to 0.99
 Output current Walk-in available
 Perfect fan speed control for energy-saving
 Patent energy-saving mode available
 Intelligent monitoring and remote control
 Surge protection on AC, DC and signal side
 Class B+C lightning protection optional
 Rectifiers and controller hot swappable
 Inner dual 330Ah battery Chambers
 Rectifier CE/UL approval
 CE mark
 Compliance with EN60950 and IEC60950, RoHS
 H-mast platform installation available

EPC48120/1800-HB
Dimensions And Weight
model Op. temp. W×D×H, mm Weight (kg)
EPC48120/1800-HA -10~+45℃
Cabinet 600×600×1700 150(rectifiers and batteries excluded)
EPC48120/1800-HB -40~+45℃

19
Outside Plant

EC200T/01
Outdoor Battery Cabinet

Applications
 Outdoor stations of GSM, UMTS, CDMA
 Fiber optic transmission systems
 Digital loop carriers

EC200T/01 Features
 Cater up to 3 strings of 165Ah batteries
 Thermoelectricity cooler (TEC) inside
 Inner temperature 5~15℃ below outside ambient
 IP55
 Dry-contact alarm for fans and door sensor
 Compliance with RoHS

Dimensions And Weight


model Op. temp. W×D×H, mm Weight (kg)
Cabinet EC150F/01 -10~+55℃ 650×720×1400 100(batteries excluded)

20
Business-Critical Continuity™

EC150F/01
Outdoor Battery Cabinet

Applications
 Outdoor stations of GSM, UMTS, CDMA
 Fiber optic transmission systems
 Digital loop carriers

EC150F/01
Features
 Cater up to 2 strings of 165Ah batteries
 Forced vent cooling
 IP34
 Dry-contact alarm for fans and door sensor
 Compliance with RoHS

Dimensions And Weight


model Op. temp. W×D×H, mm Weight (kg)
Cabinet EC150F/01 -10~+45℃ 700×700×1000 100(batteries excluded)

21
Outside Plant

EC100F/01
Outdoor Battery Cabinet

Applications
 Outdoor stations of GSM, UMTS, CDMA
 Fiber optic transmission systems
 Digital loop carriers

EC100F/01
Features
 Cater up to 2 strings of 165Ah batteries
 Forced vent cooling
 IP34
 Dry-contact alarm for fans and door sensor
 Compliance with RoHS

Dimensions And Weight


model Op. temp. W×D×H, mm Weight (kg)
Cabinet EC100F/01 -10~+45℃ 600×600×1000 100(batteries excluded)

22
EMERSON NETWORK POWER.

THE GLOBAL LEADER IN ENABLING


BUSINESS-CRITICAL CONTINUITY.™

AC POWER

CONNECTIVITY

DC POWER

EMBEDDED COMPUTING

EMBEDDED POWER

AC POWER

MONITORING

OUTSIDE PLANT

POWER SWITCHING
& CONTROLS

PRECISION COOLING

RACKS & INTEGRATED


CABINETS

SERVICES

SURGE PROTECTION

Sustaining critical operations that simply can’t

go down. We deliver a full range of uninterruptible

Liebert® AC power systems and complete

associated power distribution and enclosures,

from individual products to integrated systems

that keep network closets up and running.

AC Power. Yet another way Emerson Network

Power enables Business-Critical Continuity™.

23
AC Power

AC POWER
Configuration Matrix
Small System Medium System Small System

SERIES: US11R iTrust 31 iTrust 2G


RATING: 1/2/3KVA 10/15/20KVA 3/6/9/12/15/18KVA
MOUNTING: Tower/Rack Tower Tower/Rack
I/O: 1-ph./1-ph. 3-ph./1-ph. 1-ph./1-ph.
VOLTAGE: 220/230/240 (L-N) 380/220 220 (L-N)
FREQUENCY: 50Hz 50Hz 50Hz

Large system Medium System

SERIES: NX Hipulse-U Outdoor UPS


RATING: 10/15/20/30/40/60/80/100/120/140/160/200KVA 160/200/300/400KVA 2KVA/3KVA
MOUNTING: Tower Tower Tower
I/O: 3-ph./3-Ph. 3-ph./3-ph. 1-ph./1-ph.
VOLTAGE: 380/400/415 (L-L) 380/400/415 (L-L) 220(L-N)
FREQUENCY: 50/60Hz 50/60Hz 50Hz

24
Business-Critical Continuity™

US11-R Series——1/2/3KVA

Applications
 Servers/Storage/Workstation
 Telecommunication, VoIP
 Small Office Network
 Data Warehouses
 Medical Diagnostics
 Process Automation Equipmentsv

Special Features
 Rack/Tower design, adaptable for table and 19' IT rack application
 Double conversion, true on-line style
 Fully digital control
 Input surge suppressor equipped
 CE marked
 IGBT based rectifier and excellent input performance
 Super wide input window
 Mutiple AC output connections
 2U height
 High EMC performance, classB achieved
 Intelligent battery management

Dimensions And Weight


Model Name Size(WDH in MM) Weight(Kg)
US11R-0010 440×400×87 17.5
US11R-0010L 440×400×87 7.8
US11R-0020 440×400×87 29.1
US11R-0020L 440×400×87 9.6
US11R-0030 440×400×87 30.5
US11R-0030L 440×400×87 10.5
UF-B0007-06 440×400×87 20.5
UF-B0009-06 440×400×87 21.5
Note: US11R-0020 will be shipped with a VF-B0007-06
US11R-0023 will be shipped with a VF-B0009-06

