Component Selection

What components there are available

What components to use & where


Minimum configuration

Into the real world

Hazardous area

Some rules
Profibus Process Event, Glasgow October 2009
Master3
Master1

Master2
PSU CPU
Profibus DP

Remote I/O etc.

Basic configuration normally uses Profibus DP

Profibus Process Event, Glasgow October 2009


The Master controls all cyclic
communications
The Master is configured using a
software tool for your PLC/DCS
Use a .gsd file as the common
interface between all devices and
the master
You can have more than one master on
a network
A slave is locked to a cyclic master

Profibus Process Event, Glasgow October 2009


Cyclic Data Transfer

Single master system

Master Cyclic
operation:
MÆS1, S1ÆM
MÆS2, S2ÆM
MÆS3, S3ÆM
MÆS4, S4ÆM
MÆS1, S1ÆM
Slave Slave Slave Slave MÆS2, S2ÆM
1 2 3 4 etc.

© Manchester Metropolitan University


Profibus Process Event, Glasgow October 2009
Cyclic Data Transfer

Dual master system


Token
Token
Cyclic operation:
M1ÆS1, S1ÆM1
M1ÆS2, S2ÆM1
Master Master M1ÆS4, S4ÆM1
Token
Token
1 2 M1ÆtokenÆM2
M2ÆS3, S3ÆM2
M2ÆS5, S5ÆM2
M2ÆtokenÆM1
M1ÆS1, S1ÆM1
M1ÆS2, S2ÆM1
Slave Slave Slave Slave Slave etc.
1 2 3 4 5
© Manchester Metropolitan University
Profibus Process Event, Glasgow October 2009
For Process Automation devices you
need a converter between DP & PA
DP uses RS485
PA uses Manchester Bus Power
Different converters exist. Simple
couplers or link modules
Each has its areas of use, benefits
and disadvantages

Profibus Process Event, Glasgow October 2009


Conversion between RS485 and
Manchester Bus Powered communications

4
To
e
ul
7
volts
d
mo
k
lin Profibus PA Manchester
or
r Bus Powered multi-drop
ple
ou
Profibus DP C Current/mA 0 1 1 0 0
RS485 multi-drop
+9mA

-9mA

time

© Manchester Metropolitan University


Profibus Process Event, Glasgow October 2009
Master3
Master1

Master2
PSU CPU Powered
termination.

Link
SK3 module
coupler allows non-
Coupler usesuses
unique
unique
unique addressing,
addressing, no uses
addressing, no
one address on
address the bus
addressononthe
thebusbus Remote I/O etc.
for allbaud
but PA devicesis and
butfull rate
fixed baud rate
allows full baud rate
available PROFIBUS-PA

Profibus Process Event, Glasgow October 2009


Simple coupler (P&F / Siemens)
Master class 2 Master class 1

PROFIBUS-DP

For 31 devices approximately


half a second cycle time
PROFIBUS-PA

Unique addressing only


15 ms
15 ms
15 ms
© Endress & Hauser
Profibus Process Event, Glasgow October 2009
• Two variants of the DP/PA Coupler: Ex and Non-Ex
• Converts the signals from DP (RS 485) to PA (IEC
61158-2)
• Transparent to master and slave
• No configuration necessary
• Fixed baud rate of 45.45 or 93.75 kBit/s on DP
network
• Contains termination (one end) for the Profibus PA
bus
• Powers the PA field devices

Profibus Process Event, Glasgow October 2009


Link module (Siemens)
Master class 1

12 PROFIBUS-DP
13 etc
up to 12 Mbit/s
1 ms

Link T SEG ~ 500 msec

PROFIBUS-PA

14
12 13

Non-unique addressing
15 ms 15 ms
15 ms
© Endress & Hauser
Profibus Process Event, Glasgow October 2009
• The LINK contains at least one IM157 module and one DP/PA
coupler

Æ the Link acts as a DP-Slave to the DP-Master


Æ the Link acts as a master to the PA-Slaves
Æ max. I/O range for all PA devices:
Æ244 Byte Input + 244 Byte Output

• Address range on PROFIBUS-DP between 0-125


• Address range for slaves on PROFIBUS-PA from 3-125
• Up to 5 DP/PA couplers can be connected to one IM157 module
•Remember the 244 byte limit
• 9.6 kBit/s to 12 Mbit/s (standard bus parameters)
• GSD generator required when used outside a Siemens
environment

Profibus Process Event, Glasgow October 2009


Link module
IM 157 1..5 DP/PA Coupler(s)

© Endress & Hauser


Profibus Process Event, Glasgow October 2009
Where now?
Profibus PA can go 1900 metres in
the field with up to 31 slaves
Junction boxes are often used to
distribute PA around the plant
Current limiting devices can be
employed to protect segments
This enables a highly flexible system
to be created

Profibus Process Event, Glasgow October 2009


Master3
Master1

Master2
PSU CPU

Remote I/O

Limits apply on spur lengths Spurs can be protected

Profibus Process Event, Glasgow October 2009


Possible faults in a PROFIBUS PA segment

IM 157 redundant

DP/PA coupler, non redundant

1
4

3 PROFIBUS PA 2 bus termination


backbone
PROFIBUS DP

... max. 31 devices per coupler

spur

spur

failure effect estim. of harm


1 breakdown of PA Coupler breakdown of up to 31 devices

2 short-circuit / wire break on backbone breakdown of up to 31 devices

3 short-circuit / wire break on spur breakdown of typ. 1-4 devices

4 missing bus termination disturbance of communication

© Endress & Hauser


Profibus Process Event, Glasgow October 2009
Redundant systems
Using special devices the PA segment
can be maintained even under fault
conditions

Offers a safe and reliable system for


critical plant

Profibus Process Event, Glasgow October 2009


Fault tolerant PROFIBUS PA - Overview

PROFIBUS DP
M
DP/PA coupler, redundant

IM 157, redundant AFS

PROFIBUS PA
PROFIBUS DP

M
DP/PA coupler, redundant

AFD
IM 157, redundant

PROFIBUS PA

© Siemens Ltd
Profibus Process Event, Glasgow October 2009