873_Cons_Guide:838_Cons_Guide.qxd 7/8/2009 3:18 PM Page CG-18
Where:
Table CG-12. Pipe Weights Per Foot in Pounds
C = Condensate in lbs/hr-foot
Pipe Size (in) Schedule 40 Schedule 80 Schedule 160 XX Strong
A = External area of pipe in square feet
1 1.69 2.17 2.85 3.66
(Table CG-10, Col. 2)
1-1/4 2.27 3.00 3.76 5.21
U = Btu/sq ft/degree temperature 1-1/2 2.72 3.63 4.86 6.41
difference/hr from Chart CG-7 (page CG-19) 2 3.65 5.02 7.45 9.03
T1 = Steam temperature in °F 2-1/2 5.79 7.66 10.01 13.69
T2 = Air temperature in °F 3 7.57 10.25 14.32 18.58
E = 1 minus efficiency of insulation 3-1/2 9.11 12.51 — 22.85
4 10.79 14.98 22.60 27.54
(Example: 75% efficient insulation: 5 14.62 20.78 32.96 38.55
1 - .75 = .25 or E = .25) 6 18.97 28.57 45.30 53.16
H = Latent heat of steam 8 28.55 43.39 74.70 72.42
(See Steam Table on page CG-3) 10 40.48 54.74 116.00 —
12 53.60 88.60 161.00 —
14 63.00 107.00 190.00 —
16 83.00 137.00 245.00 —
18 105.00 171.00 309.00 —
20 123.00 209.00 379.00 —
24 171.00 297.00 542.00 —
23
Armstrong Steam and Condensate Group, 816 Maple St., Three Rivers, MI 49093 – USA Phone: (269) 273-1415 Fax: (269) 278-6555
Next armstronginternational.com
CG-18
873_Cons_Guide:838_Cons_Guide.qxd 7/8/2009 3:18 PM Page CG-19
The inverted bucket trap is recommended because it can On a supervised warm-up, make drip leg length at least
handle dirt and slugs of condensate and resists hydraulic 1-1/2 times the diameter of the main, but never less than
shock. In addition, should an inverted bucket fail, it usually 10". Make drip legs on automatic warm-ups a minimum of
does so in the open position. 28" in length. For both methods, it is a good practice to use
a drip leg the same diameter as the main up to 4" pipe size
Installation. Both methods of warm-up use drip legs and and at least 1/2 of the diameter of the main above that, but
traps at all low spots or natural drainage points such as: never less than 4". See Table CG-13.
Ahead of risers
End of mains
Ahead of expansion joints or bends
Ahead of valves or regulators Table CG-13. Recommended Steam Main and Branch Line Drip Leg Sizing
M D H
Chart CG-7. Btu Heat Loss Curves Drip Leg Length Min. (in)
TEMPERATURE DIFFERENCE Steam Main Drip Leg Supervised Automatic
150° 160° 180° 200° 240° 300° 400° 500° 700° 900° 1050°
Size (in) Diameter (in) Warm-Up Warm-Up
11 11
10 10 1/2 1/2 10 28
9 9 3/4 3/4 10 28
8 8
1 1 10 28
BTU PER SQ FT PER HOUR PER °F TEMPERATURE DIFFERENCE
7 7
2 2 10 28
6 6
3 3 10 28
5 5 4 4 10 28
4.5 4.5 6 4 10 28
4.0 4.0
8 4 12 28
10 6 15 28
3.5 3.5 12 6 18 28
3.3 3.3
14 8 21 28
3.0 3.0 16 8 24 28
2.8 1"
2.8 18 10 27 28
2" 20 10 30 30
2.6 2.6
3" 24 12 36 36
2.5 5" E S 2.5
AC
2.4 6" RF 2.4
SU
10"
AT
FL
2.3 2.3 Chart CG-8. Recommendation Chart
(See Page CG-2 for “Feature Code” References.)
2.2 2.2
Equipment Being 1st Choice and
2.15 2.15 Alternate Choice
Trapped Feature Code
2.10 IBLV
PSIG Steam Separator *DC
5.3
10.3
15.3
25.3
50.3
75.3
100.3
150.3
250.3
450.3
600.3
900.3
1500.3
2400.3
B, M, L, E, F, N, Q
PRESSURE IN LBS PER SQUARE INCH *DC is 1st choice where steam quality is 90% or less.
Steam Mains
M
M
D
H
H
Drip leg same
as the header
diameter up to
4''. Above 4'',
1/2 header size,
but never less
than 4''.
Install a full pipe-size strainer ahead of each control valve EXAMPLE: What size steam trap will be required on a flow
as well as ahead of the PRV, if used. Provide blowdown rate of 10,000 lbs/hr? Using the formula:
valves, preferably with IB traps. A few days after starting
the system, examine the strainer screens to see if cleaning Required trap capacity =
is necessary. 3 x 10,000 x 0.10 = 3,000 lbs/hr.
Separators The inverted bucket trap with large vent is recommended for
Steam separators are designed to remove any condensate separators. When dirt and hydraulic shock are not signifi-
that forms within steam distribution systems. They are most cant problems, an F&T type trap is an acceptable alterna-
often used ahead of equipment where especially dry steam tive.
is essential. They are also common on secondary steam
lines, which by their very nature have a large percentage of An automatic differential condensate controller may be pre-
entrained condensate. ferred in many cases. It combines the best features of both
of the above and is recommended for large condensate
Branch Lines loads that exceed the separating capability of the separator.
10' or Less Installation
Pitch 1/2'' per 1 ft Connect traps to the separator drain line 10" to 12" below
the separator with the drain pipe running the full size of the
drain connection down to the trap take-off (Fig. CG-35). The
drain pipe and dirt pocket should be the same size as the
Runout Oversized
drain connection.
One Pipe Size
or More Steam Separator
6'' IBLV or
DC
Figure CG-33. Piping for runout greater Figure CG-34. Regardless of the length Figure CG-35. Drain downstream side
than 10'. Drip leg and trap required of the runout, a drip leg and trap are of separator. Full-size drip leg and dirt
ahead of control valve. Strainer ahead required ahead of the control valve pocket are required to ensure positive
of control valve can serve as drip located below steam supply. If coil is and fast flow of condensate to the
leg if blowdown connection runs to above control valve, a trap should also trap.
an inverted bucket trap. This will also be installed at downstream side of
minimize the strainer cleaning problem. control valve.
Trap should be equipped with an internal
check valve or a swing check installed
ahead of the trap.