25
AC Power

US11-R Series Datasheet


US11R-0010 US11R-0020 US11R-0030
Model
US11R-0010L US11R-0020L US11R-0030L
Nominal Power Rating at 0.7 PF 1KVA 2KVA 3KVA
Input Parameters
Rectifier Type IGBT-based PFC(Power Factor Correction)
Input Voltage 220Vac, 1-ph, 3-w
Permissible Input Voltage Range 120-288Vac
Permissible Input Frequency Range 50Hz ±2%,5%,7%,10% User selectable
Input Power Factor at nominal voltage ≥0.99
Battery
Battery Type Maintenace Free, VRLA (Valve Regulated Lead Acid)
Nominal Battery Bus 36Vdc 72Vdc 72Vdc
Recharging Time to 90% Recovery <4 hours <4 hours <4 hours
Output Parameters
Inverter Type IGBT-based Inverter
Output Power 0.7kW 1.4kW 2.1kW
Output Connection GB/IEC GB/IEC GB/IEC/Terminal
Output Voltage 220Vac, 1-ph, 3-w
Output Frequency 50Hz ±0.2%
Output Voltage THD <3% at linear load; < 5% at non-linear load
Capability to handle High Crest Factor Load 3:1 (compliant with IEC 62040-3)
Capability to handle Step Load 100%
105% FL Infinite
105-125% FL for 5 mins
Overload Capability
125-150% FL for 1min
>150% FL for 10s
System Parameters & Standards
AC-AC Efficiency >89% >90% >90%
Switch Time When Input Fails 0s
Noise <43dB <45dB
Display LED
Dimension (W×D×H)mm 440×400×87
U-Height 2u 2u 2u
Weight (Standard/L model) 17.5/7.8kg 29.1/9.6 30.5/10kg
Safety EN62040-1-1, CE Marked
EMI /EMC EN50091-2 Class B
Inmunity EN50082-1
Surge Protection IEC 60664-1 Level IV
Protection IP21
Communication & Management
Interface Port Serial / Dry Contact / SNMP Card
Web/SNMP Card Optional
Environmental Parameters
Operating Temperature Range 0℃ to 40℃ (UPS) & 25℃ ±5 (Battery)
Relative Humidity 0% to 95% (non-condensing)
Maximum Altitude above MSL 1500m (as per IEC 62040-3)

26
Business-Critical Continuity™

UH31 Series—10/15/20KVA
Applications
 Small data centers of banks/stock exchanges, server groups, small/middle computer rooms,
offices, PC groups, important facilities, etc

Features
 Three phases input, one phase output ( 220/230Vac)
 True on-line style
 IGBT based rectifier/inverter
 DSP control
 Super wide input window (-45%~+15%)
 On-line operation when input phases lose
 D-class surge suppressor equipped
 Intelligent battery management
 Chinese/English LCD interface available
 Class A EMC standard acquired
 Input phase loss tolerance

Dimensions And Weight


Model Name Size(WDH in MM) Weight(Kg)
UH31-0100L 280×875×770 97
UH31-0150L 280×875×770 97
UH31-0200L 280×875×770 116

27
AC Power

UH31 Series Datasheet


Model UH31-0100L UH31L-0150 UH31-0200L
Nominal Power Rating at 0.7 PF 10KVA 15KVA 20KVA
Input Parameters
Rectifier Type IGBT-based PFC (PF Corrected)
Input Voltage 380Vac, 3-ph, 4-w
Permissible Input Voltage Range 120Vac-276Vac
Permissible Input Frequency Range 45-55Hz
Input Power Factor at nominal voltage ≥0.95
Battery
Battery Type VRLA (Value Regulated Lead Acid)
Nominal Battery Bus 480Vdc 480Vdc 480Vdc
Output Parameters
Inverter Type IGBT-based Inverter
Output Power 7kW 10.5kW 14kW
Bypass Voltage Range 120Vac-253Vac
Output Voltage 220Vac, 1-ph, 3-w
Output Voltage Regulation ±0.5%
Output Frequency 50Hz
Output Voltage THD < 3% at linear load; < 5% at non-linear load
Capability to handle High Crest 3:1 (compliant with IEC 62040-3)
Factor Load
Capability to handle Step Load 100%
105-125% FL for 10 mins
Overload Capability 125-150% FL for 1min
>150% FL for 200ms
System Parameters &Standards
AC-AC Efficiency >91% >92%
Switch Time When Input Fails 0s
Noise <55dB <60dB
Display LED+LCD
Dimension (W×D×H) 280×875×770mm
Weight (Standard/L model) 97kg 116kg
Safety EN60950
Immunity EN61000-4-2,3,4,6,8,11 Level III, EN61000-4-5 Level IV
EMC EN55022 Class A
Surge Protection IEC 60664-1 Level IV
Parameters &Standards
Operating Temperature Range 0℃ to 40℃ (UPS) & 25℃ ±5℃ (Battery)
Relative Humidity 0% to 95% (non-condensing)
Maximum Altitude above MSL 1500m (as per IEC 62040-3)

28
Business-Critical Continuity™

iTrust 2G Series UPS


Applications
 Industrial equipments
 Small data centers
 Computing centers
 Telecommunication network hubs

Features
 Modular Design- Plug & Play
 N+X Redundancy - Higher reliability
 Easy and cheap expansion- Modules only
 Online during maintenance- By simply replacing modules
 Space saving - Compact Design
 Large Capacity Battery Affordable -Extendable 10A/20A charger available
 Energy Saving - High Efficiency and excellent input PF
 Higher adaptability to harsh input - Extremely Wide Input window
 Longer battery life available - Intelligent Battery Management
 Quiet - Low noise
 Less worry - Self diagnosis and Fault Prediction

Dimensions And Weight


Model Name Size(WDH in MM) Weight(Kg)
Power Module UF-P0030 436 × 412 × 85 10.4
Battery Module UF-B0007-8 436 × 400 × 36 26
10A Charger Module UFP-BCH110/10 436 × 412 × 85 7.6
20A Charger Module UFP-BCH110/20 436 × 412 × 85 10.4
6-Bay Rack UP11-0180/6 500 × 552 × 994 70
12-Bay Rack UP11-0180/12 500 × 552 × 1492 105

