Anda di halaman 1dari 6

A member of the Set Point group TRANSFORMER

3 6
I S S U E
OIL ANALYSIS
By Neil Robinson, B.Sc. Hons.

A basic introduction to an essential part of a


cost-efficient maintenance programme
It is well known networks. Extreme reliability is
that regular oil demanded of electric power
analysis is distribution and, even though the
extremely failure risk of a transformer and
useful in other oil-filled electrical equipment
monitoring the is small, when failures occur they
condition of inevitably lead to high repair
e n g i n e s , costs, long downtime and very
drivetrains, real safety risks. Moreover,
hydraulics, transformers are too expensive
turbines and to replace regularly and must be
many other properly maintained to maximise
Neil Robinson types of oil their life expectancy.
lubricated equipment. The same
can be said for transformer oils By accurately monitoring the
which are used to insulate many condition of the oil, many types
transformers and other electrical of faults can be discovered
distribution equipment. The before they become serious
analysis of transformer oils not failures and outages can
only provides information about potentially be avoided.
the oil, but also enables the Furthermore, an efficient
detection of other potential approach to maintenance can
problems, including contact be adopted and the optimum
arcing, ageing insulating paper intervals determined for
and other latent faults and is an replacement. Some of the checks
indispensable part of a cost- are relatively simple: on the
efficient electrical maintenance operation of the gas relays,
programme. on the operation of the on-load
tap-changer, on oil leaks, etc.

ENSURING However, breakdown of one of


the most crucial elements, the
TRANSFORMER oil / paper insulating system, can
RELIABILITY only reliably be detected by
routine oil analysis. By measuring
certain physical and chemical
Transformer maintenance has properties of the oil, in addition
evolved over the past 20 years to the concentrations of certain
from a necessary item of dissolved gases, a number of
expenditure to a strategic tool problem conditions associated
in the management of electrical with either the oil or the
transmission and distribution transformer can be determined.

WEAR CHECK AFR ICA IS AN ISO9001 AND ISO14001 R EGIS T ER ED COMPAN Y


The following are some common tests the oil. An increase in acid number often
performed on electrical transformer oils: goes hand in hand with a decrease in dielectric
strength and increased moisture content
as shown in Figure 1. Again, just like their
MOISTURE CONTENT
industrial cousins, the acid content of
One of the most important functions of
transformer oils is determined by
transformer oil is to provide electrical potentiometric titration with potassium
insulation. Any increase in moisture content hydroxide.
can reduce the insulating properties of the
oil, which may result in dielectric breakdown.
Sludge and
Water and oil, due to their differing chemical varnish
properties are not mutually soluble. However,
Paper degradation
up to a certain limit, a small amount of water Oil oxidation
Temperature Temperature
will dissolve in the oil. This limit is a function
of the temperature of the system and the
solubility increases exponentially with Oil Paper
increasing temperature. This is of particular
importance with fluctuating temperatures
Oxygen Metal Water
because, as the transformer cools down, catalysts

any dissolved water will become free, Acids


and
Paper chain
scissors
hydroperoxides
resulting in poor insulating power and oil + water

degradation. A point to note is that as the


oil ages in service, a certain amount of Figure 1
oxidation occurs which changes the chemical
make up of the oil. This, in turn, allows more
DIELECTRIC STRENGTH
water to dissolve. In addition, many
The dielectric strength of a transformer oil
transformers contain cellulose-based paper,
is a measure of the oil’s ability to withstand
which is used as insulation in the windings.
electrical stress without failure. Because
Again, excessive moisture content can result
transformer oils are designed to provide
in the breakdown of this paper insulation
electrical insulation under high electrical
with a resultant loss in performance. The
potentials, any significant reduction in the
moisture content of the oil is determined
dielectric strength will indicate that the oil is
using a coulometric Karl Fischer instrument.
no longer able to perform this vital function.
This is an extremely sensitive test and can
Some of the things that can cause a reduction
detect water at levels down to a few parts
in dielectric strength include contaminants
per million.
such as water, sediment, conducting particles,
ACID NUMBER oil degradation by-products and cellulose
Just like lubricating oils, transformer oils paper breakdown. The test method for
are oxidised under the influence of excessive determining dielectric strength is relatively
temperature and oxygen, particularly in the simple and involves applying an AC voltage
presence of small metal particles which can at a controlled increasing rate to two
act as catalysts. Oxidation products are electrodes immersed in the transformer oil.
usually acidic in nature and result in an The gap is a specified distance and when the
increase in acid number. Further reaction current arcs across this gap the voltage
of these acids with the bulk oil can result in recorded is used to determine the dielectric
sludge and varnish deposits. In the worst strength.
case scenario, the oil canals become blocked
and the transformer is not cooled adequately, POWER OR DISSIPATION FACTOR
which further exacerbates oil breakdown. The power factor of a transformer oil is the
Furthermore, an increase in the acidity has ratio of true power to apparent power and
a damaging effect on the cellulose paper. is a measure of the current leakage through
Oil degradation by-products such as acids the oil, which in turn is a measure of the
and hydroperoxides also generally have the contamination or deterioration of the oil. In
ability to conduct an electrical charge, which a transformer, a high power factor is an
in turn reduces the insulating properties of indication of significant power loss in the

