Super Series

Relay &Protection Microcomputer Test System

Operation Manual

(V1.2)

Guangzhou Bonzn Electric Technology Co., Ltd.

May. 2010
Chapter One General.......................................................................................................................................1
Chapter Two Brief Intr oduction......................................................................................................................2
I.Characteristics of Product.....................................................................................................................2
II Technical Parameters...........................................................................................................................4
III. Product Structure...............................................................................................................................6
Chapter Three Basic Operation.....................................................................................................................10
I. Circuit connection..............................................................................................................................10
II. Software Operation...........................................................................................................................13
1. Operation guide for panel keys.............................................................................................13
2. Basic software operation.......................................................................................................13
2.1 Main menu......................................................................................................................14
2.2 Function menu.................................................................................................................15
2.3 File service......................................................................................................................17
III. Software Upgrade............................................................................................................................20
Chapter Four Test Method.............................................................................................................................21
I. U/I Test..............................................................................................................................................21
II. DC Test.............................................................................................................................................24
III. Impedance Characteristics...............................................................................................................26
IV. Power Direction Test.......................................................................................................................29
V. I-T Test..............................................................................................................................................31
VII. Differential Relay..........................................................................................................................36
VIII. Harmonic Test..............................................................................................................................38
IX. Differential Protection.....................................................................................................................40
X. Distance Protection..........................................................................................................................48
XI. Zero Sequence Protection...............................................................................................................51
XII. Setting Group Test.........................................................................................................................53
XIII. State Sequence..............................................................................................................................56
XIV. Synchronization Test....................................................................................................................58
XV. Special Test....................................................................................................................................60
XVI. Transplay (Fault Reappearance)...................................................................................................62
XVII. Oscillation Test...........................................................................................................................64
XVIII. Metering Instrument..................................................................................................................66
XIX. Hardware Checkout......................................................................................................................68
XX. Low Voltage Protection.................................................................................................................70
Chapter Five Analyses and Solutions of Common Problems........................................................................72
Attached accessories:....................................................................................................................................74
1 Relay &Protection Microcomputer Test System

Chapter One General

Relay &Protection microcomputer test device (hereinafter referred to as tester) is an


important test tool for ensuring safe and reliable running of power system. With the rapid
development of computer technology, microelectronic technology and electrical and
electronic technology, continuously emergence of high-performance relay protection test
device by using the latest technological achievements is the inevitable trend of technical
progress.
Guangzhou Bonzn Electric Technology Co., Ltd. was founded in Jan. 2005, and its
precursor is Guangzhou Bangde Electric Automation Co., Ltd.
Bonzn Company integrates the production, debugging, sales and after-sale service of the
tester and acts as a pioneer for the development, production and sales of the relay protection
test device and initiates the advanced field for relay protection and even for microcomputer
protection test technology. It takes the lead in creating the novel industry of relay protection
test all over China, and has formed a leading pattern for this kind of products. Since early
1990s, it has successfully developed MRT-02, MRT-02D, MRT-02DS and Super-007 series of
products, etc. Through more than a decade's efforts, we have witnessed a great success and
created a good brand. And all these could not be obtained without all old and new friends
cooperating with our company.
Super series relay &protection microcomputer test device is the latest product of our
company. It is produced by referring to Technical Condition for DL/T624-1997
Microcomputer Relay &Protection Test Devic e issued by the original Power Department,
extensively listening to the opinions of users, carefully reviewing the developing and
producing experience of the former generations of products and adopting the modern latest
digital technology, high precision electronic apparatus, microcomputer system and new
circuit and new structure. It can independently finish device test in professional fields of
microcomputer protection, relay protection, excitation, metering, fault recording, etc. and is
widely applied to scientific research, production and electrical test sites in electric power,
petrochemical, metallurgy, railway, aviation and military industries.
Don’t hesitate to enquire us if you have any question.
2 Relay &Protection Microcomputer Test System

Chapter Two Brief Introduction

I.Characteristics of Product
1. Embedded host machine equipped with Complex Programmable Logic Device (CPLD)
The host machine adopts a high-speed and high-performance embedded microcomputer system equipped
with a CPLD, so it has high response speed, wide transmission band and can producing high-density fitting
sine wave with 500 points per cycle for the fundamental wave. The output waveform is smooth, and no
harmonic component exists. Since there are a great number of output points and accurate filtering circuit is
used, the distortion of the waveform is very small. In a harmonic output process, a high density of 55 points
per cycle can be achieved for even the ninth harmonic at 450Hz. Meanwhile, the software has very
powerful man-machine conversation and on-line assistance functions, and can control any test parameter.
2. Twelve-path synchronous D/A output in a single machine
A 16-digit high-accuracy DAC chip is used to ensure high fitting waveform accuracy and good linearity.
Twelve paths of analog signals can be output at the same time so as to meet full-range tests, such as
transformer protection and standby power source automatic put-in.
3. High-accuracy linear power amplifier and synchronous output of six-phase voltage and
six-phase current
Voltage and current amplifiers are designed elaborately to realize AC/ DC sharing, and the output stage
adopts unique high-accuracy ultra-linear amplifying technique. High accuracy and good reliability can be
achieved, and six-phase AC voltage and six-phase AC current can be output at the same time. Each phase
of AC voltage output is as high as 130V, 70VA, while full AC current output is as high as 180A. The DC
voltage output is up to 300V, 130VA.
4. Host machine-integrated single cabinet structure with big screen LCD and complete
interface has obtained appearance patent
The device uses an 8.0" big-screen high-resolution-graph liquid crystal display (LCD) screen with dot
matrix of 640×480. The operation interface and the test result are displayed fully in Chinese, and all
operation processes are set on the display screen. The display screen displays intuitively and clearly.
The device is operable by an external keyboard, and external keyboard/ mouse interface is provided.
Furthermore, two USB interfaces and two RS232 interfaces are provided to communicate with an external
computer and other equipment. It only requires 220V AC power and runs immediately after being started
up. It is convenient to carry, and very suitable for flow test and field work.
5. Intelligent self-protection
A radiating structure of the latest design is used to ensure excellent ventilation state. Phenomena
endangering the safety of the device, such as overcurrent, overvoltage, overload, short circuit, over-high
temperature and data abnormity can be judged at the same time, and even faulty operation does not go so
far as to damage the device. Besides, the alarming indicating lamp of the device turns red and the amplifier
is switched off automatically when danger signal, such as external voltage enters the tester through a
terminal.
6. Plentiful Binary and powerful software function
3 Relay &Protection Microcomputer Test System

The device has eight binary inputs ( A B C R a b c r ) and four binary outputs. The binary input contact is
compatible with the idle contact and the 0-250Vdc electric potential contact, and can be recognized
intelligently. The device is operated by 23 keys via the big liquid crystal display screen, and all interfaces
are displayed in Chinese. The device can finish checking most on-site tests. Meanwhile, it can conveniently
finish testing protective devices produced by foreign manufactures, such as ABB, Siemens and AREVA.
The device can be placed vertically or horizontally, and allows off line operation as well as operation with
externally connected PC machine. The test result can be sorted out and recorded automatically into a test
report for easy reference, and can also be directly stored in a U disk, so it can be conveniently transferred to
the externally connected PC machine for editing, printing, etc. The software can be upgraded simply and
rapidly through the U disk or through downloading of the externally connected PC machine without
modifying any hardware.
The software has powerful auxiliary computing function, and can automatically calculate positive, negative
and zero-sequence voltages and currents and primary and secondary active power, reactive power and
power factors.
The six -phase voltage and six -phase current outputs can perform standby power automatic switching
double-group test and transformer three-phase differential test, and wires are connected conveniently.
4 Relay &Protection Microcomputer Test System

II Technical Parameters
l Main rated parameters
Phase current output (effective value) 6×0~30A or 3×0~60A
Super-630 Maximum output power 520VA/phase
Maximum parallel current output (effective value) 0~180A
Phase current output (effective value) 6×0~25A or 3×0~50A
Super-625 Maximum output power 460VA/phase
Maximum parallel current output (effective value) 0~150A
Phase current output (effective value) 6×0~20A or 3×0~40A
Super-620 Maximum output power 400VA/phase
AC current Maximum parallel current output (effective value) 0~120A
output Phase current output (effective value) 6×0~15A or 3×0~30A
Super-615 Maximum output power 300VA/phase
Maximum parallel current output (effective value) 0~90A
Phase current output (effective value) 3×0~30A
Super-330 Maximum output power 260VA/phase
Maximum parallel current output (effective value) 0~90A
Long-term allowable working value of phase current (effective value) >10A
Allowable working time of maximum current >11s
Accuracy < ±0.2%
Super-630
Super-625 Phase voltage output (effective value) 6×0~130V
Super-620 Line voltage output (effective value) 0~260V
AC voltage Super-615
output Phase voltage output (effective value) 5×0~130V
Super-330
Line voltage output (effective value) 0~260V
Maximum output power 70VA/phase
Accuracy < ±0.2%
Super-630
Output range 0~300V or 6×0~±130V
Super-625
Maximum output power 130VA
Super-620
DC voltage Accuracy < ±0.2%
Super-615
output
Output range 0~300V or 5×0~±130V
Super-330 Maximum output power 130VA
Accuracy <±0.2%
Super-630
Output range -15~15A or 6×0~±15A
Super-625
DC current Maximum output power 200VA
Super-620
output Accuracy <±0.2%
Super-615
Super330 Output range -15~15A or 3×0~±15A
5 Relay &Protection Microcomputer Test System

Maximum output power 200VA


Accuracy <±0.2%
Idle contact 1~20mA, 24V (DC)
Binary input
Electric potential contact 0~250V (DC)
Binary output Idle contact 250V/0.5A (DC)

l Other rated parameters


Frequency error < ±0.01Hz
Phase error <±0. 2°
Waveform distortion < ±0.3% (fundamental wave)
Rated output
Time error <40µs
Output frequency 0~1050Hz
Superposed harmonic wave 0~21times
Power voltage Allowable range AC220V±10%, 50Hz±10%
Use range 0~45℃
Ambient temperature
Storage range -25~70℃
Time measurement Test range 0.1ms~999999.999s
Imported electromagnetic compatible cabinet, which is made of high-grade all
Exterior appearance of
aluminum alloy extruded section and has fine appearance, is selected.
cabinet
Dimension of cabinet: length×width×height 360mm ×195mm ×375mm
Weight of cabinet Weight of host machine 16.6kg
Selectable between light load or heavy load output
(When any phase current output surpasses 15A, it is suggested to press key F3
Load-bearing output
before test of each functional module so as to switch to heavy load output
mode)
6 Relay &Protection Microcomputer Test System

III. Product Structure

Fig. 2.3.1 Structure and connection way of host machine

1. High-speed and high-performance embedded microcomputer system


The main control machine of the device is a high-speed and high-performance microcomputer system, and
the control software adopts hybrid programming of C++ and assembly so as to produce various phases of
high-accuracy waveforms. Since the device has an integral structure and different parts are combined firmly,
as many as 500 points per cycle are output and the waveforms at least can be output by a frequency of
higher than 1050Hz, which are impracticable for the traditional way of directly controlling the test device
via a communication port by using a computer. Since the point number is high and the waveform distortion
is low, the requirement on the low-pass filter is very low. Therefore, excellent transient behavior,
phase-frequency characteristic and amplitude-frequency characteristic are achieved, and accurate phase
shift and harmonic superposition are easy to realize.

2. 16-digit DAC
A 16-digit high-accuracy DAC chip is adopted to ensure high fitting waveform accuracy and good linearity.
Tiny distortion can be ensured even during small signal output.

3. Low-pass filter
Since DAC has high resolution and a large number of waveform points and step waves output by DAC
conversion have high waveform quality, only a simple low-pass filter is needed to filter high-frequency
components in a later stage so as to restore high-quality and high-stability sine waves. Therefore, the
problems of amplitude value, phase drift, etc. are overcome, and the trueness of harmonic test and
high-grade simulation transient waveform are ensured.