29
AC Power

iTrust 2G Series Datasheet


Models 3KVA 6KVA 9KVA 12KVA 15KVA 18KVA
2.4kW 4.8kW 7.2kW 9.6kW 12kW 14.4kW
Model Name UP11-0180/12(12-Bay) UP11-0180/6(6-Bay)
Input Parameters
Rectifier Type IGBT-based PFC
Input Voltage 220Vac/1ph/3w
Permissible Input Voltage Range 120-288Vac
Permissible Input Frequency Range 45-55Hz
Input Power Factor at nominal voltage ≥0.99 without any Filter
Ace
Battery
Battery Type VRLA
Nominal Battery Bus 96Vdc
Output Parameters
Inverter Type IGBT-based
Output Rating 3/6/9/12/15/18 KVA
Output Power Factor 0.8
Output Voltage 220Vac/1ph/3w
Output Voltage Regulation 1%
Output Frequency 50Hz
Capability to handle High Crest Factor Load 3:1
Capability to handle Step Load 100%
Compliance to EMC Class-A Applicable for both Radiated & Conducted
105% FL for continuous running
Overload Capability 125% FL for 10 minutes
150% FL for 10 S
System Performance
AC-AC Efficiency > 90%
Transfer Time When Input Fail 0s
Environmental Parameters
Operating Temperature Range 0℃to 40℃ (UPS)
Relative Humidity 0% to 95% (non-condensing)
Maximum Altitude above MSL 1500m (as per IEC 62040 3)
Physical Parameters &Standards
Colour Black
Degree of Protection IP21

30
Business-Critical Continuity™

NX Series UPS
Applications
 Server Rooms and Mid-sized Data Centers
 Telecommunication (Fixed, WiLL & Mobile) Billing Computers
 Networks (LAN, MAN & WAN), InfoCom and WiFi Hot Spots
 Industrial Process & Motion Automations for Mid-sized Plants
 Medical Diagnostic / Imaging Equipment

Features
 Full digital control based on latest DSP
 Advanced Vector Control to Achieve Excellent Output Performance
 'Green UPS' Design with High input power factor : 0.99 Low input current harmonic of less than : 3%
 Wide input window : 208-477V (L-L voltage)
 Parallel up to 6 units, No MSS needed
 High Efficiency: up to 94%
 Compact Footorint and Front Access
 Unique Dual Bus design
 Flexible Power Walk-in
 Built-in Redundancies to Achieve High Reliability(fans/auxiliary power supply card/..)
 Intelligent battery management
 Self diagnosis

Dimensions And Weight


Model Name Size(WDH in MM) Weight(Kg)
NXe-10KVA 600×700×1400 180
NXe-15KVA 600×700×1400 204
NXe-20KVA 600×700×1400 204
NXe-30KVA 600×700×1400 260
NXa-40KVA 600×825×1600 340
NXa-60KVA 600×825×1600 400
NXa-80KVA 600×825×1600 445
NXa-100KVA 700×825×1800 720
NXa-120KVA 700×825×1800 720
NXa-140KVA 1000×825×1800 824
NXa-160KVA 1000×825×1800 973
NXa-200KVA 1000×825×1800 973

31
AC Power

NX Series Datasheet
Models Nxe10 Nxe15 Nxe20 Nxa30 Nxa40 Nxa60 Nxa80 Nxa100 Nxa120 Nxa140 Nxa160 Nxa200
NominalPowerRatingat0.8PF 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 140KVA 160KVA 200KVA
Input Parameters
Rectifier Type IGBT-based Vector Controlled PFC (PF Corrected)
Input Voltage 380/400/415Vac (Accepted from 305-477Vac without Batt. Use)
Input Frequency 40-70Hz
Input Current THD <3% (without any Filter)
Input Power Factor ≥0.99 (without any Filter)
Flexi Power Walk-In 5 to 30S (Selectable)
Battery
Battery Type VRLA (Value Regulated Lead Acid) / Wet-Flooded / NiCd
End-Cell Voltage Selectable from 1.60-1.90Vdc/Cell (VRLA)
DC ripple Current in float
<5%(C10 AH Capacity) RMS Value
mode
DC ripple Voltage in
<1% (RMS Value)
float & Const V Ch.mode
Temperature
Standard (for in-build batteries for 10/15/20/30/40 KVA)
Compensated Battery
Optional (for all other battery configurations)
Charging
In-Built VRLA Battery
Optionally applicable for 10/15/20/30/40 KVA
Availability
Output Parameters
Inverter Type IGBT-based Vector, Repetitive & PI Controlled
Output Power 8kW 12kW 16kW 24kW 32kW 48kW 64kW 80kW 96kW 112kW 128kW 160kW
Output Voltage 380/400/415Vac * (Nominal: 400V) 3-ph, 4-w (Ph+N)
Output Voltage
±0.5%
Regulation
Output Frequency 50/60±0.05Hz Regulation
Output Voltage THD 1% (max)
Max. Crest Factor Load 3:1 (compliant with IEC 62040-3)
Capability to handle
100%
Step Load
Max. Leading PF Load Up to 0.9
Voltage Displacement 120o±1oel (with 100% unbalanced load)
Overload Capability 110 for 60 minutes, 125 for 10 minutes, 150 for 1 minutes
Standards
EMC Class Class A (Applicable for both Radiated & Conducted)
Enclosure IP IP 20 even with front door in opened condition, IP21 Optional
Standards & IEC 62040-3, IEC 62040-2, IEC 62040-1-1, IEC 60146-1-1, IEC 61000-4-2,4,5,6,8,11, EN 50091-1-1,
Conformities EN 50091-2, EN 50091-3, EN60950, EN 60529, ANSI C62.41 (IEEE 587)
Environmental Parameters
Operating Temperature
0 to 40℃ (UPS) & 25 ±5℃ (Battery)
Range
Relative Humidity 0 to 95% (non-condensing)
Maximum Altitude
1000m (as per IEC 62040-3)
above MSL