2
transformer oil, usually as a result of
contaminants such as water, oxidised oil

Degree of polymerisation
and cellulose paper degradation. It may also
be any substance in the oil that either resists
or conducts electricity differently to that of
the oil itself, which may include diesel fuel,
lubricating oil and kerosene. The test is not
specific in what it detects and is usually
carried out at elevated temperatures
because contaminants that affect the test
may remain undetected at 25ºC and only
reveal themselves at >90ºC.
Furanic concentration

INTERFACIAL TENSION (IFT)


The interfacial tension of transformer oil is Figure 2
related to its deterioration. Transformer oil
is generally a hydrocarbon and thus The cellulose materials are the weakest link
hydrophobic. However, when the sample in the insulation system. Since the life of the
undergoes oxidative degradation, oxygenated transformer is actually the life of the cellulose
species such as carboxylic acids are formed, insulation, and degradation of the cellulose
which are hydrophilic in nature. Interfacial is irreversible, the decay products should be
tension is the surface tension of a sample removed before they can do any further
of the oil carefully floated on top of a layer damage to the cellulose. With proper
of water. The more hydrophilic the oil maintenance the cellulose can virtually have
becomes, the lower the value of the surface an indefinite life. To test for furanics, a
tension between the two liquids. Studies sample of the oil is obtained and certain
have shown that there is a definite chemical techniques are used to extract the
relationship between acid number and IFT. furans from the oil. The extract is then
An increase in acid number generally shows analysed using a process called high
a decrease in IFT. However, when there is performance liquid chromatography (HPLC).
a loss in IFT without the corresponding The results are usually reported in terms of
increase in acid number, it is generally parts per billion (ppb).
because of contamination with another
hydrophilic substance not derived from DISSOLVED GAS ANALYSIS (DGA)
oxidation of the oil. The analysis of gases from petroleum
products has been performed for decades
FURANICS OR DEGREE using gas chromatography. However, this
OF POLYMERISATION (DP) technique was not applied specifically to
The solid insulation (cellulose-based products) transformer mineral oils until the late 1960s
in transformers degrades with time at or early 1970s and is now commonly called
rates which depend on the temperature, dissolved gas-in-oil analysis (DGA). DGA has
moisture content, oxygen and acids in the become a standard in the electrical
insulation system. Heat and moisture are maintenance industry throughout the world
the main enemies of the solid paper insulation and is considered to be the most important
with oxidation as the primary culprit. oil test for transformer oils in electrical
When degradation occurs, the cellulose apparatus. More importantly, an oil sample
molecular chains (polymers) get shorter. can be taken at any time from most
Chemical products such as furanic derivatives equipment without having to take it out of
are produced and dissolve in the service, allowing a “window” inside the electrical
transformer oil. Of the furanic compounds, apparatus that helps with diagnosing and
2-furaldehyde is the most abundant. Its troubleshooting potential problems.
concentration in oil has been related to the
degree of polymerisation (DP) and As the insulating materials of a transformer
consequently to the physical strength of the break down from excessive thermal or
solid insulation (see Figure 2). electrical stress, gaseous by-products form.