4. High-accuracy power amplification module


Output ends of current and voltage amplifiers are not provided with voltage booster or current booster, but
direct output mode is adopted, so current and voltage sources can directly output DC waveform to
waveforms including various frequency components, such as square waves, combined waveforms
superposed by harmonics and fault transient waveforms. Meanwhile, current and voltage characteristics
during short circuit failure of the protective device can be simulated truly.
7 Relay &Protection Microcomputer Test System

Power amplifying circuit adopts the unique ultra-linear amplifying technique, uses an imported high-power
apparatus as the output stage and combines the elaborately and rationally designed radiating structure so as
to achieve enough power redundancy and heat capacity. Intelligent protection can judge overvoltage,
overcurrent, overload, overheat and short circuit protection at the same time. When overcurrent occurs in a
current circuit and overload or short circuit occurs in a voltage circuit, the entire power amplifying circuit is
switched off automatically and sound alarm signal is emitted to prompt. In order to avoid overheat of the
power amplifying circuit after long-term running under heavy current, software time limit under heavy
current is set for the device. The device can run for a long time during output under 10A. When the current
reaches 10A or above, the software time limit is started. After reaching the time limit, the software
automatically stops power output and gives alarm instruction. The higher the output current is, the shorter
the time limit is, so safe running of the power amplifier is ensured.

5. Binary input and output


The device is provided with eight binary input circuits compatible with the idle contact and the 0-250Vdc
electric potential contact. The acting time and holding time of each phase of switch contact can be
measured conveniently.
There are four binary outputs, which are relay idle binary outputs. The output capacity is DC: 250V/0.5A.
The binary output is fully isolated from parts of voltages, current, input, etc. The acting processes of the
four paths of outputs are slightly different from each other in each test module. For details, please refer to
software operation instruction of each module.

6. Big-screen LCD and panel key operation


The device uses 8" big-screen high-resolution graphic liquid crystal display screen with dot matrix of
640×480. The operation interface and the test result are displayed fully in Chinese in an intuitive and clear
way. All operation processes are performed by 23 keys on the panel, and all interfaces are displayed in
Chinese and set on the display screen. The 23 keys are arrayed aesthetically on the panel and are
human-friendly; meanwhile, the keys are simple and convenient to operate and easy to grasp basically
without computer knowledge. The panel structure is shown in Fig. 2.3.2.

7. Panel structure
The panel structure of the device is shown in Fig. 2.3.2.
8 Relay &Protection Microcomputer Test System

Fig. 2.3.2 Panel Layout Diagram


Note: when the tester acts self-protection for a certain reason (overvoltage, overcurrent, over-high
temperature or data abnormity), sound alarm will be sent out and the user is required to reset the
power key.

Description of danger signal indicating lamp: it is orange under normal state; it turns red when danger
signal enters the tester and does not turn orange until the danger signal is cleared; here, the danger signal
indicates the entry of external voltage into the tester through voltage output (UA, UB, UC, UX, UY, UZ)
and current output (IA, IB, IC, IX, IY, IZ) terminals.

Descriptions of voltage short circuit, current open circuit and over-heat indicating lamps are shown in
the following table.
Indicating Description Indicating Description
lamp lamp
"~" When the external power supply voltage is too high, "℃" When the internal temperature
the indicating lamp is on. of the tester is too high, the
indicating lamp is on.
"IA" When open loop occurs in the path of analog output "UA" When short circuit occurs in the
"IB" or the output is distorted while the program is "UB" path of analog output or the
"IC" running, the indicating lamp is on. "UC" output is distorted while the
"IX" When the power amplifier is not switched on or "UX" program is running, the
"IY" there is no practical output, the state of the "UY" indicating lamp is on.
"IZ" indicating lamp will be displayed randomly, which "UZ"
can be neglected.
Note: in case of alarming, please switch off the power amplifier and the main power supply and check
9 Relay &Protection Microcomputer Test System

external wiring, power supply, temperature, etc. in time.


Description of indicating lamp of power key: the green lamp is on under normal state, and the red
indicating lamp is on during self-protection (protection during overvoltage, overcurrent, over-high
temperature or data abnormity) of power amplifier output.
Binary input and other USB, LAN, Key, Mouse and COM interfaces of the tester are positioned right
above the device (shown in the following Fig. 2.3.3). Nine-pin (hole) serial communication port
(COM1/COM2) is communicated with external computer or GPS device, and Windows software of
background computer can control the device via the communication port.

Fig. 2.3.3 Layout Diagram of Interface Board


Furthermore, the device also provides optional 110V/220V auxiliary DC source output (provided in
the right side board, shown in Fig. 2.3.4) and can provide enough DC power supply for test microcomputer
protection and relay.

Fig. 2.3.4 Layout Diagram of Side Board


10 Relay &Protection Microcomputer Test System

Chapter Three Basic Operation

(Note: Super series of products basically have the same operation mode, and the operation
manual takes Super-630 for example).
I. Circuit connection
Connection modes of analog quantity and binary output terminals are shown in the following Fig.:

Fig. 3.1.1 Connection Mode of Each Terminal

Note: if the tested device is on the running site, on-site current transformer (CT) and potential
transformer (PT) loops shall be disconnected from the protective device so as not to affect correct test of
the device by strong disturbance. Furthermore, please connect all external connecting wires before
switching on the power amplifier.
Current output terminal: correspondingly connect IA, IB, IC, Ix, Iy, Iz and In with the tested device
one by one.
Voltage output terminal: correspondingly connect UA, UB, UC, Ux, Uy, Uz and Un with the tested
device one by one.
11 Relay &Protection Microcomputer Test System

Fig. 3.1.2 Connection Mode of Interphase Output Terminal

Description: Please connect any end of current output to the ground (shown in Fig. 3.1.2) while testing
interphase output of the current relay so as to obtain the highest accuracy; and grounding is not required
when IA, IB, IC and IN are all connected during test of microcomputer protection.
Binary input terminal: binary input signal shares a common terminal. A, B, C and R or a, b, c and r
are connected to the tested device respectively, and if the tested device is not a relay, all the contacts shall be
connected for the software of the device decides how to calculate the breakdown quantity of the next step
according to the acting situation of the contact point. Therefore, all protected signals of A, B, C and R shall
be connected to the device while testing the protective device so as to ensure correct test.
The input part is isolated from working power supply, power amplifying power supply, etc. of the host
machine, so the common terminal of the input part is not communicated with the common terminals UN and
IN of current and voltages parts. Switching value potential input is directed, so the common terminal shall
be connected with positive potential terminal while the input end shall be connected with negative potential
terminal. Keep the common terminal potential higher than the input terminal shown in Fig. 3.1.3.

Fig. 3.1.3 Connection Mode of Contact

The system judges whether the contact is normally open or normally closed by overturn of contact
signal, and correct detection is unavailable if the contact point is connected reversely. The contact point is
normally closed when the test device judges the existence of potential under normal state. The contact point
is closed during protection action, and the idle contact is closed. Therefore, overrun of the contact point
cannot be judged.
Binary output terminal: four terminals ①、②、③and ④ are connected to external contact needing
fault startup respectively. When the device starts testing and outputs breakdown quantity, the contact is
12 Relay &Protection Microcomputer Test System

closed; on the contrary, the contact is disconnected when the breakdown quantity is eliminated.
Auxiliary DC output terminal: the device is provided with two sets of auxiliary DC voltage sources,
one of which is 110V, and the other is 220V and they can work at the same time;
Warning: Do not connect DC output with other output terminals.

Lead-in of external power adopts conventional 220VAC/50Hz for power supply. Please refer to Fig.
2.3.4.

Note: in order to ensure reliable grounding of device housing, lead-in wire of external power
shall be three-core power cord.

Attentions:
1) Lead-in of external AC/DC power to jacks of voltage
outputs (UA, UB, UC, UX, UY and UZ) or current
outputs (IA, IB, IC, IX, IY and IZ) of front panel for the
device is absolutely prohibited!
2) The device shall be grounded reliably! (Ground terminal
is positioned on right upper side of the cabinet)
3) Please do not plug and pull analog quantity connecting
wire of the device during test!

Warning:
In order to ensure safety, please do not detach any cover of
the machine body or try to contact the inside of the product.
If maintenance is needed, please contact authorized
maintenance personnel.
13 Relay &Protection Microcomputer Test System

II. Software Operation


The device can run after connecting it to side board socket by three-hole power cord, leading external
power in, connecting other circuits and pressing power switch on lower side panel. After the startup of the
device, the system performs self-check and automatically enters main software menu. Please enter the
functional software needing testing according to directions, press power key on the panel and start testing
after preheating for about 15 minutes. Please pay attention to startup & shutdown sequence:
Startup: power switch→ power key Shutdown: power key → power switch

1. Operation guide for panel keys

Panel of the device includes 23 keys, through which all operations are realized. Functions of these
keys are similar to keypad on a US keyboard. The 23 keys generally include:
One backspace key for deleting characters input in previous operation (represented by "backspace");
One ESC key for exiting the running process or the current setting window so as to return to previous
menu;
Four cursor keys of up, down, left and right for changing the current setting focus or increase/decrease
of variable (represented by "←↑↓→");
One enter key for entering or determining the current setting focus (represented by " ");
Ten number keys from 0 to 9 and two symbolic keys of "." and "-" for inputting parameter value of the
current setting focus or characters;
Four function keys (F1, F2, F3 and F4), in which F1 is used to open help file of the current function
menu; F2 is used to switch view; F3 is used to change load-bearing ability (light load or heavy load, heavy
load is recommended when any phase of current output is higher than 15A); and F4 is a shortcut key for
starting test.

2. Basic software operation

The machine is provided with integral cabinet and test software, so it can operate and test without
externally connected computer.
After startup of the device, a dialog box interface will pop out. You can select local operation or
on line operation (operation with externally connected PC machine) to enter test, shown in Fig. 3.2.1.
14 Relay &Protection Microcomputer Test System

Fig. 3.2.1 Selection of Operation Software

When you select background computer operation, please connect external PC with local
communication port COM1 via nine-core cable.
And then, press ESC key to exit background computer operation according to directions and
return to the interface shown in Fig. 3.2.1.
Interface style and operation method of control software for the background computer operating
the device are basically the same as those of off-line software, so details are not given here. Since
machine operation software is mainly introduced here.

2.1 Main menu

After selection of local operation, main menu of the system is entered automatically, as shown in Fig.
3.2.3.
15 Relay &Protection Microcomputer Test System

Fig. 3.2.3 Main Menu

Up, down, left and right keys on the panel are operated to move the block in reverse display and enter
function menu interface to be tested.
After finishing all tests, you can selectively enter screen protection in Fig. 3.2.1 or directly shut down.

2.2 Function menu

The system nearly comprises all function menus for testing the relay and checking microcomputer
protection. In all function menu interfaces, parameter setting and running menu items are provided and
corresponding vector graphics and parameter values are displayed.
16 Relay &Protection Microcomputer Test System

Fig. 3.2.4 Module Test Interface

Interface explanation: in order to ensure simple operation and visual effect of the software interface,
function menus of the system are designed in uniform interface style. One of the function test modules is
shown in Fig. 3.2.4.
For parameter setting, each function corresponds to different parameters. Please refer to use method of
sub-item function menu in Chapter Four.
For setting range of each basic parameter, please refer to technical parameters in Chapter Two:
Amplitude values of phase voltages Ua, Ub, Uc, Ux, Uy and Uz: 0.000~130.000V
Amplitude values of phase currents Ia, Ib, Ic, Ix, Iy and Iz: 0.000~30.000A
Amplitude values of line voltages Uab, Ubc and Uca: 0.000~260.000V
Amplitude values of full parallel current: 0.000~180.000A
Phase positions of each phase voltage and current: -360.00~360.00°
Output frequency: 0.000~1050.000Hz
DC voltage: 0.00~300.00V
DC current: -15.00~15.00A
Auxiliary DC voltage output: 110V/220V
In order to ensure correct test results for various relays (such as voltage, current, impedance and
power), contact chattering time shall be set generally within the range of 0~3 seconds.
Impedance value setting range:
Generally, the impedance value does not have specific setting range. Only after setting, the software
may automatically calculate corresponding voltage value. If the voltage surpasses a preset range, prompt of
reentering impedance value is given.
For microcomputer protection, the impedance value is fixed. If the situation above occurs, please set
the impedance value as 0.01 Ω. Meanwhile, failure current value is reduced, and then the impedance value
is reset as the fixed value so correct setting can be ensured.
17 Relay &Protection Microcomputer Test System

Running process: as shown in Fig. 3.2.5, load start


is prompted before the function test. Please ensure
correct circuit connection loop, press power amplifier
switch, operate panel keys and select button
"confirmation" so as to enter test process. At this
moment, power amplifying loop of the tester has been
Fig. 3.2.5 Load Confirmation Dialog Box
switched on and the entire device is in working state.
In the running process, the machine firstly outputs initial voltage and current vector values, detects the
contact state and memorizes the state of external input contact as a basis for judging the action or return of
the tested device; when contact states of A B C R a b c r are not accordant with the memorized state, action
of the tested device is proved and corresponding output is changed. Contact return of the tested device is
judged when the contact state is detected to be not accordant with the memorized state. "ESC" key can be
pressed at any time in the testing process to exit test.
After completion of the test, power amplifier output is switched off automatically by the machine.
Meanwhile, prompt box will pop out to inquire user about handling suggestions after the end of test.