32
Business-Critical Continuity™

Hipulse-U Series—160/200/300/400KVA
Applications
 Medinm & large Data Center
 Telecommunication
 Industrial Automation
 Transport Automation
 Banking, Insurance and Financial Sernices
 Software Development Houses/Software Technology Parks(STP)
 Building Automation
 Medical Diagnostics
 Satellite

Features
 Fully Digital, Twin DSP controlled.
 Rated at 0.9 output power factor to deliner more real power
 Handle Leading Power factor Loads withour KW de-rating under specified conditions
 On-Line Double Conversion
 IGBT-based PWM Inverter
 Wide input voltage tolerance(+15/15%)
 Wide input frequency tolerance(45Hz-65Hz)
 High overload capability of static bypass(14 times for 10 milliseconds and 10 times for 100
nukkusecibds)
 Built-in maintenance bypass(Single and 1+N Models)
 Wrap-around maintenance bypass(optional)
 Front acces for spares replacement and preventive maintenance
 Easy Dual bus Configuration architecture
 Adjustable frequency synchronisation window up to 9% in the static bypass
 Provision of automatic battery circuit breaker instead of using conventional isolator in the DC path
 Field protocols ModBus/Jbus
 Eady Scalability (Parallel 1+N configuration up to 6 modules paralleling)without centralised Main
Static Switch (MSS)
 Bypass Switch
 Compact footorint

Dimensions And Weight


Model Name Size(WDH in MM) Weight(Kg)
Hipusle U-160KVA, 6 Pulse 1250×840×1910 1200
Hipusle U-160KVA, 12 Pulse 1640×840×1910 1725
Hipusle U-200KVA, 6 Pulse 1250×840×1910 1350
Hipusle U-200KVA, 12 Pulse 1640×840×1910 2000
Hipusle U-300KVA, 6 Pulse 1640×840×1910 1600
Hipusle U-300KVA, 12 Pulse 2280×840×1910 2200
Hipusle U-400KVA, 6 Pulse 2280×840×1910 2100
Hipusle U-400KVA, 12 Pulse 2280×840×1910 2750

33
AC Power

Hipulse-U Series Datasheet


Hipulse UPS System
Nominal Rating(KVA)(0.9pf)/kW 160/144 200/180 300/270 400/360
Rectifier Type 6P 12P 6P 12P 6P 12P 6P 12P
Input
Voltage 380/400/415V(+/-15%)-3Ph-4w(rectifier:290-498V)
Frequency 50 or 60Hz +/-5%
ITHD 4 to 9% with optional harmonic filter
Power Factor 0.90-0.95 with optional harmonic filter
Output
Voltage 380/400/415V-3Ph-4w
Voltage stability
-Steady state +/-0.5%
-100% Load Step +/3%
Frequency 50 or 60Hz
Frequency Stability
-Synchronised with the bypass supply +/0.5 Hz, +/-1 Hz, +/-2Hz, +/-3Hz(settable)
-Auto-Synchronised +/0.1%
Overload copacity from inverter at vominal voltage
-3 Ph 110% for 60 minutes, 125% for 10 minutes, 150% for 1 minute
-1 Ph 200% for 30 seconds
short circuit current from inverter
-3 Ph 1.5 in for 5 seconds (in acordance with EN 50091-1-1)
-1 Ph 2.9 in for 5 seconds 2.2 in for 5 seconds
Voltage Distortion with Linear Load <3%
Voltage Distortion with 100%
<5%
Non-Linear Load
Max.Deliverable Power
100%
with Non-Linear Load(CF-3:1)
Max Unbalanced Load 100%
Voltage Displacement With
120o+/-1oel
100% Unbalanced Load
Output Voltage Dissymmetry
2%
with 100% Unbalanced Load
Standards and Approvals
Safety / EMC / Design IEC60950-1,IEC62040-1-1,UL1778,IEC62040-2 CLASS A,EN50091-CLASS A,IEC62040-3
European Directives
73/23/EEC and 89/336/EEC CE

34
Business-Critical Continuity™

Outdoor Series
Application
 Outdoor BTS

Special Features
 Natural cooling, high system reliability achieved
 Dual conversion, online style
 Fully digital control
 Auto start up when mains recovered
 Super wide input window (150-310V L-N)
 IP55 protection level
 Wide operation Temperature: -40-550C
 High level surge suppressor can be equipped inside; (Optional)
 Boosted/float charging auto transfer
 3 mounting options available (wall/mask/floor)
 Zero output interrupt when input fails
 Optional charger for quick battery recovery in long backup system
 Heater optional for cold area
 Optional Battery cabinet available with maximum 4 hours backup time at full load
 Power module separate with battery enclosure, high system flexibility achieved

Dimensions And Weight


Model Name Size(WDH in MM) Weight(Kg)
Outdoor 2KVA UPS UH11-0020LC 485×263×615 53*
Outdoor 3KVA UPS UH11-0030LC 485×263×615 59**
Battery Cabinet (South Type) U6-100C3S 850×550×1170 70
Battery Cabinet (North Type) U6-100C3N 850×550×1170 72
*: Including Mounting Kit,36Kg Net
**: Including Mounting Kit,42Kg Net

35
AC Power

Outdoor Series Datasheet


Capacity 2KVA/3KVA
Model Name UH11-0020LC, UH11-0030LC
Input
Rated Voltage 220Vac
Voltage Range 150-310Vac
Frequency 45~65Hz
Power Factor > 0.98
Output
Powe Factor 0.7 temp<5℃ 0.6 temp>10℃
Normal Voltage 220Vac 3%
Frequency 50Hz
Frequency Tracking Rate ≤1 Hz/s
Inverter Overload Capability 105%-125%, 5mins, >125%, 20s,
Peak Factor 3:1
Bypass Voltage 150~310Vac
Efficiency (NormalMode) >89%
Sheft Time
Utility Failure 0ms
Shift between invertermode and < 10ms
bypass mode (Synchronized )
Insulation
Insulation Resistance >2MΩ(500Vdc)
Dielectric Strength (Output to earth Input to earth)2820Vdc,leakage current <3.5mA for 1min without arc or
breakdown
Environment
Operation temperature -40℃ -55℃
Storage temperature -40℃ -70℃
relative humidity 10%-100% (no condensing)
altitude Under 4000m, over 4000m, de-rated,
Protection Level IP55
Noise <40dB