3
The by-products are characteristic of the
KEY GASES GENERAL FAULT
type of incipient fault condition, the materials
CONDITION
involved and the severity of the condition.
Indeed, it is the ability to detect such a Methane, Ethane, Thermal condition
variety of problems that makes this test Ethylene and small involving the oil
amounts of Acetylene
such a powerful tool for detecting incipient
fault conditions and for root cause Hydrogen, Methane Partial discharge
and small amounts of
investigations after failures have occurred. Acetylene and Ethane
Dissolved gases are detectable in low
Hydrogen, Acetylene Sustained arcing
concentrations (ppm level), which usually and Ethylene
permits early intervention before failure of
Carbon Monoxide and Thermal condition
the electrical apparatus occurs, and allows Carbon Dioxide involving the paper
for planned maintenance. The DGA technique
involves extracting or stripping the gases Table 1: Categories of key gases and general fault condition
from the oil and injecting them into a gas
chromatograph (GC). time analysis on service-aged transformers
(several years old), which could contain
Typical gases generated from mineral oil / residual gases from previous events.
cellulose (paper and pressboard) insulated
transformers include: Some gas generation is expected from normal
ageing of the transformer insulation and it
Hydrogen H2 is therefore important to differentiate
Methane CH4 between normal and excessive gassing rates.
Ethane C2H6 Normal ageing or gas generation varies with
Ethylene C2H4 transformer design, loading and type of
Acetylene C2H2 insulating materials. Routinely, general gassing
Carbon Monoxide CO rates for all transformers are used to define
Carbon Dioxide CO2 abnormal behaviour. Specific information for
a family of transformers can be used when
Additionally, oxygen and nitrogen are always sufficient dissolved gas-in-oil data is available.
present. Their concentrations vary with the
type of preservation system used on the Acetylene is considered to be the most
transformer. Also, gases such as propane, significant gas generated. An enormous
butane, butene and others can be formed amount of energy is required to produce
as well, but their use for diagnostic purposes acetylene, which is formed from the
is not widespread. The concentration of breakdown of oil at temperatures in excess
the different gases provides information of 700ºC. Excessively high overheating of
about the type of incipient fault condition the oil will produce the gas in low
present as well as the severity. For example, concentrations. H o w e v e r, higher
four broad categories of fault conditions concentrations are typically symptomatic of
have been described and characterised in sustained arcing, a more serious operational
Table 1. issue that can cause a transformer failure
if left unchecked.
The severity of an incipient fault condition is
ascertained by the total amount of DGA is used not only as a diagnostic tool
combustible gases present (CO, H2, C2H2, but also to stem apparatus failure. Failure
C2H4, C2H6, CH4), their rate of generation of a large power transformer not only results
and their ratios with one another. Generally, in the loss of very expensive equipment but
transformers will retain a large portion of it can cause significant collateral damage as
the gases generated and therefore produce well. Revenue losses due to operational
a cumulative history of the insulating outages may be the least worrisome
materials’ degradation. This is an important consequence of a failure. Replacement of
tool for detecting and trending incipient that transformer can take up to a year if
problems. However, it also means that care the failure is not catastrophic and can result
is needed in interpreting values for a first in tremendous revenue losses. If the failure