(a) (b) (c)


Fig. 3.2.6 Saving Dialog Box after End of Test

As shown in (a) of Fig. 3.2.6, operate panel key to select "confirmation" button and enter file name
setting dialog box; as shown in (b) of Fig. 3.2.6, input basic file name of correct format; if parameter setting
is modified after inputting, dialog box (3) of Fig. 3.2.6 is displayed. Save the test parameters after
confirmation and return to main interface of function menu.

2.3 File service

Certain result files (*.END) and graphics files (impedance characteristic curve [*.ZFG], precision
current characteristic curve [*.JFG], differential relay characteristic curve [*.DII] and I-T characteristic
curve [*.CIT]) saved by user after end of test can be referred to and uploaded to the PC machine to be
printed into report, so the system provides file service function.
After entering file service menu, report file and characteristic curve are available. Press report file
button, and if no report file is saved, prompt of "This type of report file does not exist" is given on the
interface; otherwise, select and confirm report file to be referred to as shown in Fig. 3.2.7.
18 Relay &Protection Microcomputer Test System

Fig. 3.2.7 Selection of Report File

Up, down, left and right keys are used to select file name and enter key is used to confirm. Press ESC
key to exit the interface. When file needs uploading, please make sure that communication cable has been
correctly connected to PC machine firstly, and corresponding software on the PC machine has been opened.
At this moment, press key F2 and upload selected file to the PC machine according to corresponding
prompt.
After corresponding file name is selected, the file content is displayed on the interface. Test report of
impedance relay is shown in Fig. 3.2.9.
The test report is saved in form of text file. If user needs modifying content in the report, any available
text editing software can be used to sort in the PC machine after uploading the file.
Characteristic curve item is used to observe four characteristics (shown in Fig. 3.2.8) of the relay so as
to test recorded action track. Its parameter is also saved in the form of text file, but its corresponding
parameter cannot be modified generally, or program error will be caused. After selection of file name
corresponding to the curve type, corresponding action motion is displayed on the screen. Impedance
characteristic curve is shown in Fig. 3.2.10.

Fig. 3.2.8 Selection of Characteristic Curve File Type


19 Relay &Protection Microcomputer Test System

Fig. 3.2.9 Display of Report File

Fig. 3.2.10 Motion Track of Characteristic Curve

Report copying item is used to copy all current test reports of the device to external U disk. Make sure
that the U disk has been inserted correctly before copying.
20 Relay &Protection Microcomputer Test System

III. Software Upgrade


The device adopts an embedded microcomputer system. Software of lower computer can be upgraded
by the following two ways.
In the first way, USB storage device (randomly equipped U disk or other USB hardware of FAT format)
with update software is directly connected via USB interface and connected to the lower computer. The
following steps shall be carried out:
1. Switch off main power.
2. Install the U disk attached at delivery or other normally usable USB storage device in upgrade
software and insert it into local USB interface.
3. Turn the main power on, start up the machine and select "software upgrade (U disk)" in an
operation mode to upgrade automatically.
In the second way, nine-core data communication cable is externally connected with PC machine. The
following steps shall be carried out:
1. Switch off main power.
2. Connect one end of the DB9 communication data wire attached at delivery to local COM1 port
and the other end to COM port of external PC machine.
3. Turn the main power on, start up the machine, select "software upgrade (on-line)" in an operation
mode and enter background computer operation.
4. Start external PC machine, enter on-line test software system and open lower computer upgrade
module; carry out every step as required.
21 Relay &Protection Microcomputer Test System

Chapter Four Test Method

I. U/I Test

(I) Test purpose


The menu is used to manually and automatically test voltage and current protection functions of the
protective device and action return situations of voltage and current relays.
In the interface, parameter setting is displayed on the left upper side, laboratory result display column
is displayed on the left lower side, vector graph, linear component graph and sequence component graph
are displayed on the right upper side and contact state simulation and notes are displayed at the bottom.
Press key F2 to switch display.
(II) Test Principle
During manual test, output initial voltage or current value firstly, press up and down cursor keys to
increase or decrease varible value until contacts of the protective device and the relay act, press the cursor
keys once again to increase or decrease component value until contacts of the protective device and the
relay return.
During manual test, output initial voltage or current value firstly, then positively and gradually modify
22 Relay &Protection Microcomputer Test System

the component by a step length (add a step length) according to the step time until contact points of the
protective device and the relay act and record the action value; if the return mode is "start → end→ start",
the program reversely and gradually modifies the component by a step length (subtract a step length) until
contact points of the protective device and the relay return and record the return values.

Figure 4.1.1 Running Process of UI Test


After finishing test, test results will be displayed on the screen and user can save the result file.
(III) Circuit connection
○1 Connect coil winding to corresponding voltage or current output end of the device according to
types (voltage protection, current protection; voltage type, current type) of the protective device and
the relay.
○2 Connect acting contact of tested protective and acting contact of tested relay to binary input of the
device.
(IV) Parameter explanation
A. Item setting page
1. Test item: select item of this test from the following three choices: low voltage protection,
overvoltage protection and current protection.
2. Test mode: select mode of the test from the following two choices: automatic test and manual test.
3. Current configuration: select current output configuration mode of the experiment from the
following two choices: three-phase current and six-phase current. In three-phase current configuration, A
phase current= IA and IX in parallel; B phase current= IB and IY in parallel; and C phase current=IC and
IZ in parallel.
4. Test phase: select phase of tested relay from the following seven choices: AN, BN, CN, AB, BC,
CA, 3U0 and three phases in parallel.
5. Initial variable value: set initial value of variable.
6. Variable step length: set step length of variable in each change.
7. Maximum current: search the maximum current value only during current protection while setting
current protection test so as to avoid excessive current from damaging the protective device or the relay.
8. Return mode: select process of the test from the following two choices: start →end→start (measure
the action value, return value and action time) and start → end (measure the action value and the action
time).
23 Relay &Protection Microcomputer Test System

9. Time per step: set wait time for every change of one step length within the range of 0-3600 seconds.
10. Shattering time: set anti-contact shattering time within the range of 0-3 seconds in order to prevent
contact shattering from affecting the test result. Only when the contact action surpasses the time limit,
actions (or returns) of the protective device and the relay are confirmed. Default value: 200 milliseconds.
B. Output setting page
Set amplitude values, angles and frequencies of six-phase voltage and six-phase or three-phase
current.
[Explanation]: Analog quantity of corresponding test phase will be automatically calculated, modified
and output by the program in the testing process. Other quantities are output according to the phase setting.
For example: amplitude value and angle of A phase voltage will be calculated and output by the program
while testing low voltage protection and AN phase while other voltage and current will be output according
to setting in this page.
24 Relay &Protection Microcomputer Test System

II. DC Test

(I) Test purpose


The menu can be used to manually or automatically test parameters of action value, return value and
acting time and the like for DC relay or time relay.
In the interface, parameter setting is displayed on the left upper side, test results are displayed on the
left lower side, DC analogue table is displayed on the right upper side and contact state simulation and
notes are displayed at the bottom.
(II) Test principle
During manual test, input initial values of voltage, current and frequency firstly. Keys ↑ and ↓ can be
pressed to increase/decrease variable value. If user needs testing the time, he shall press key "F3" firstly,
and then press keys ↑ and ↓ can be pressed to increase/decrease variable value and start counting. The time
limit range is 0-3600 seconds. For example, if the time limit is 20 seconds, i.e., the tested device does not
act within 20 seconds, timing state is released automatically.
During automatic test, input initial value of each parameter firstly, and gradually increase step length
to change the variable value at a speed determined according to the setting of the time per step; if the relay
or the protective device acts, gradually decrease the step length to change the variable value until the
protection returns, and the software will record the action value and the return value. If protection does not
act after the variable has increased to the maximum state or decreased to the minimum state, the software
will automatically exit test.
25 Relay &Protection Microcomputer Test System

After finishing the test, test results are displayed on the screen, and user can save the result file.
(III) Circuit connection

1 Connect coil winding to corresponding DC voltage and DC current output ends of the device
according to protection type of the protective device and parameter type of the relay.

2 Connect acting contact point of tested protective and acting contact of tested relay to binary input of
the device.
(IV) Description of parameters
1. DC voltage: set initial value and maximum value of DC voltage within the range of 0 to 300V.
[Note]: output mode of DC voltage: Udc=Uxy, i.e., Ux terminal is positive and Uy terminal is ground.
2. DC current: set initial value and maximum value of DC current within the range of -15 to 15A.
[Note]: output mode of DC current: Idc=Iz, i.e., Iz terminal is positive and In terminal is negative.
3. Variable selection: select variable of the test from the following two choices: DC voltage and DC
current.
4. Test mode: select mode of the test from the following two choices: automatic test and manual test.
5. Variable step length: set step length of variable. Voltage range: 0 to 300V; current range: -15 to 15A.
6. Time per step: set time for every change of one step length within the range of 0-60 seconds. The
higher the value is, the higher the corresponding accuracy is. This parameter only needs setting in the
automatic mode.
7. Return mode: select process of the test from the following two choices: start→ end→ start (measure
the action value, return value and action time) and start → end (measure the action value and the action
time).
8. Action time limit: set action time limit of the relay. It indicates that the maximum action time of the
relay shall be within the time limit. If its value is smaller than the action time, close the timer or exit test. It
is within the range of 0-60 seconds.
9. Voltage compensation factor: set a compensation factor to correct the accuracy of DC voltage within
the range of 0.7 to 1.43.
10. Current compensation factor: set a compensation factor to correct the accuracy of DC voltage
within the range of 0.7 to 1.43.
11. Shattering time: set anti-contact shattering time within the range of 0-3 seconds in order to prevent
contact shattering from affecting the test result. Only when the contact action surpasses the time limit,
actions (or returns) of the protective device and the relay are confirmed. Default value: 200 milliseconds.
(V) Experiment example
Please try to use manual mode during test of time relay. Firstly, set initial value of DC voltage as 0V
and step length as 220V (greater than action voltage), press key F3 to turn on the timer after the test starts
and press the up cursor key to upgraduate the voltage to 220V. The software will measure the action time
accurately.
26 Relay &Protection Microcomputer Test System

III. Impedance Characteristics

(I) Test purpose


The menu is used to automatically test the impedance characteristic of microcomputer protective
device and action boundary, i.e., Z( φ) action boundary characteristic of impedance type relay (including
impedance relay and power direction relay).
In the interface, parameter setting is displayed on the left upper side, current and voltage outputs in the
testing process are displayed on the left lower side, action curve is displayed on the right upper side and
contact state simulation and note are displayed at the right bottom.
(II) Test principle
After start of the test, scan from initial angle to end angle by angular step length and search between
K% and 100% of scanning radius for each scanning line. Generally, K% of the scanning radius shall be
ensured to be within the action region while 100% is positioned outside the action region, i.e., the scanning
line must fully cover the action boundary.
For test on general scanning line, the program searches action boundary point by the dichotomy
principle, and the searching process is as follows:
1) Test start point of scanning line;
2) Test end point of scanning line;
3) Decide the searching action of the next step according to the acting situations of the start point and
the end point:
27 Relay &Protection Microcomputer Test System

☆ If the start point and the end point have the same acting situation, it is indicated that the
boundary point is not on the scanning line or more than two boundary points may exist; and search of
the boundary point is ended;
☆ If the start point and the end point have different acting situations, it is indicated that the
action boundary point exists on the scanning line. Enter dichotomy search, gradually approach the
boundary point until test accuracy is met and end the search of the action boundary.