36
Business-Critical Continuity™

Monitoring Solutions
Our Monitoring Solution Includes 5 Parts
1.Point-to-point and internet-based network remote monitoring, unlimited with the number of
nodes
2.SNMP Card: An internet node, providing UPS with Ethernet communication capability
3.UPS Network Adapter: Monitoring UPS products of other brands
4.UPS Adapter for Equipment Room Signals Applied together with our SNMP Card, realizing
centralized monitoring and processing of multi environment measures such as temperature,
humidity, infrared, door alarm, water immersion ( 8 analogues and 8 dry contacts)
5.Wireless MODEM: Able to send wireless messages, reporting UPS operation status and alarms to
the customers and realizing No-Man-On-Duty

Features
 Java programming language. Web-based general-purpose monitoring software
 Compatible with multi operation systems, eg., Windows, Linux, Solaris, AIX, HP-UX, etc.
 Can log on via any computer on network
 UPS by-layer management mode
 Complete history records for inquiry, statistics and preview before printing
 Multi alarming: Sound, paging, email and messages, etc.
 Multi language versions, on-line upload and upgrade
 WEB-configured interfaces, very easy to operate
 Large storage of history records
 Least system resource occupied
 Strict safety management mechanism
 On-line smooth access system for new equipment
 Multi system environment measures accessible

37
AC Power

SiteMonitor

1. Easy installation

2. Clear display of UPS operation status

Can name based on requirements and Click on UPS icons to check all operation
display by layer indices and historical records online, with
power status completely in hand

3. Easy setting and adjustment

Under authorization, a network Model selection and configuration


administrator can remotely control the
center, eg. operate turnoff, battery self-
diagonosis, erase after sound alarm, etc.

38
Business-Critical Continuity™

SNMP Card-A Bridge Connecting


UPS and Network
The SNMP card is based on TCP/IP communication protocol and can also
support SNMP, HTTP(web server), Telnet communication protocols to meet the
needs of all sorts of networks

Features
 Supports web browse and NMS management systems
 Software can be updated on line
 10/100M network self-adapting
 Hot plug-in/plug-out supported
 All the settings can be done through software

39
AC Power

Intelligent Battery Management


Auto-adaptable on EOD(End Of Discharge) Adjustment
 Different discharging solution for short backup-time system (<1h) and long backup-time
system(>1h)
 The data of different models of batteries are stored in DSP and the UPS will detect the discharging
current and automatically adjust the EOD for best performance of the battery. In this way, over-
discharge of battery is avoided

Self-diagnosis
 Battery self-diagnosis can be set to operate periodically via front panel

Auto-switch between Boost and Float Recharging


 Shorten recharging period and prolong the battery life by 50%

Temperature Compensation
 Auto-adjustment for float charging voltage according to ambient temperature

40
EMERSON NETWORK POWER.

THE GLOBAL LEADER IN ENABLING


BUSINESS-CRITICAL CONTINUITY.™

AC POWER

CONNECTIVITY

DC POWER

EMBEDDED COMPUTING

EMBEDDED POWER

RACKS & INTEGRATED CABINETS

MONITORING

OUTSIDE PLANT

POWER SWITCHING
& CONTROLS

PRECISION COOLING

RACKS & INTEGRATED


CABINETS

SERVICES

SURGE PROTECTION

Optimizing technology and performance needs

for the global IT and telecom markets. We deliver

standard and customized integrated cabinet

solutions that meet unique and specific needs,

from knürr and Liebert® rack solutions for

customer rooms of all sizes to knürr,MESA® and

Netspan™、Matrix™ enclosures and shelters for

wireline and wireless applications.

RACKS & INTEGRATED CABINETS .Yet another

way Emerson Network power enables Business-

Critical Continuity™.

41
Racks & Integrated Cabinets

Server Enclosure Systems


Rack system and IT total solution

Emerson Network Power Co.,Ltd. Launched the high reliability and high
availability rack system and IT room total solution that suit the features of
blade server based on its deep understanding in the user’s requirements for IT
application and the existing issues.

Applications
 Network access rooms
 Computer rooms
 Data center

Features and Benefits


 World-leading heat dissipation design: The 83% perforating rate that is the highest in the world
meets the heat dissipation requirement of high thermal-density of blade server
 Special modular structure: Modular structure and modular installation: Convenient storage and
transportation, fast and convenient disassembly and assembly
 Reliable and stable power supply and distribution design: double conversion online UPS, the total
power distribution solution meets the different customer requirements
 Convenient cable management: Comprehensive cable management accessories meet the
different cable management requirements
 Advanced rack monitoring and safety system: Remote monitoring to the rack environment,
including temperature, humidity, door alarm and smoke, etc

Miracel Series:
Product Type Capacity Width(mm) Distance(mm) High(mm)
NR-M060820 42U 600 800 2000
SR-M061020 42U 600 1000 2000
SR-M061220 42U 600 1200 2000
SR-M081020 42U 800 1000 2000
SR-M081220 42U 800 1200 2000
Accessories Fan, plinth, cable management unit, power distribution unit, etc.

42
EMERSON NETWORK POWER.

THE GLOBAL LEADER IN ENABLING


BUSINESS-CRITICAL CONTINUITY.™

AC POWER

CONNECTIVITY

DC POWER

EMBEDDED COMPUTING

EMBEDDED POWER

PRECISION COOLING

MONITORING

OUTSIDE PLANT

POWER SWITCHING
& CONTROLS

PRECISION COOLING

RACKS & INTEGRATED


CABINETS

SERVICES

SURGE PROTECTION

Maintaining precise temperature for reliable equipment

performance. We deliver “chip-to-room cooling”-the

most comprehensive range of liebert® precision-cooling

solutions,which protect mission-critical applications

from even the slightest increase in temperature.