4
is catastrophic, then additional losses could costly decontamination work.
occur, such as adjacent transformers,
environmental problems from the release PCDDs and PCDFs cause damage and
of oil (which could be as much as 20 000 death in doses as low as 1ppb to
litres), and the resulting fire that would have 5000ppb. They are some of the most
to be contained and smothered. In order to potent cancer promoters known and can
avoid such a failure, the sample frequency damage organs such as the liver, kidney
of most large power transformers is between and digestive tract as well as cause
one and three years. However, sampling miscarriage and sterility.
frequencies will increase as an incipient fault
is detected and monitored. Often sampling Methods of PCB analysis
frequencies are dictated by insurance Current methods of analysis are divided
requirements, which often stipulate that into two major groups: PCB specific and
annual transformer oil analysis must be PCB non-specific. Non-specific methods
conducted to ensure continued coverage. test for PCBs indirectly by detecting
one of the components of the PCB
PCB ANALYSIS compound, usually chlorine. In general,
PCBs (polychlorinated biphenyls) are a group non-specific methods are quicker and
of synthetic oil-like chemicals of the less expensive than the specific methods.
organochlorine family. Until their toxic nature However, these tests are susceptible to
was recognised and their use was banned false positive results, since the test does
in the early 1980s, they were widely used not detect PCB itself.
as insulation in electrical equipment,
particularly transformers. Three types of Specific methods utilise some type
PCBs are normally used in electrical of chromatography to separate
transformers: Aroclor 1242, 1254 and PCB molecules from each other and
1260, commonly known by various brand interfering compounds. It is not a case
names which include Askarel, Chlorectol, of simply finding an easily quantifiable
Elemex, Inerteen and Pyranol. compound, but of quantifying a complex
mixture of compounds. Of the three
One of the most important problems with major chromatography types, gas
PCBs is that they concentrate in the fatty chromatography (GC), thin layer
parts of microorganisms. This concentration chromatography (TLC) and liquid
factor between the organism and the water chromatography, GC is the preferred
can be as much as a million times. and most extensively used method.
Concentrations are further amplified as the
microorganisms become food for animals Terminology associated with PCBs is
further up the food chain, ultimately ending defined below
up in humans. PCBs are very stable and
their degradation process is slow, making Non PCB
for yet greater amplification in organisms. Any fluid, including that in electrical
Although not overly toxic in themselves, equipment and any item that has a
PCBs are poisons, which have been shown measurable PCB concentration of less
to cause damage to the reproductive, than 50ppm of PCB, is considered a
neurological and immune systems of wildlife non-PCB item.
and humans.
PCB contaminated
Far more serious are the risks of a fire or Any fluid, including that in electrical
an explosion. At temperatures around equipment, and any item which has a
500ºC, extremely toxic compounds - measurable PCB concentration of 50ppm
polychlorinated dibenzofuranes (PCDF) and or greater but less than 500ppm is
polychlorinated dibenzodioxins (PCDD) - are regarded as being PCB contaminated.
formed. Small amounts of these compounds Transformer oil that has not been tested
have been found at accidents where must be classified as PCB contaminated
transformers and capacitors have been until shown to be otherwise.
exposed to fire or have exploded. Even if
the amounts have been extremely small and PCB item
have caused no personal injuries, it has been Any fluid, including that in electrical
necessary to perform very extensive and equipment and in any item which has a

5
measurable PCB concentration equal to or dependent on the quality of the oil sample
greater than 500ppm, is regarded as a PCB that is sent to the lab. A sampling point on
item. Once the PCB status is determined, any equipment should be identified and clearly
a sticker is issued and fixed to the item in labelled for the technician. Also, as with
question. This allows for quick reference and sampling locations in other types of
ensures that potential cross contamination equipment, the same location should be used
is avoided during future sampling, each time a sample is collected to ensure
maintenance and decommissioning if representative conditions are tested.
necessary. This point should be located in a place where
a live oil sample can be collected rather
Blending PCB contaminated oil with virgin than in an area where the oil is static.
or other oil to meet the legal requirements
is obviously an illegal practice that has been Just like machinery oil analysis, electrical
shown to happen from time to time. transformer oil analysis can play a vital role
This practice simply has the effect of in preventing unscheduled outages in electrical
contaminating virgin oil supplies and ensures transmission and distribution equipment by
that the PCBs persist in the environment, determining the condition of the equipment
leading to further contamination. itself, as well as other vital components,
including the condition of the oil and the
Greater detail on PCBs, their management, cellulose paper insulation. Regular routine oil
disposal and applicable legislative issues analysis should be the cornerstone of any
surrounding them, can be viewed on the PM programme for all critical oil-filled electrical
Wearcheck web site (www.wearcheck.co.za) equipment, including transformers, circuit
in an article entitled “Guide for PCB breakers and voltage regulators.
management of insulating oils in South Africa”
by I.A.R. Gray under the Additional Info REFERENCES
section.
Anne Reygaerts – Laborelect, courtesy of
Noria Corporation.
PROPER NTT WorldWide Technical Bulletins
TRANSFORMER Lance R. Lewand, Doble Engineering
SAMPLING Company, courtesy of Noria Corporation

I.A.R. Gray - Transformer Chemistry Services


As with machinery oil analysis, the ability of
transformer oil analysis to provide an early Neil Robinson is managing director of
warning sign of a problem condition is Wearcheck Africa.

Copies of previous Technical Bulletins can be accessed


on Wearcheck’s web site: www.wearcheck.co.za

A member of the Set Point group

Publications are welcome to reproduce articles or extracts from them providing they acknowledge Wearcheck Africa, a member of the Set Point group.

Felicity Howden Public Relations 6/2006


6

Anda mungkin juga menyukai