(III) Circuit connection


○1 Connect coil winding to corresponding DC voltage and DC current output ends of the device
according to protection type of the protective device and parameter type of the relay.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
A. Characteristic setting page
1. Characteristic shape: select impedance characteristic of tested protection from the following two
choices: circle (including ellipse) and quadrilateral (tetragonal CSL protection).
2. Set Z1: form of polar coordinates for the first setting impedance of the circle characteristic:
amplitude value and angle which require setting during selection of circle characteristic.
3. R1+jX1: form of rectangular coordinates for the first setting impedance of the circle characteristic:
resistance and impedance which require setting during selection of circle characteristic.
4. Set Z2: form of polar coordinates for the second setting impedance of the circle characteristic:
amplitude value and angle which require setting during selection of circle characteristic.
5. R2+jX2: form of rectangular coordinates for the second setting impedance of the circle
characteristic: resistance and impedance which require setting during selection of circle
characteristic.
6. Setting value R: setting value R with quadrilateral characteristic which require setting during
selection of quadrilateral characteristic.
7. Setting value X: setting value R with quadrilateral characteristic which require setting during
selection of quadrilateral characteristic.

B. Scan setting page


1. Central impedance Z: form of polar coordinates for circle center Z of radial type scanning circle:
size and angle.
2. R+jX: form of rectangular coordinates for circle center Z of radial type scanning circle: resistance
and impedance.
3. Scanning area: set start angle and end angle of scanning angle.
4. Step length: start scanning from the start angle, use the angular step length as the interval and
determine scanning line needing testing along the anticlockwise direction.
5. Scanning radius: the radius of the radial type scanning circle. A circle is drawn by using the radius
of the scanning line as the radius to form a scanning circle in relation to central impedance Z, i.e.,
with Z as the circle center.
28 Relay &Protection Microcomputer Test System

6. Scanning range: the scanning line searches among K% ~ 100% of the scanning radius. Generally,
K% of the scanning radius shall be ensured to be within the action region while 100% shall be
outside the action range, i.e., the scanning line must fully cover the action boundary.
7. Measuring accuracy: when the difference between the impedance of an action point and a
stationary point is smaller than the accuracy, the action point and the stationary point can be
considered as the same point as well as the action boundary point.
8. Test characteristic: select the test characteristic from the following two choices: static experiment
(current before failure is not sent before failure but failure current is sent) and dynamic
experiment (current before failure is output in a pulse form before failure, and it is suitable for
testing sudden change protective device).

C. Failure setting page


1. Failure type: failure type to be tested includes seven kinds of failures: A phase grounding, B phase
grounding, C phase grounding, AB interphase, BC interphase, CA interphase and three-phase
short circuit
2. Failure direction: select failure direction from the following two choices: positive failure and
negative failure.
3. Failure current: failure current magnitude in the testing process.
4. Short-circuit closing angle: voltage angle during failure.
5. Zero sequence compensation: in order to calculate zero sequence impedance in a grounding
system, two compensation factors (zero sequence resistance compensation factor Kr) and (zero
sequence impedance compensation factor Kx) need setting. The specific relation is as follows:
R0=R1 (3Kr+1)
X0=X1 (3Kx+1)
6. Time before failure: current before failure and voltage before failure are output before failure.
7. Failure time: test the maximum test time kept by each scanning point in a current changing
process. Generally, the failure time shall be longer than the action time of the relay.
8. Break time: if action occurs on a certain scanning point, zero state of break time is sent to ensure
that the protective device and the relay are reset reliably.
29 Relay &Protection Microcomputer Test System

IV. Power Direction Test

(I) Test purpose


The menu is used to automatically test power direction characteristic and power direction relay of the
protective device.
In the interface, parameter setting is displayed on the left upper side, laboratory result is displayed on
the left lower side, vector graph is displayed on the right upper side and contact state simulation and notes
are displayed at the right bottom.
(II) Test principle
Test of action boundary: the program firstly tests and records the state of protection or relay at a
reference angle, scans along anticlockwise direction to search the first action boundary, scans from the
reference angle along clockwise direction to search the second action boundary, and calculates sensitive
angle to finish searching the action boundary.
Test of action voltage: use the sensitive angle (if sensitive angle is obtained by testing the action
boundary) or the reference angle (if no sensitive angle is obtained), increase the voltage value from zero
and search the action voltage.
Test of action current: use the sensitive angle (if sensitive angle is obtained by testing the action
boundary) or the reference angle (if no sensitive angle is obtained), increase the current value from zero
and search the action current.
Test of action time: set the initial state as zero, send action voltage (rated voltage), use the sensitive
30 Relay &Protection Microcomputer Test System

angle or reference angle as the angle, starts timing, initiate protective action and obtain the action time.
(III) Circuit connection
○1 Connect coil winding to corresponding DC voltage and DC current output terminals of the device
according to protection type of the protective device and parameter type of the relay.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to the
binary input of the device.
(IV) Description of parameters
1. Test phase: select test phase from the following seven choices: AN, BN, CN, AB, BC, CA, 3U0 and
three phases in parallel.
2. Test item: select item content to be tested and tick ("√") the selected test.
3. Failure current: set the current magnitude during failure in the testing process.
4. Rated voltage: set rated voltage of tested protection or relay.
5. Initial angle value: set scanning initial angle during test and set it positive in case of leading voltage.
6. Test accuracy: scan coarsely at the start of test, find the action boundary, return a step length,
continue scanning by the test accuracy value and find the action boundary.
7. Failure time: set waiting time of each failure. In order to ensure correct test, time setting of each
step shall be greater than the action time of the relay.
8. Break time: set waiting interval time after scanning a value so that the tested protection or the relay
can return reliably. The test instrument outputs the rated voltage and the zero current within the interval
time.
9. Shattering time: set anti-contact shattering time within the range of 0-3 seconds in order to prevent
contact shattering from affecting the test result. Only when the contact action surpasses the time limit,
actions (or returns) of the protective device and the relay are confirmed. Default value: 200 milliseconds.
31 Relay &Protection Microcomputer Test System

V. I-T Test

(I)Test purpose
The menu is used to test I(t) action characteristic of inverse time-limit overcurrent relay.
In the interface, parameter setting is displayed on the left upper side and characteristic curve and
action record are displayed on the right upper side. User can shift display by pressing F2. Contact state
simulation and notes are displayed at the bottom.
(II) Test principle
The menu is for automatic test; when test is started, the software automatically computes and outputs
current value according to set parameter, records corresponding action time and scans IT curve on the
screen until the test is completed.
(III)Circuit connection
○1 Connect coil winding to corresponding DC voltage and DC current output terminals of the device
according to protection type of the protective device and parameter type of the relay.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
1. Failure type: select failure type to be simulated from the following seven choices: A phase
grounding, B phase grounding, C phase grounding, AB short circuit, BC short circuit, CA short circuit
and three-phase short circuit. When single-phase grounding is selected, current output mode can be
32 Relay &Protection Microcomputer Test System

selected from the following two choices: single phase output and three parallel phases. If it is required to
test high current, it is suggested to adopt three-phase parallel output mode.
2. Initial current value: set initial value of scanning current within the range of 0-30A (single phase)
and 0-90A (three phase).
3. Current end value: set end value of scanning current within the range above.
4. Change step length: set current magnitude per change in program scanning process.
5. Failure time: set the maximum time needed for completing every failure within the range of 0-999
seconds.
6. Break time: after finishing searching an action current value, the test device enters the time span of
interruption state. The current output is zero in this state. Range: 0-20 seconds.
7. Reference angle: set included angle between voltage and current. This item is positive in case of
leading voltage. Range: -360 to 360 degrees.
8. Rated voltage: set the rated voltage value of which the range is related to phase.
33 Relay &Protection Microcomputer Test System

VI. Frequency Protection

(I) Test purpose


The menu is used to test low-cycle characteristic of microcomputer protection and action values,
action time and slippage latch-up characteristic of frequency relay, low-cycle unloading device, etc.
In the interface, parameter setting is displayed on the left upper side, test state is displayed on the left
lower side, vector graph and frequency table are displayed on the right upper side and contact state
simulation and notes are displayed at the bottom.
(II) Test principle
Manual frequency conversion: manual test mode for manually simulating frequency conversion and
manually testing return value of action value for frequency relay.
Action frequency: test action value of frequency relay or action frequency of low-cycle unloading
device. This item is automatic test mode for searching action frequency value by using slip ratio as the
rate of change within preset frequency range.
Action time: test action time of low-cycle unloading device. This item is automatic test mode for
starting frequency conversion from the initial frequency value to the end frequency and timing from the
threshold frequency to the time of the protective action and the measured value.
Slip ratio: test fixed value of slip ratio for the low-cycle unloading device. This item is automatic test
mode for setting (the initial slippage value shall be greater than the protective fixed value, while the final
value shall be smaller than the protective fixed value) variation frequency and searching whether the
34 Relay &Protection Microcomputer Test System

slippage can be protection action for testing the fixed value.


(III) Circuit connection
○1 Connect coil winding of protective device or low-cycle unloading device and frequency relay to
corresponding current and voltage output terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
Test item: set test items from the following four choices: manual frequency conversion, action
frequency, action time and slip ratio. If different test items are selected, the parameter setting page will be
different.
A. Manual frequency conversion
1. Frequency conversion selection: select analog quantity needing frequency conversion from the
following three choices: voltage and current frequency conversion, voltage frequency conversion and
current frequency conversion.
2. Initial frequency value: set initial frequency value after the start of test.
3. Frequency step length: set frequency amplitude per change.

B. Action frequency
1. Frequency conversion selection: select analog quantity needing frequency conversion from the
following three choices: voltage and current frequency conversion, voltage frequency conversion and
current frequency conversion; select frequency conversion mode from the following two choices: cycle
frequency conversion and continuous frequency conversion.
2. Frequency range: set searching frequency range in the testing process.
3. Frequency step length: set frequency amplitude per change.
4. Slip ratio: set speed of frequency change as a slippage value for protective action and a value
smaller than the slippage latching value of the low-cycle unloading device.
5. Change time delay: set time for sending 50HZ normal value before every change.
6. Failure time: set protective action waiting time of each searching frequency.
7. Break time: set zero sending time before the start of change.

C. Action time
1. Frequency conversion selection: select analog quantity needing frequency conversion from the
following three choices: voltage and current frequency conversion, voltage frequency conversion and
current frequency conversion; select frequency conversion mode from the following two choices: cycle
frequency conversion and continuous frequency conversion.
2. Frequency range: set searching frequency range in the testing process.
3. Slip ratio: set speed of frequency change as a slippage value for protective action and a value
smaller than the slippage latching value of the low-cycle unloading device.
4. Threshold frequency: set fixed value of protection threshold frequency and start timing from the
frequency by the program.
5. Change time delay: set time for sending 50HZ normal value before every change.
35 Relay &Protection Microcomputer Test System

6. Failure time: set protective action waiting time of each searching frequency.
7. Break time: set zero sending time before the start of change.