PRECISION COOLING. Yet another way Emerson

Network power enables Business-Critical Continuity™.

43
Precision Air Conditioning

Liebert DataMate3000(S)
Precision cooling for Small Equipment Rooms

DataMate3000 series air conditioning is developed by Emerson Network Power


Co., Ltd. for small equipment rooms. The system provides 5.5kW , 7.5kW and
12.5kW cooling capacities and many configuration options.

Applications
 Mobile base stations and control centers
 Communications base stations
 Outdoor equipment rooms
 Microwave/Satellite earth stations
 Medium ,Small computer rooms

Features and Benefits


 High sensible cooling capacity and energy efficient. Saves 20-30% energy as compared to
"comfort" air conditioner
 Provides constant temperature and humidity, high air flow rate and low energy consumption to
meet specific reqirements of computer rooms
 Copeland scroll compressor provides high reliability, efficiency and maximum life
 Large LCD display, password protection and self diagnosis
 Wide input voltage range, allowing voltage fluctuation 20%
 Phase loss protection ,phase order detection, automatic regulation to phase disorder
 Automatic startup when utility is recovered
 Front access ,easy for maintenance and flexible installation
 Standard port for monitoring equipment
 Flexible and automatic switchover and alternative operation between master and slave

Dimensions And Weight


model W×D×H, mm Weight (kg) Capacity
DME05W 510×386×1740 80 5.5 kW
DME07W 510×386×1740 85 7.5 kW
Indoor model
DME07M 500×550×1900 150 7.5 kW
DataMate3000(s)
DME12M 500×550×1900 160 12.5 kW
DMC07W 702×408×626 34 7.5kW
Outdoor model
DMC12W 702×408×1238 58 12.5 kW

44
Business-Critical Continuity™

Liebert PEX
Precision cooling for medium/large equipment room

The Liebert PEX is the next generation precision air conditioning system from
Emerson Network Power. The PEX is the latest in a long line of advanced
products from the Liebert family designed to support business-critical
applications.

Applications
 Data Centres
 Telecom/CATV
 Computer Rooms
 Labs and Test Rooms
 Network Centres
 Production Facilities
 Hospitals and medical diagnostic rooms

Features and Benefits


 Front access for convenient maintenance. There is no need to keep back or sides clear
 The Liebert iCOM™ control system offers the highest capabilities of unit control, communication
and monitoring
 ICOM network provides a choice of Teamwork, Lead/Lag and Cascade functions
 A-Frame Evaporator Coils has larger surface to provide even air flow distribution. Its heat exchange
is highly efficient
 Unique fan driving system ensures stable system operation and more efficient airflow
 Infrared Humidifier, Full capacity achieved in 5-6 seconds using almost any water quality;
Approved for direct connection to potable water supplies; Autoflush™ cycle helps remove mineral
deposits
 All compressorised models are designed to operate on either HCFC R22 or HFC R407C refrigerants
 High kW to footprint ratio

45
Precision Air Conditioning

Dimensions And Weight


Total Capacity(kW)
model Weight (kg) L×W×H, mm
(24℃/50%RH)
P1020 20.0 365
P1025 23.1 375
853×874×1970
P1030 30.1 385
P1035 33.1 388
P2045 45.0 530
P2055 53.2 570
P2040 41.0 622
1704×874×1970
P2050 46.4 661
P2060 60.6 680
P2070 66.9 687
P3080 81.4 825
P3090 89.3 825 2553×874×1970
P3100 100.0 835

46
Business-Critical Continuity™

Liebert XD
Flexible, Energy-Saving Cooling Solutions For High Heat Density
Applications

Applications
 IDC
 Blade servers
 High density servers and communications switches
 Rooms existing high heat density

Features and Benefits


 Can cool more than 30 kW per rack
 Floor-mount, rack-mount and ceiling-mount modules, plus a choice of cooling capacities, cover
any application requirements
 Pumped refrigerant solutions are ideal for use around electronic equipment. No water into the
room
 Scalable – add or move fan coils as your needs
 Energy efficient. Total energy savings potential of up to 40% can be achieved with the Liebert XD
solution
 Minimal floor space requirements allow more room for IT equipment

Dimensions And Weight


Total Capacity(kW)
model Weight (kg) W×D×H, mm
(24℃/50%RH)
XDP160 140 372 965×864×1981
Main Unit
XDC160 130 817 1879×879×1981
XDO20 17.7 68 1829×610×572
XDV10 8.3 35 597×(749-1003)×355
Cooling Module
XDH20 19 112 300×1066×1982
XDH32 27 112 300×1066×1982

47
EMERSON NETWORK POWER.

THE GLOBAL LEADER IN ENABLING


BUSINESS-CRITICAL CONTINUITY.™

AC POWER

CONNECTIVITY

DC POWER

EMBEDDED COMPUTING

EMBEDDED POWER

MONITORING

MONITORING

OUTSIDE PLANT

POWER SWITCHING
& CONTROLS

PRECISION COOLING

RACKS & INTEGRATED


CABINETS

SERVICES
Managing critical equipment activity at multiple

sites and site monitoring around the clock. We SURGE PROTECTION


make it easy in today’s ROL-driven business

environment,with 24/7 remote and self-

monitoring systems and services that provide

continuous oversight of data centers,computer

rooms and network closets,as well as wireless,

wireline and enterprise telecom applications.

MONITORING. Yet another way Emerson Network

power enables Business-Critical Continuity™.