D. Slip ratio
1. Frequency conversion selection: select analog quantity needing frequency conversion from the
following three choices: voltage and current frequency conversion, voltage frequency conversion and
current frequency conversion; select frequency conversion mode from the following two choices: cycle
frequency conversion and continuous frequency conversion.
2. Slippage range: set slippage range searched in the testing process. The initial slippage value shall be
greater than the slippage latching fixed value of low-cycle unloading device, and the final slippage value
shall be smaller than the slippage latching fixed value of low-cycle unloading device.
3. Slippage step length: set slippage amplitude per change.
4. Frequency range: set searching frequency range in the testing process. The range shall cover the
fixed value for the protection action frequency.
5. Change time delay: set time for sending 50HZ normal value before every change.
6. Failure time: set protective action waiting time of each searching frequency.
7. Break time: set zero sending time before the start of change.
36 Relay &Protection Microcomputer Test System

VII. Differential Relay

(I) Test purpose


This menu is used to test proportional brake of differential relay and harmonic characteristic of
transformer.
In the interface, parameter setting is displayed on the left upper side, test result is displayed on the left
lower side, action curve is displayed on the right upper side, and contact state simulation and notes are
displayed at the right bottom.
(II) Test principle
In manual test, user increases and decreases variable value by keys ↑ and ↓ according to selected
variable till the action of tested protection and presents action value. Meanwhile, changing variable can be
modified online during the test.
In automatic mode, the software automatically increases and decreases step length value to test action
value of protection. 30 times of action situations can be recorded at most.
(III) Circuit connection
○1 Connect coil winding of protective device or low-cycle unloading device and frequency relay to
corresponding current and voltage output terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
37 Relay &Protection Microcomputer Test System

1. Differential phase: select acting phase and braking phase of differential relay from the following
three choices: Ia acts and Ib brakes; Ib acts and Ic brakes; and Ic acts and Ia brakes. If Ia acts and Ib
brakes, Ia is the acting phase and Ib is the braking phase, and so on.
2. Action current: set initial value and frequency of action current (Id).
3. Breaking current: set initial frequency of breaking current (Iz).
4. Included angle ΔG: set included angle between two currents (the range is the same as above), and it
is positive in case of leading action current (Id).
5. Change mode: set experiment mode from the following two choices: automatic mode and manual
mode.
6. Variable selection: select variable target from the following three choices: action current, braking
current and angle ΔG. It is only set in manual mode. In the manual mode, the program is preset as action
current.
7. Variable step length: set step length of the variable.
8. Iz step length: set searching step length of braking current within the range of -30 to 30A.
9. Time per step: set the time used by every change of one step length within the range of 0-60 seconds.
The higher the value is, the higher corresponding accuracy is. It is only set for automatic test.
10. Break time: set interval time, i.e., the test device will enter a break state after finishing searching
action current value every time. In this state, the current output is zero. Range: 0-60 seconds.
38 Relay &Protection Microcomputer Test System

VIII. Harmonic Test

(I)Test purpose
The test module statically test microcomputer protection DC and (2-21 times of) harmonic
superposition processes. In the interface, parameter setting is displayed on the left upper side, superposition
oscillogram is displayed on the right upper side and contact state simulation and notes are displayed at the
bottom.
(II)Test principle
Before test, user firstly sets each harmonic amplitude and angle of each phase of voltage and current
and selects variable and step length. After the test is started, harmonic waveform is output and user presses
keys ↑ and ↓ to increase/decrease the variable value. Meanwhile, the software gives the superposition
oscillogram and simulation block. If no key is pressed, the test will be ended after 10 seconds.
(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
Ua, Ub, Uc, Ia, Ib and Ic: set 0-21 harmonic amplitudes and phase position of corresponding phase
respectively. Press F2 to turn page and switch between 0-10 setting and 11-21 setting. Parameter contents
39 Relay &Protection Microcomputer Test System

of different parameters are the same as each other. Note: once the superposition value set above surpasses
its range, the software will make a screaming alarm. At this moment, user must reset the parameter.
1. DC: set DC component of the phase analog quantity.
2. Fundamental wave: set fundamental wave component of the phase analog quantity.
3. Second harmonic: set the second harmonic of the phase analog quantity.
4. Third harmonic: set the third harmonic of the phase analog quantity.
5. Fourth harmonic: set the fourth harmonic of the phase analog quantity.
6. Fifth harmonic: set the fifth harmonic of the phase analog quantity.
7. Sixth harmonic: set the sixth harmonic of the phase analog quantity.
8. Seventh harmonic: set the seventh harmonic of the phase analog quantity.
9. Eighth harmonic: set the eighth harmonic of the phase analog quantity.
10. Ninth harmonic: set the ninth harmonic of the phase analog quantity.
11. Tenth harmonic: set the tenth harmonic of the phase analog quantity.
12. Eleventh harmonic: set the eleventh harmonic of the phase analog quantity.
13. Twelfth harmonic: set the twelfth harmonic of the phase analog quantity.
14. Thirteenth harmonic: set the thirteenth harmonic of the phase analog quantity.
15. Fourteenth harmonic: set the fourteenth harmonic of the phase analog quantity.
16. Fifteenth harmonic: set the fifteenth harmonic of the phase analog quantity.
17. Sixteenth harmonic: set the sixteenth harmonic of the phase analog quantity.
18. Seventeenth harmonic: set the seventeenth harmonic of the phase analog quantity.
19. Eighteenth harmonic: set the eighteenth harmonic of the phase analog quantity.
20. Nineteenth harmonic: set the nineteenth harmonic of the phase analog quantity.
21. Twentieth harmonic: set the twentieth harmonic of the phase analog quantity.
22. Twentieth harmonic: set the twentieth harmonic of the phase analog quantity.
22. Twenty-first harmonic: set the twenty-first harmonic of the phase analog quantity.
23. Phase variable: select phase variable from the following six choices: A phase voltage, B phase
voltage, C phase voltage, A phase current, B phase current, C phase current.
24. Harmonic variable: select harmonic from the following 22 choices: DC, fundamental wave, the
second harmonic, the third harmonic, the fourth harmonic, the fifth harmonic, the sixth harmonic, the
seventh harmonic, the eighth harmonic, the ninth harmonic, the tenth harmonic, the eleventh harmonic, the
twelfth harmonic, the thirteenth harmonic, the fourteenth harmonic, the fifteenth harmonic, the sixteenth
harmonic, the seventeenth harmonic, the eighteenth harmonic, the nineteenth harmonic, the twentieth
harmonic and the twenty-first harmonic.
25. Variable step length: set for the step length of the variable.

Harmonic coefficient
Set DC and compensation coefficient of each harmonic. Since low-pass filter circuit of the device is
regulated according to the fundamental wave and little effect is brought on the DC and the amplitude value
output by each harmonic, user can set their compensation coefficients to achieve output meeting the
accuracy requirement.
40 Relay &Protection Microcomputer Test System

IX. Differential Protection

(I)Test purpose
This menu is full six-phase differential test for automatically testing the proportional braking
characteristic, harmonic braking characteristic and DC magnetic assisting characteristic according to
working principle of differential protection of transformer.
In the interface, parameter setting is displayed on the left upper side, variable in the testing process is
displayed on the left lower side and characteristic curve and action record are displayed on the right upper
side. User can shift display by pressing F2. Contact state simulation and notes are displayed at the right
bottom.
(II) Test principle
[Proportional braking test]: firstly, output zero current value and give initial values (displayed on the
interface) of braking current and action current according to preset searching parameter after continuing
for a period of break time. The initial value of the action current is smaller than one step length of
negative error value of a calculation point. Fix the braking current and vary the action current according
to the step length till the protection action. If no protection acts within a fault time limit period, do not
search this point any more. Vary one step length of braking current and search the action current once
again till the action current under the braking current is found. The test ends when the action current
under the last braking current is found.
[Harmonic braking test]: firstly, output zero current value and give initial values of differential current
41 Relay &Protection Microcomputer Test System

and harmonic current according to preset searching parameter after continuing for a period of break time.
The initial value of the harmonic current is smaller than one step length of positive error value of a
calculation point. Fix the differential current and vary the differential current according to the step length
till the protection action. If no protection acts within a fault time limit period, do not search this point any
more. Vary one step length of differential current and search the harmonic current once again till the
harmonic current under the differential current is found. The test ends when the harmonic current under
the last differential current is found.
[DC magnetic assisting test]: firstly, output zero current value and give initial values of action current
and DC current according to preset searching parameter after continuing for a period of break time. The
initial value of the action current is zero. Fix the DC current and vary the action current according to the
step length till the protection action. If no protection acts within a fault time limit period, do not search
this point any more. Vary one step length of DC current and search the action current once again till the
action current under the DC current is found. The test ends when the action current under the DC current
is found.
(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device,shown in the following Fig. 4.9.1.

Fig. 4.9.1 Six-phase differential test connection mode


○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
A. Item setting page
1. Test item: select the item content of the test from the following three choices: proportional braking,
harmonic braking or DC magnetic assist.
2. Connection mode: select connection mode according to hour number of connection mode on each
side of the transformer from the following three choices: Y/Y-12, Y/△-11 and Y/△-1.
3. Balancing coefficient: set balancing coefficient of the transformer, wherein kh is high-voltage side
42 Relay &Protection Microcomputer Test System

current balancing coefficient and kl is low (medium) voltage side balancing coefficient.
4. Ir range: set searching range of braking curve from small to large. Generally, the value is a little
greater than the braking current value on the top inflection point of the curve; and in DC magnetic
assisting test, the value is the DC searching range.
5. Ir step length: set variation step length of braking current. The smaller the step length is, the denser
the searching position is. Range: 0-30A.
6. Fault time limit: set output duration of action current or braking current per change within the range
of 0-100 seconds.
7. Break time: set output interval time of action current or braking current per change. When the
searching current is relatively high, it is suggested to enlarge the value. Range: 0-100 seconds.

B. Parameter setting page


1. Ir setting: select formula of Ir from the following five choices: (|Ih|+|Il|)/k, |Ih-Il|/k, ma ×{|Ih|, |Il|},
{|Id|-|Ih|-|Il|}/k and |Il|.
2. Value k setting: set coefficient value k in formula Ir.
3. Id setting: display formula of Id without modification.
4. Action threshold: set action threshold setting value of differential current.
5. Differential quick break: set quick break setting value of differential current.
6. Action time: set action time setting value of differential current.
7. Searching accuracy: set the searching accuracy in the searching process. The smaller the value is,
the higher the searching value is.

C. Proportional braking characteristic parameter page


1. Inflection point ○1 : set fixed value of protection proportional braking characteristic inflection point
1.
2. Inflection point ○2 : set fixed value of protection proportional braking characteristic inflection point
2.
3. Inflection point ○3 : set fixed value of protection proportional braking characteristic inflection point
3.
4. Total number of inflection points: select the number of protection inflection points from the
following three choices: one, two and three.
5. Error selection: select error type for test from the following two choices: absolute error and relative
error.
6. Relative error: set relative error value, which is valid when the error is relative error.
7. Absolute error: set absolute error value, which is valid when the error is absolute error.

D. Harmonic braking characteristic parameter


1. Harmonic definition: select harmonic definition of tested protection from the following two choices:
high-voltage side harmonic superposition differential current and high-voltage side harmonic
low-voltage side differential current.
2. Harmonic times: set harmonic times within the range of 2-9.
43 Relay &Protection Microcomputer Test System

3. Harmonic angle: set harmonic angle within the range of -360 to 360 degrees.
4. Harmonic coefficient: set harmonic coefficient within the range of 0-50.
5. Error selection: select error type for test from the following two choices: absolute error and relative
error.
6. Relative error: set relative error value, which is valid when the error is relative error.
7. Absolute error: set absolute error value, which is valid when the error is absolute error.
8. Id step length: set step length of Id within the range of 0-30A.

E. DC magnetic assisting characteristic parameter


1. AC current: display definition of AC current, which cannot be set.
2. DC current: display definition of DC current, which cannot be set.
3. Maximum Id: set the maximum value of ID during searching within the range of 0-30A.
44 Relay &Protection Microcomputer Test System

[Supplemental Instruction for Microcomputer Differential Test]


Full-phase differential protection test cannot be performed on test instrument with three-phase current
output during microcomputer differential protection test for only three phases of current inputs can be
provided to microcomputer protection. Differential protection test shall be carried out for each phase
respectively.
According to the type of differential protection and the connection mode of transformer, the wiring
method for single phase differential protection test by the test instrument of our Company is as follows:

Table 1: IA, IB, IC and protection wiring when in Y phase compensation (the turn angle is
on high-voltage side)

Connection mode A phase B phase C phase


of transformer differential differential differential

IA-Y side A phase IA-Y side B phase IA-Y side C phase


Y/Y type
IB-Y side a phase IB-Y side b phase IB-Y side c phase

IA-Y side A phase IA-Y side B phase IA-Y side C phase


Y/Δ-11 IB-Δ side a phase IB-Δ side b phase IB-Δ side c phase
IC-Δ side c phase IC-Δ side a phase IC-Δ side b phase
IA-Y side A phase IA-Y side B phase IA-Y side C phase
Y/Δ-1 IB-Δ side a phase IB-Δ side b phase IB-Δ side c phase
IC-Δ side b phase IC-Δ side c phase IC-Δ side a phase
Table 2: IA, IB, IC and protection wiring when in Δ phase compensation (the turn
angle is on low-voltage side)

Connection mode A phase B phase C phase


of transformer differential differential differential

IA-Y side A phase IA-Y side B phase IA-Y side C phase


Y/Y type
IB-Y side a phase IB-Y side b phase IB-Y side c phase

IA-Y side A phase IA-Y side B phase IA-Y side C phase


Y/Δ-11 IB-Δ side a phase IB-Δ side b phase IB-Δ side c phase
IC-Δ side c phase IC-Δ side c phase IC-Δ side a phase
IA-Y side A phase IA-Y side B phase IA-Y side C phase
Y/Δ-1 IB-Δ side a phase IB-Δ side b phase IB-Δ side c phase
IC-Δ side c phase IC-Δ side a phase IC-Δ side b phase
Wiring diagrams are as follows:
45 Relay &Protection Microcomputer Test System

I. A phase differential test


1. Y/Y type connection mode:

2. Y/Δ-11 type:

3. Y/Δ-1 type:
46 Relay &Protection Microcomputer Test System

II. B phase differential test


1. Y/Y type connection mode:

2. Y/Δ-11 type:

3. Y/Δ-1 type:
47 Relay &Protection Microcomputer Test System

III. C phase differential test


1. Y/Y type connection mode:

2. Y/Δ-11 type:

3. Y/Δ-1 type:
48 Relay &Protection Microcomputer Test System

X. Distance Protection

(I) Test purpose


The menu is used to check distance protection setting value of microcomputer protective device and
qualitatively analyzing the sensitivity and reliability of the protection distance on protection action of each
section.
In the interface, parameter setting is displayed on the left upper side, voltage and current outputs in the
testing process are displayed on the right lower side, test record is displayed on the right upper side and
contact state simulation and notes are displayed at the bottom.
(II)Test principle
The menu is automatic test mode for partitioning the test into several sub-test items according to
selection of the test item and fault type so as to check each fixed value of distance protection.
(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters

A. Interphase page
49 Relay &Protection Microcomputer Test System

1. Section I impedance Z1: set impedance fixed values for phase distance section I: amplitude and angle.
2. R1+j X1: set impedance fixed values for phase distance section I: resistance and reactance.
3. Section II impedance Z2: set impedance fixed values for phase distance section II: amplitude and
angle.
4. R2+j X2: set impedance fixed values for phase distance section II: resistance and reactance.
5. Section III impedance Z3: set impedance fixed values for phase distance section III: amplitude and
angle.
6. R3+j X3: set impedance fixed values for phase distance section III: resistance and reactance.
7. Section IV impedance Z4: set impedance fixed values for phase distance section IV: amplitude and
angle.
8. R4+j X4: set impedance fixed values for phase distance section IV: resistance and reactance.

B. Grounding page
1. Grounding impedance Z1: set impedance fixed values for grounding distance section I: amplitude and
angle.
2. R1+j X1: set impedance fixed values for grounding distance section I: resistance and reactance.
3. Grounding impedance Z2: set impedance fixed values for grounding distance section II: amplitude and
angle.
4. R2+j X2: set impedance fixed values for grounding distance section II: resistance and reactance.
5. Grounding impedance Z3: set impedance fixed values for grounding distance section III: amplitude
and angle.
6. R3+j X3: set impedance fixed values for grounding distance section III: resistance and reactance.
7. Grounding impedance Z4: set impedance fixed values for grounding distance section IV: amplitude
and angle.
8. R4+j X4: set impedance fixed values for grounding distance section IV: resistance and reactance.

C. Fault page
1. A Phase grounding fault: tick ("√") indicates the test is selected and fault direction of this type of fault
can be set.
2. B Phase grounding fault: tick ("√") indicates the test is selected and fault direction of this type of fault
can be set.
3. C Phase grounding fault: tick ("√") indicates the test is selected and fault direction of this type of fault
can be set.
4. AB interface fault: tick ("√") indicates the test is selected and fault direction of this type of fault can be
set.
5. BC interface fault: tick ("√") indicates the test is selected and fault direction of this type of fault can be
set.
6. CA interface fault: tick ("√") indicates the test is selected and fault direction of this type of fault can be
set.
7. Three-phase short-circuit fault: tick ("√") indicates the test is selected and fault direction of this type of
fault can be set.
50 Relay &Protection Microcomputer Test System

D. Item page
1. Section I impedance Z1: set and select four test items of section I impedance.
2. Section II impedance Z2: set and select four test items of section II impedance.
3. Section III impedance Z3: set and select four test items of section III impedance.
4. Section IV impedance Z4: set and select four test items of section IV impedance.

E. Parameter page
1. Section I fault current: set fault current of section I during test.
2. Section II fault current: set fault current of section II during test.
3. Section III fault current: set fault current of section III during test.
4. Section IV fault current: set fault current of section IV during test.
5. Current before fault: set current output before fault as zero generally.
6. Voltage before fault: set voltage output before fault.
7. Short-circuit closing angle: set voltage angle before fault.

F. Other pages
1. Fault start mode: select the trigger mode of each sub-test from the following two choices: self-start:
the program automatically enters the next sub-test item after this sub-test ends; key start: the program
automatically reminds and waits for user to press the key and control whether to enter the next sub-test test
item at the end of the sub-test.
2. Time before fault: set the waiting time before each fault and output the zero state. Range: 0-60
seconds.
3. Fault time delay: set the time per fault. Range: 0-60 seconds
4. Zero sequence compensation Kr:
5. Zero sequence compensation Kx: in order to calculate zero sequence impedance in the grounding
system, two compensation coefficients, i.e. (zero sequence resistance compensation coefficient Kr) and (zero
sequence reactance compensation Kx), are set. Specific relations are as follows:
R0=R1 (3Kr+1)
X0=X1 (3Kx+1)
6. Tripping time delay: set the tripping action time of simulation breaker. Once the test instrument
receives protected tripping signal, it will enter the voltage and current state after tripping after "tripping time
delay" according to the input connection. If the input of the test instrument is directly connected to “position
skip” contact, tripping time delay can be zero.
51 Relay &Protection Microcomputer Test System

XI. Zero Sequence Protection

()ⅠTest purpose
The menu is used to check setting value of zero sequence protection and qualitatively analyze the
sensitivity and reliability of action in each stage of zero sequence protection.
In the interface, parameter setting is displayed on the left upper side, voltage and current outputs in the
testing process are displayed on the left lower side, test record is displayed on the right upper side, and the
contact state simulation and notes are displayed at the right bottom.
(Ⅱ) Test principle
The menu is automatic test mode for partitioning the test into several sub-test items according to
selection of the test item and fault type so as to check each fixed value of distance protection.
()ⅢCircuit connection
○1 Connect circuit winding of tested protective device to corresponding current and voltage output
terminals of this device.
○2 Connect acting contact point of tested protective device to binary input of the device.
(IV) Description of parameters
A. Fixed value page
1. Zero sequence section I I0: set the fixed value of zero sequence section I.
2. Zero sequence section II I0: set the fixed value of zero sequence section II.
3. Zero sequence section III I0: set the fixed value of zero sequence section III.
52 Relay &Protection Microcomputer Test System

4. Zero sequence section Iv I0: set the fixed value of zero sequence section IV.

B. Item page
1. Zero sequence section I: set and select four test items of zero sequence section I.
2. Zero sequence section II: set and select four test items of zero sequence section II.
3. Zero sequence section III: set and select four test items of zero sequence section III.
4. Zero sequence section IV: set and select four test items of zero sequence section IV.

C. Fault page
1. A phase grounding fault: tick ("√") indicates the test is selected and fault direction of this type of fault
can be set.
2. B phase grounding fault: tick ("√") indicates the test is selected and fault direction of this type of fault
can be set.
3. C phase grounding fault: tick ("√") indicates the test is selected and fault direction of this type of fault
can be set.
4. Zero sequence compensation Kr:
5. Zero sequence compensation Kx: in order to calculate zero sequence impedance in the grounding
system, two compensation coefficients, i.e. (zero sequence resistance compensation coefficient Kr) and (zero
sequence reactance compensation Kx), are set. Specific relations are as follows:
R0=R1 (3Kr+1)
X0=X1 (3Kx+1)

D. Parameter page
1. Fault start mode: select the trigger mode of each sub-test from the following two choices: automatic
start: the program automatically enters the next sub-test item after this sub-test ends; key start: the program
automatically reminds and waits for user to press the key and control whether to enter the next sub-test test
item at the end of the sub-test.
2. Time before fault: set the waiting time before each fault and output the zero state. Range: 0-60
seconds.
3. Fault time delay: set the time per fault. Range: 0-60 seconds
4. Current before fault: set the current output before fault, generally as zero.
5. Voltage before fault: set the voltage output before fault.
6. Short-circuit closing angle: set voltage angle when the fault occurs.
7. Tripping time delay: set the tripping action time of simulation breaker. Once the test instrument
receives protected tripping signal, it will enter the voltage and current state after tripping after "tripping time
delay" according to the input connection. If the input of the test instrument is directly connected to “position
skip” contact, tripping time delay can be zero.
53 Relay &Protection Microcomputer Test System

XII. Setting Group Test

(I) Test purpose


The menu is mainly used to test setting group characteristics of distance protection, zero sequence
protection, etc., and can simulate various simple single-phase grounding, two interphases, two-phase
grounding and three-phase short circuit faults in electric system, including momentary, permanent and
conversion faults and simulate total process of tripping, reclosing and the like of transmission switch.
In the interface, parameter setting is displayed on the left upper side, amplitudes, phase positions and
vector graphics of voltage and current before and after fault are displayed on the right upper side, and
contact state simulation and notes are displayed at the bottom.
(I) Test principle
Firstly, input zero as voltage and current values, and a prompt of "Press enter key to enter state before
fault" is indicated for user; further another prompt of "Press enter key to start fault" is presented. The
voltage and current values before fault are normal values (voltage: 57.8V, current: 0A). After the start of
fault, the test device inputs fault voltage and current values. Once tripping occurs at this moment, the
software will record the acting situation of tested protection, or record zero value. Meanwhile, the software
gives a parameter vector value and vector graphic. The test result is displayed and can be saved.
(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device.
54 Relay &Protection Microcomputer Test System

○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
A. First parameter page
1. Fault type: select fault type to be simulated in the tested from the following ten fault types: AN
single-phase grounding, BN single-phase grounding, CN single-phase grounding, AB two-phase grounding,
BC two-phase grounding, CA two-phase grounding, ABD three-phase short circuit, AB interphase short
circuit, BC interphase short circuit and CA interphase short circuit.
2. Set impedance value R+jX: set rectangular coordinates form of setting impedance Zd: resistance
and reactance.
3. Set impedance Z: set polar coordinates form of setting impedance Zd: amplitude and angle.
4. Short circuit point: set the position of fault short circuit point.
5. Fault current value: set fault current value when fault occurs within the range of 0-30A.
6. Fault direction: select fault direction from the following two choices: positive fault and negative
fault.
7. Fault property: select fault property from the following two choices: permanent fault and
momentary fault. Permanent fault: fault amount of output if fault still exists after fault superposition;
momentary fault: normal amount is output if no fault exists fault superposition.
8. Initial phase angle of voltage: set initial angle of voltage. Range: -360 to 360 degrees.
9. System reactance value: set system reactance value. It is suitable for various systems during
grounding fault. It is used to set system impedance of power supply along opposite direction in the system
in order to correct sudden change of the voltage and adapt to action characteristic of protection without
affecting the setting value for changing any fault amount.
10. Zero sequence compensation: values of zero sequence resistance compensation coefficients Kr and
Kx within the range of 0-4. In order to calculate zero sequence impedance in the grounding system, two
compensation coefficients, i.e. (zero sequence resistance compensation coefficient Kr) and (zero sequence
reactance compensation Kx), needing setting. Specific relations are as follows:
(Completed by software) R0=R1 (3Kr+1);
X0=X1 (3Kx+1);
11. PT mounting position: set mounting position of PT in fault to be simulated from the following two
choices: bus side and circuit side. PT is mounted after fault phase on the bus side has been eliminated, the
current of the phase is zero and the voltage is normal value. PT is mounted on the circuit side after the fault
phase has been eliminated, and both the current and voltage of the phase are zero.