48
Business-Critical Continuity™

Emerson Power Equipment And Benefits


 Real time alarms
In case of monitored object's failure,

Environment Monitoring System the monitoring system can give alarm


within 30 seconds

 Multiple alarm reports


Emerson Power Equipment and Environment Monitoring System is applicable to There are sound & light alarm, printed
monitoring in real time and managing in unity power supply equipment (power alarm, paging alarm,mobile short
system, battery, UPS, generator and low-voltage distributor), airconditioning message alarm, E-mail alarm and voice
equipment and environment(door alarm, temperature, humidity, smoke alarm
detection, water immersion, infrared and scene)in telecom exchanges and base
 Flexible networking
stations
Flexible single or mixed networks can
After11-year development and optimization, Emerson monitoring system be set up through CE1, DDN/LL, ISDN,
has become a total solution including hardware, software and transmission PSTN and WAN
products. The monitoring solution can be customized to adapt to different
 Supports maintenance management
regions, different maintenance management mechanisms, different exchanges
Provides maintenance anlysis
and different transmission resources. The solution can meet the demands of
data,improves maintenance efficiency
monitoring the whole power equipment, environment of both fixed and mobile
and cuts maintenance cost
telecom networks
 Real time data collection
The system operates around the clock
Series and reports in real time the monitored
 Emerson power equipment and environment monitoring system equipment and environment's
 Single version system conditions. The system provides first-
hand data to evaluate equipment
conditions.
Applications
 Power equipment and environment monitoring system  Wide-range monitored objects
Applicable to monitoring power equipment, environment in switch site, base stations,transmission The monitored objects include HV
relay stations and LV distribution equipment,
power system, air conditioning,diesel
generator, battery and UPS; and also
Features Of Monitoring Center include environment data in relation
 supervision center SC consists of database server, console, printer and auxiliary equipment to temperature, humidity, water
The server collects, saves, analyzes and manages all monitoring data from monitoring end office immersion, smoke and door
SU. It gives various alarms (sound & light alarm, email, message, etc.) in case of monitored object's
failure

 Fexible Transmission Networking


Monitoring center SC, monitoring station SS and monitoring end office SU can form a wide area
network through IP, 2M, DDN, ISDN, PSTN and WAN

49
Monitoring

Communication Solution of
Monitoring System
IP Networking
Features:
 Using the available
 TCP/IP network in site
 Supportive of HTTP, TELNET, FTP
 Remote debugging and upgrade
 Applicable to:IDC room, MSC room, 3G base station, GPRS and CDMA site

Server Console

LAN

Host

IP network

IDU IDU

IDU IDU
IDU IDU

Server Console

LAN

Host

BRG-POOL
E1 E1

Emerson Power Equipment And Environment


Monitoring Software V4.39
Emerson IP Video Monitoring Software IDU IDU IDU IDU IDU IDU

50
Business-Critical Continuity™

Solution of large site


 The SU has IDU and sensors
 Applicable to: exchange station, switch centers ( MSC)
 Monitored equipment: HV and LV, generator diesel, AC distribution, rectifier, DC distribution,
battery strings,DC converter, inverters and air-conditioner, it can also be applied to acquire
theenvironment data, such as smoke detector, temperature and humidity sensor, access control
andwater detector
Generator
Monitoring
Center

Transmission
Low Voltage
Distribution
diesel level

DC Power IDU-HOST
Intrusion detector
For Door

Smoke Detector

Battery
Water Leakage

Communication line Temperature Air


Power line And Humidity Condition

solution of small site


 The SU has IDU and sensors
 Applicable to: base station (BTS)
 Monitored equipment: Low Voltage, DC power, air-conditioner, temperature and humidity sensor,
diesel level, smoke detector, door accessl and water detector

Transmission

IDU-HOST
diesel level
Intrusion detector
Smoke Detector
Water Leakage
DC Power
Temperature
And Humidity
Air
Power meter
Condition

51
Monitoring

IDU series product specifications


model BOM Description Functions
10 AI inputs (compatible with digital signals), 4 DI inputs, 1 THS
temperature/humidity input channel, 4 relay outputs, with 4 serial
IDU-HOST 02311425 IDU host
ports, 2 battery group voltage channels, 1 Ethernet port, 1 USB port and
2 expansion slots
Battery board 1 Capable of monitoring 24 battery cells, 1 charge/discharge current,
IDU-BAT1 02311434
(1 battery group) auto-switchover among measurement ranges of 2V, 6V and 12V
Battery board 2 capable of monitoring 48 battery cells, 2 charge/discharge currents,
IDU-BAT2 02311427
(2 battery groups) auto-switchover among measurement ranges of 2V, 6V and 12V
E1-IP network bridge 2 Ethernet ports (LAN), 1 E1 port (point-to-point, cannot be upgraded
IDU-BRG1 02311438
communication board to double loop
Double E1-IP network bridge
IDU-BRG2 02311429 2 Ethernet ports (LAN), 2 E1 ports (supportive of double loop)
communication board
Temperature measurement range: -10℃~50℃. Precision: +/-2℃
External THS temperature/
IDU-THS 33030018 Humidity measurement range: 5~95%RH. Precision: +/-5% (20~
humidity sensor
80%RH, 25℃)

IDU series product mechanical specifications


Name Sizes Weight
IDU-HOST 440 ± 1mm × 295 ± 1mm × 44 ± 1mm ≤5kg
IDU-BAT1 122 ± 1mm × 185 ± 1mm × 1.6mm ≤0.5kg
IDU-BAT2 122 ± 1mm × 185 ± 1mm × 1.6mm ≤0.5kg
IDU-BRG2 122 ± 1mm × 185 ± 1mm × 1.6mm ≤0.5kg
BRG-POOL 440 ± 1mm × 295 ± 1mm × 44 ± 1mm ≤5kg

The features of IDU include


 IP-network based, supportive of TCP/IP and network protocols such as HTTP, TELNET, FTP, TFTP
and DHCP
 TELNET remote debugging
 Highly integrated, with superb processing and storing ability of bottom data
 Integrated connection with multiple intelligent devices
 Low cost image monitoring solution (USB image and anti-burglary)
 High standard lightning protection for all ports. Built-in SPDs are used for all ports, with lightning
protection ability 2-times higher than the international standard
 Hardware self-diagnostic ability, including detection of E1 cable status, detection of board
insertion fault, and measurement of CPU usage
 Network management function: IP flux statistics, IP contradiction auto-detection, and network
topology structure
 Remote on-line upgrading of software
 IP networking mode, supportive of transmission modes of double loop, ADSL and E1
 Supportive of ADSL static IP address
52
Business-Critical Continuity™