B. Second parameter page


1. Conversion fault: select whether to simulate fault conversion from the following two choices:
non-conversion fault and conversion fault.
2. Type of conversion fault: select type of conversion fault from the following four choices: AB
two-phase grounding, BC two-phase grounding, CA two-phase grounding and ABC three-phase short
circuit. User shall select corresponding type of conversion fault according to different faults.
3. Conversion moment: set input conversion time. User can select occurrence before outlet, before
55 Relay &Protection Microcomputer Test System

reclosing, after reclosing, etc. of the protection according to specific situation.


4. Fault amount switching: select switching mode of fault amount during the test from the following
two choices: contact point mode (opening and closing of contact point) and automatic mode (set time
value).
5. Fault time: set the time in fault state, i.e., time lasting from the start of the fault to the first tripping
(or the time lasting from the fault reclosing to the second tripping). The parameter must be set in automatic
mode within the range of 0.200-5 seconds.
6. Interval time: set the time under break state, i.e., time lasting from the first tripping to the fault
reclosing (or time lasting from the second tripping to the end of the test). The parameter must be set in
automatic mode within the range of 0.300-3 seconds.
7. Voltage before fault: set voltage value before fault, i.e., normal amount, which is generally 57.8V.
Range: 0-130V.
8. Current before fault: set current value before fault, i.e., normal amount, which is generally 0A.
Range: 0-30A.
9. Reclosing outlet time: set outlet time of reclosing (switch closing time delay). Range: 0-1.5 seconds.
10. Tripping arc extinguishing time: set arc extinguishing time to carry out transmission experiment
correctly. Fixed time of open circuit is simulated by adjusting arc extinguishing time parameter, and the
default is set as 0.140 seconds. If the contact point signal input to the test device is directly given by the
output contact point of the tested protective device, this value shall be zero. Range: 0-1.5 seconds.
11. Post acceleration time: set post acceleration arc extinguishing time to carry out transmission
experiment correctly. The principle is the same as above. The default is 0.500 seconds. Range: 0-9.9
seconds.
56 Relay &Protection Microcomputer Test System

XIII. State Sequence

(I) Test purpose


The menu allows user to freely customize test mode and test content and up to 20 test states are
available. All states can be freely set by user and switchover between states is controlled by time control,
contact switch switchover and key press by user.
In the interface, parameter setting is displayed on the left upper side, vector graphic is displayed on the
right upper side and contact state simulation and notes are displayed at the bottom.
(II) Test principle
User optionally increases or decreases within the range of 20 states. In each state, amplitudes, phase
positions and frequencies of six phases of voltage and six phases of current can be set optionally.
Meanwhile, user can select three different types of state switching mode and the state of output contact
point in each state. After the start of test, analog quantity under no state is output according to user setting
till the end of the test. Under the contact point switchover, there is time measurement result.
(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.

(IV) Description of parameters


57 Relay &Protection Microcomputer Test System

In each state, all settable parameters and ranges are the same.
1. UA voltage: set the amplitude, DC or not, phase and frequency value of UA voltage.
2. UB voltage: set the amplitude, DC or not, phase and frequency value of UB voltage.
3. UC voltage: set the amplitude, DC or not, phase and frequency value of UC voltage.
4. UX voltage: set the amplitude, DC or not, phase and frequency value of UX voltage.
5. UY voltage: set the amplitude, DC or not, phase and frequency value of UY voltage.
6. UZ voltage: set the amplitude, DC or not, phase and frequency value of UZ voltage.
7. IA current: set the amplitude, DC or not, phase and frequency value of IA voltage.
8. IB current: set the amplitude, DC or not, phase and frequency value of IB voltage.
9. IC current: set the amplitude, DC or not, phase and frequency value of IC voltage.
10. IX current: set the amplitude, DC or not, phase and frequency value of IX voltage.
11. IY current: set the amplitude, DC or not, phase and frequency value of IY voltage.
12. IZ current: set the amplitude, DC or not, phase and frequency value of IZ voltage.
13. End mode: select the end mode of this state from the following three choices: key control, time
control and contact point control.
14. End time: set the end time of this state. It shall be set when the end mode is time control. Range:
0-100 seconds.
15. Output 1: set the state of output contact point 1 in the state. If this state is different from the
previous state, it can be set to act after time delay after entering this state.
16. Output 2: set the state of output contact point 2 in the state in the same way as above.
17. Output 3: set the state of output contact point 3 in the state in the same way as above.
18. Output 4: set the state of output contact point 4 in the state in the same way as above.
19. Fault calculation: auxiliary calculation function. Output setting of this state is modified by setting
the state type and parameter, calculating output value in an auxiliary way and verifying the value.
20. Add state: insert a new state after the current state.
21. Deletion state: delete the current state.
58 Relay &Protection Microcomputer Test System

XIV. Synchronization Test

(I) Test purpose


The test is used to test action voltage, action frequency and action angle of synchronous relay or
synchronous device and can carry out automatic adjusting test.
In the interface, parameter setting is displayed on left side, synchronous window is displayed on right
upper side, and test result, contact state simulation and notes are displayed at the bottom.
(II) Test principle
Manual test: firstly, input the initial values of voltage, current and frequency. User then can press keys
↑ and ↓ to increase and decrease the variable value.
Automatic test: firstly, input initial value of each parameter, and then gradually increase the step length
and change the variable value at a speed determined according to time per step; if protection acts, the
software will record its action value. If the variable has been increased to maximum or decreased to
minimum while protection does not act, the software will automatically exit test.
(III) Circuit connection
○1 Connect coil winding of tested synchronous protective device to corresponding current and voltage
output terminals of the device.
○2 Connect acting contact point of tested synchronous protective device and acting contact of tested
relay to binary input of the device.
(IV) Description of parameters
A. Test item page
59 Relay &Protection Microcomputer Test System

1. Test item: select item of the test from the following four choices: parallel side voltage amplitude,
parallel side voltage frequency, parallel side voltage phase and automatic adjusting test.
2. Current variable: display variable under the current test item. It is not settable.
3. Variation mode: select mode of the test from the following two choices: automatic test and manual
test.
4. Initial variable value: set the initial value of current variable.
5. Variable step length: set the step length per change of variable.
6. Time per step: set the waiting time per change of step length. Range: 0-20 seconds.
7. Variation time: set anti-contact chatter time within the range of 0-3 seconds. In order to prevent
contact chatter from affecting the test result, the default value is 200 milliseconds.

B. Other setting pages


1. Voltage regulating step length: change amount of parallel side voltage upon each reception of speed
regulating signal, which is effective under automatic adjusting test.
2. Speed adjusting step length: change amount of parallel side frequency upon each reception of speed
regulating signal, which is effective under automatic adjusting test.
3. Input contact A: displayed input contact A shall be connected with acceleration contact↑f.
4. Input contact a: displayed input contact a shall be connected with deceleration contact↓f.
5. Input contact B: displayed input contact B shall be connected with pressurizing contact↑V.
6. Input contact b: displayed input contact b shall be connected with pressurizing contact↓V.
7. Output contact: select state of output contact during test from the following two choices: closing
and switching-off.

C. Synchronous window page


+ΔV: positive voltage difference of synchronous window
-ΔV: negative voltage difference of synchronous window
+Δf: positive frequency difference of synchronous window
-Δf: negative frequency difference of synchronous window

D. System side page


[Note]: connection mode of system side voltage is Ua, i.e., A voltage output of test instrument.
1. Voltage: set system side voltage amplitude within the range of 0-130.0V.
2. Phase: system side voltage angle is reference phase, so it is generally zero.
3. Frequency: set system side voltage amplitude within the range of 25-75Hz.

E. Parallel side page


[Note]: connection mode of system side voltage is Uc, i.e., C voltage output of test instrument.
Voltage: set system side voltage amplitude within the range of 0-130.0V.
2. Phase: set parallel side voltage angle within the range of -360 to 360 degrees.
3. Frequency: set parallel side voltage frequency within the range of 25-75Hz.
60 Relay &Protection Microcomputer Test System

XV. Special Test

(I) Test purpose


The test is for special experiment because test of certain special equipment needs synchronous change
of various variables on the site and needs recording time. Meanwhile, the test can enable user to design the
test method independently.
In the interface, parameter setting is displayed on the left upper side, tor graphics of voltage and
current and frequency table are displayed on the right upper side. User can shift display by pressing F2.
Contact state simulation and notes are displayed at the bottom.
(I) Test principle
Manual test: input initial values of voltage, current and frequency firstly. User then can press keys ↑
and ↓ to increase and decrease variable value and press [Enter] key to vary all parameters on line. If user
needs to test the time, he shall press key "F3" firstly, and then press keys ↑ and ↓ to increase and decrease
variable value and start counting. The time limit range is 0-3,600 seconds. For example, if the time limit is
20 seconds, i.e., the tester does not act within 20 seconds, then timing state will be released automatically.
Automatic test: input initial value of each parameter firstly, and gradually increase step length to
change the variable value at a speed determined according to the setting of the time per step; if the
protection acts, gradually decrease the step length to change the variable value until the protection returns,
and the software will record the action value and the return value. If protection does not act after the
variable has increased to the maximum state or decreased to the minimum state, the software will
61 Relay &Protection Microcomputer Test System

automatically exit test.


(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
1. UA voltage: set amplitude (range: 0-130V), changeable or not, change step length (range:-130 to
130A), DC output or not, phase position (range: -360 to 360 degrees), variable phase position or not and
phase position change step length (range: -360 to 360 degrees) of A phase voltage.
2. UB voltage: set relevant parameters of B phase voltage with the same content as above.
3. UC voltage: set relevant parameters of C phase voltage with the same content as above.
4. UX voltage: set relevant parameters of X phase voltage with the same content as above.
5. UY voltage: set relevant parameters of Y phase voltage with the same content as above.
6. UZ voltage: set relevant parameters of Z phase voltage with the same content as above.
7. IA current: set amplitude (range: 0-30A), changeable or not, change step length (range:-30 to 30A),
DC output or not, phase position (range: -360 to 360 degrees), variable phase position or not and phase
position change step length (range: -360 to 360 degrees) of A phase voltage.
8. IB current: set relevant parameters of B phase current with the same content as above.
9. IC current: set relevant parameters of C phase current with the same content as above.
10. IX current: set relevant parameters of X phase current with the same content as above.
11. IY current: set relevant parameters of Y phase current with the same content as above.
12. IZ current: set relevant parameters of Z phase current with the same content as above.
13. Frequency parameter: set frequencies (range: 0-1, 000HZ) of all analog quantities, changeable or
not and change step length (range: -1, 000 to 1, 000HZ).
14. Test mode: select the test mode from the following two choices: manual test and automatic test.
15. Test item: select the test item from the following two choices: action time and holding time.
16. Timing time delay: set the maximum waiting time of timing. It is the maximum waiting time when
F3 is pressed to measure the time in manual mode; it is the waiting time per variable change in automatic
mode. Generally, the time shall be greater than the action time or holding time of the protective device.
62 Relay &Protection Microcomputer Test System

XVI. Transplay (Fault Reappearance)

(I) Test purpose


The test is used for inputting fault recording data (note: data recording format shall be accordant
with IEEE standard COMTRADE format) of certain dynamic simulation test or measured on site into the
device in the form of file so as to make dynamic simulation or on-site working condition reappear, which
is helpful for analyzing and finding fault cause.
Four interfaces, including file, channel, waveform and test parameter are provided.
(II) Test principle
Firstly, enter pre-fault state according to selected fault recording file (COMTRADE format
including configuration file and data file) and output setting of each phase, and then trigger fault
according to fault triggering mode and enter fault state until all data reappearance is finished, and end the
test; once tripping occurs in the testing process, the software will record the action situation of tested
protection, otherwise it will record the zero value. Meanwhile, test result can be saved.
(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
63 Relay &Protection Microcomputer Test System