BRG-POOL
 BRG-POOL bridge pool ( BRG-POOL) is conversion device for E1-IP transfer function. It provides
eight independent E1-IP transfer channels and can be flexibly configured through CONSOLE
portaccording to the actual application conditions and meet the requirements of different
networkingmodes

BRG-POOL specifications
model Voltage input range Power
BRG-POOL -38V ~ -60Vdc <20W
model Dimensions Weight
BRG-POOL 440mm × 295mm × 44mm < 5kg
parameters Transmission distance
10/100M, half/full-duplex self-adaptable, RJ45 port,
100m max.
Ethernet cable intercross function

53
EMERSON NETWORK POWER.

THE GLOBAL LEADER IN ENABLING


BUSINESS-CRITICAL CONTINUITY.™

AC POWER

CONNECTIVITY

DC POWER

EMBEDDED COMPUTING

EMBEDDED POWER

EMBEDDED POWER

MONITORING

OUTSIDE PLANT

POWER SWITCHING
& CONTROLS

PRECISION COOLING

RACKS & INTEGRATED


CABINETS

SERVICES

SURGE PROTECTION

Making power conversion easy for IT and

communications equipment. We deliver a broad

offering of Astec® and Artesyn® solutions,

including AC/DC and DC/DC power supplies,

adapters,chargers and power accessories.

EMBEDDED POWER.Yet another way Emerson

Network power enables Business-Critical

Continuity™.

54
Business-Critical Continuity™

GIE4805/2A/500-2
Mini Power System

Key Features
 1 U Height and designed for 19” racks
 Integrated Battery Low Voltage Disconnection function

Key Benefits
 Space efficient solution with all functions integrated

GIE4805/2A/500-2
 Nominal system voltage: -48 V
 System rated output power @ - 54 V: 540 W
 Rectifier rated output power @ - 54 V: 270 W
 DC distribution branch
Branch 1 10A(FUSE)
Branch 2 10A(FUSE)
Battery 10A(FUSE)
 AC input range: 90-264 V AC
 Safety EN 60950
 Sub rack dimensions (H x W x D): 43 x 482 x240mm

55
Embedded Power

GEPS4820F/01-10/22-EN
Mini Power System

Key Features
 1 U Height and designed for 19”racks
 Integrated LVD and priority load

Key Benefits
 Space efficient solution with all functions integrated

GEPS4820F/01-10/22-EN
 Nominal system voltage: - 48 V
 System rated output power @ - 54 V: 1600 W
 Rectifier rated output power @ - 54 V: 800 W
 DC distribution branch
Branch 1 10A(FUSE)
Branch 2 20A(FUSE)
Battery 20A(FUSE)
 AC input range: 90-290 V AC
 Safety EN 60950, UL 60950
 Sub rack dimensions (H x W x D): 45.6 x 482.6 x 325mm

56
Business-Critical Continuity™

GIE4815/2A/1.7KW
Mini Power System

Key Features
 2 U Height and designed for 19”racks
 Integrated AC distribution, LVD and priority load
 Remote monitoring and dry contacts

Key Benefits
 Space efficient solution with all functions integrated

GIE4815/2A/1.7KW
 Nominal system voltage: - 48 V
 System rated output power @ - 54 V: 1700 W
 Rectifier rated output power @ - 54 V: 850 W
 DC distribution branch
Branch 1,2 5A(FUSE)
Branch 3 10A(FUSE)
Branch 4,5 20A(FUSE)
Battery 50A(MCB)
 AC input range: 90-290 V AC
 Safety EN 60950, UL 60950
 Sub rack dimensions (H x W x D): 88 x 483 x 350mm

57
Embedded Power

GIE4815/3A/2.55KW
Mini Power System

Key Features
 3 U Height and designed for 19”racks
 Remote monitoring and dry contacts
 Integrated AC distribution, surge protection, LVD and priority load

Key Benefits
 Space efficient solution with all functions integrated on one shelf
 Robust and well proven design for tropical climates
 Provides reliable DC supply

GIE4815/3A/2.55KW
 Nominal system voltage: - 48 V
 System rated output power @ - 54 V: 2550 W
 Rectifier rated output power @ - 54 V: 850 W
 DC distribution branch
Branch 1, 10A(MCB)
Branch 2,3 20A(MCB)
Branch 4, 50A(MCB)
Battery 63A(MCB)
 AC input range: 90-290 V AC
 Safety EN 60950, UL 60950
 Sub rack dimensions (H x W x D): 133 x 465 x 360mm

58
Business-Critical Continuity™

GIE4820/3A/3.45KW
Mini Power System

Key Features
 3 U Height and designed for 19”racks
 Remote monitoring and dry contacts
 Integrated AC distribution, surge protection, LVD and priority load

Key Benefits
 Space efficient solution with all functions integrated on one shelf
 Robust and well proven design for tropical climates
 Provides reliable DC supply

GIE4820/3A/3.45KW
 Nominal system voltage: - 48 V
 System rated output power @ - 54 V: 3450 W
 Rectifier rated output power @ - 54 V:1150 W
 DC distribution branch
Branch 1, 10A(MCB)
Branch 2,3 20A(MCB)
Branch 4, 50A(MCB)
Battery 63A(MCB)
 AC input range: 90-290 V AC
 Safety EN 60950, UL 609 50
 Sub rack dimensions (H x W x D): 133 x 465 x 360mm

59
Emerson Network Power Co., Ltd.
No. 1 Kefa Rd., Science & Industry Park
Nanshan District 518057, Shenzhen, China
Phone: +86-755-8601-0808

Emerson Network Power.


The global leader in enabling Business-Critical Continuity™. www.emersonnetwork.com.cn

AC Power Systems Embedded Power Outside Plant