1. File: select wave recording file needing reappearing. The software will list all configuration files in
the current catalog. Display some parameter information included in the file after selection.
2. Channel: optionally set four paths of voltage and three paths of current in a wave recording file
replaying channel (including 64 paths of analog quantities and 128 paths of binarys at most) selected by
user as the output of the device. The software automatically sets the variable ratio according to the output
maximum value, and then displays the maximum value and minimum value of each selected channel.
3. Waveform: display output waveform preview of the device according to selected waveform file and
channel setting.
4. Test parameter: this parameter is set for each parameter in the testing process, including setting of
triggering mode, repeated section and contact point output.
64 Relay &Protection Microcomputer Test System

XVII. Oscillation Test

(I) Test purpose


The menu simulates voltage and current output process when a circuit supplied with power by
double-end power supply oscillates.
In the interface, parameter setting and voltage and current ranges during oscillation are displayed on
the left upper side, oscillation voltage and current peak values and equivalent network diagram are
displayed on the left lower side, oscillation oscillogram is displayed on the right upper side, and contact
state simulation and notes are displayed at the bottom.
(II) Test principle
After the start of the test, the device calculates oscillation load according to input parameter value,
draws voltage and current simulation curves and calculates their ranges during the oscillation period and
simulates power oscillation output. The oscillation lasts for 10 seconds. When the test is finished, the test
device automatically enters standard state without outputting voltage and current.
(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
65 Relay &Protection Microcomputer Test System

1. System impedance Zm: set generator side impedance Zm in double-end power supply system.
2. Circuit impedance Zl: set equivalent value impedance Zl of protected circuit.
3. System impedance Zm: set generator side impedance Zm in double-end power supply system.
4. Oscillation period: set oscillation period of simulation fault. Range: 0-1 second.
5. Reference potential: set power supply potential, i.e., maximum peak value of voltage during
oscillation. Range: 0-183V.
6. |Em|/|En|: ratio of amplitude of generator side voltage Em to amplitude of system side voltage En.
66 Relay &Protection Microcomputer Test System

XVIII. Metering Instrument

(I) Test purpose


Check metering instruments, such as AC voltmeter, ammeter, active power meter, passage power
meter and transducer. The test mode is of manual control. Three-phase voltage and three-phase current can
change at the same time according to different step lengths.
In the interface, parameter setting is displayed on the left upper side, vector graphic, active power,
passage power and power factor of each phase on primary side or secondary side and linear sequence
component are displayed on the right upper side. User can press key F2 to switch display.
(II) Test principle
The menu is for manual test mode. After the start of the test, the program outputs according to voltage,
current and frequency values set by user. User can press keys ↑ and ↓ to increase and decrease the variable
value or press [Enter] key to change all parameters on line and press "ESC" key to exit test.
(III) Circuit connection
○1 Connect analog input end to corresponding voltage and current output terminals of the device
according to test table type.
(IV) Description of parameters
1. A phase voltage: set amplitude, variable or not, and change step length of A phase voltage.
2. Ua phase: set amplitude, variable or not, and change step length of Ua phase.
3. B phase voltage: set amplitude, variable or not, and change step length of B phase voltage.
67 Relay &Protection Microcomputer Test System

4. Ub phase: set amplitude, variable or not, and change step length of Ub phase.
5. C phase voltage: set amplitude, variable or not, and change step length of C phase voltage.
6. Uc phase: set amplitude, variable or not, and change step length of Uc phase.
7. A phase current: set amplitude, variable or not, and change step length of A phase current.
8. Ia phase: set amplitude, variable or not, and change step length of Ia phase.
9. B phase current: set amplitude, variable or not, and change step length of B phase current.
10. Ib phase: set amplitude, variable or not, and change step length of Ib phase.
11. C phase current: set amplitude, variable or not, and change step length of C phase current.
12. Ic phase: set amplitude, variable or not, and change step length of Ic phase.
13. Frequency parameter: set frequencies of all outputs.
14. CT change: set change of CT to calculate power for displaying primary side.
15. PT change: set change of PT to calculate power for displaying primary side.
68 Relay &Protection Microcomputer Test System

XIX. Hardware Checkout

(I) Test purpose


The menu can compare piratical output and theological output of analog quantity of test device. When
user is determining the theological output, the software automatically calculates the compensation
coefficient and the differential value, which can be optionally saved.
In the interface, prompt menu is displayed on the upper side, theological value, practical value,
compensation coefficient or compensation differential value for the analog quantity of each phase are
displayed at the middle, and notes are displayed at the bottom.
(II) Test principle
During the test, the software outputs voltage of 60V and current of 5A with frequency of 50Hz for
each phase. User shall measure the practical output value of the analog quantity of each phase through an
external meter and make records. "ESC" key can be pressed at any time to exit test. Then, the recorded
practical output value is filled in the measured value column, and the program will automatically calculates
the step length coefficient. Please save setting, so the coefficient becomes effective.
(III) Circuit connection
○1 Connect analog input end to corresponding voltage and current output terminals of the device
according to test table type.
(IV) Description of parameters
Correct when voltage and current of each phase are 60V and 5A respectively.
69 Relay &Protection Microcomputer Test System

Measured value: records are made in each inspection test. For this item, user fills corresponding
quantities, and the software automatically calculates the compensation coefficient and the differential value.
F2 for invoking default value: invoke default values of compensation coefficient and the differential
value. The default compensation coefficient is 1.0 and the default compensation differential value is 0.0.
70 Relay &Protection Microcomputer Test System

XX. Low Voltage Protection

(I) Test purpose


The menu is used for checking setting values of three-section overcurrent, three-section zero sequence
current, etc. of the protective device below 110kV (35kV or10kV).
In the interface, parameter setting is displayed on the left upper side, vector graphics of voltage and
current are displayed on the right upper side. User can press key F2 to switch display of output in each fault
state. The contact state simulation and notes are displayed at the bottom.
(I) Test principle
The menu is automatic test mode for partitioning the test into several sub-test items according to
parameter setting and selection of test item to check each fixed value of microcomputer protective device.
(III) Circuit connection
○1 Connect coil winding of tested protective device to corresponding current and voltage output
terminals of the device.
○2 Connect acting contact point of tested protective device and acting contact of tested relay to binary
input of the device.
(IV) Description of parameters
A. Parameter setting page
1. Overcurrent section I: set relevant parameters of overcurrent section I, including selection test, setting
value, setting time, reference voltage and reference angle.
71 Relay &Protection Microcomputer Test System

2. Overcurrent section II: set relevant parameters of overcurrent section II in the same way as above.
3. Overcurrent section III: set relevant parameters of overcurrent section III in the same way as above.
4. Zero current section I: set relevant parameters of overcurrent section I in the same way as above.
5. Zero current section II: set relevant parameters of overcurrent section II in the same way as above.
6. Zero current section III: set relevant parameters of overcurrent section III in the same way as above.
7. Overcurrent acceleration: set relevant parameters of overcurrent acceleration, including selection test,
setting value, setting time and reference voltage.
8. Zero current acceleration: set relevant parameters of zero current acceleration, including selection test,
setting value and setting time.
9. Overload: set relevant parameters of overload, including selection test, setting value and setting time.
10. Setting ratio 1: set to test by the setting ratio and display corresponding result in action time 1.
11. Setting ratio 2: the same as above, display corresponding result in action time 2.
12. Fault start mode: select start mode of each sub-test from the following three choices: delay start,
enter key start and contact turnover.
13. Pre-fault time delay: set waiting time before the start of each sub-test. Range: 0-100 seconds.
Generally, it shall be set within the range of 10-15 seconds.
14. Test break time: set break time after each fault.

B. P hase testing page


1. Overcurrent section I: set test phase of overcurrent section I from the following choices: A phase, B
phase and C phase.
2. Overcurrent section II: set test phase of overcurrent section II from the following choices: A phase, B
phase and C phase.
3. Overcurrent section III: set test phase of overcurrent section III from the following choices: A phase, B
phase and C phase.
4. Overcurrent acceleration: set test phase of overcurrent acceleration from the following choices: A
phase, B phase and C phase.
5. Overload: set test phase of overload from the following choices: A phase, B phase and C phase.
6. Zero current section I: set test phase of zero current section I from the following choice: A phase.
7. Zero current section II: set test phase of zero current section II from the following choice: A phase.
8. Zero current section III: set test phase of zero current section III from the following choice: A phase.
9. Zero current acceleration: set test phase of zero current acceleration from the following choice: A
phase.
72 Relay &Protection Microcomputer Test System

Chapter Five Analyses and Solutions of Common Problems

No. Fault phenomenon Cause analysis Solutions


Switch off the main supply and
Sound alarm is sent out when Power supply source is too high
1 switch it on again when
power key is switched on. (>250VAC)
external voltage is lowered.
When power key is switched on
there is no remarkable change
2 of power supply power, and no Power supply fuse is burnt out. Replace power supply fuse.
fault amount is output during
all functional menu tests.
Action of section I is displayed Protection false operation is
but section II acts practically caused by too small impedance Change fault current of distance
3
when periodic inspection test is value of distance protection I section to 8A or above.
performed on distance section I. section I
Action of section I is displayed
but section II acts practically Set fixed value in zero
False operation is caused by too
4 when whole group test is sequence current region
large overrun range.
performed on zero sequence between 0.94-0.97 times.
section I.
Reclosing is unavailable after
Outlet time for reclosing is too
5 opening of the switch in whole Set the value be about 100ms.
short.
group transmission test.
Incorrect protective action is Connect binary input terminals
Contact action is incorrect
caused by time delay among A,B and C of test device to
6 during 901 series protection in
separate actions of 901 series of corresponding contacts of 901
periodic inspection test.
outlets A,B and C. protection.
Reservedly connect high
Protection does not act when potential and low potential of
7 test contact of whole group Wire connection is incorrect. test instrument, that is,
protection has electric potential. reservedly connect jumping A,
B, C and R and public end N.
The device outputs fault Set return time in parameter be
Voltage broken wire is closed in
8 amount before the protection greater than return time of
impedance characteristic test.
returns. protection.
The device outputs fault
Voltage broken wire is closed in
9 amount before the protection
periodic inspection test.
returns.
73 Relay &Protection Microcomputer Test System

Set protection return time in


parameter be greater than return
time of tested protection and set
end frequency be fixed action
The test device acts but the
End frequency is set wrongly. value of tested device.
10 action time is zero in slip
Generally, the fixed value is
locking test.
obtained by subtracting the
low-cycle differential value
from the initial frequency:
fe=fb-df
The test device acts but there is Determine frequency
The device outputs fault
great difference between the conversion after the protection
11 amount before the protection
action time and set action time returns according to prompt
returns.
delay in slip locking test. after the test.
74 Relay &Protection Microcomputer Test System

Attached accessories:

Main device
No. Name Specification Quantity Unit Remark
Microcomputer-cont
1 rolled relay Super series 1 Set
&protection tester

Dedicated parts, attached technical data and spare parts


No. Name Specification Quantity Unit Remark
Six-phase voltage and six-phase
1 Dedicated test lead BZDCC -3 1 Package
current (3m)
2 Operation manual Super series 1 Copy
Numbered as per unique ex-factory
3 Product certificate Super series 1 Copy
No. of product
Numbered as per unique ex-factory
4 Delivery report Super series 1 Copy
No. of product
5 Packing case Super series 1 Set Intensified high-grade aluminum alloy
6 Power cord 300/500V 1 Piece
7 Fuse tube 10A 2 Piece
Communication
8 DB9 1 Piece Dedicated for on-line operation
data wire
Optical disk Software installation disk dedicated for
9 Super series 1 Piece
attached at delivery on-line operation or operation manual
U disk attached at SSK, 2G or Upgrade of host machine software and
10 1 Piece
delivery above export of test report

Optional part
No. Name Specification Quantity Unit Remark
Dedicated Exported or user
1 1 Set Super series on-line software operation
notebook computer customized