Protect NG125N circuit breakers

Circuit protection B, C and D curves


IEC 60947-2: 25 kA

Function
This circuit breaker is specially designed for functions requiring a high breaking
capacity (up to 25 kA):
b modular enclosure incomer,
b main incomer in sub-distribution switchboards,
b outgoer, protection of loads directly supplied by a power switchboard.

Description
Common technical data
b Rating: 10…125 A
b Reference temperature: 40 °C
b Uimp: 8 kV
b Ui: 690 V
b Maximum voltage rating: 500 V AC
b Breaking capacity: as in IEC 60947.2
Type Voltage Breaking capacity
(V AC) (A)
1P 220…240 25000
1P 380…415 6000 (1)
2, 3, 4P 380…415 25000
(1) 1-pole breaking capacity in the IT isolated neutral system (double fault).
b Isolation with positive break indication
b 3-position toggle: open-tripped-closed
b Built-in padlocking facility on 3P and 4P
b Fault display on front face by:
v fault indicator
v position of toggle: tripped
b Test button to check proper operation of the tripping mechanism
b Fast closing
b Electrical durability: 10,000 cycles at In
b Tropicalisation as in IEC 68.1: treatment 2 (relative humidity: 95 % at 55 °C)
b Weight (g):
Type 1P 2P 3P 4P
240 480 720 960
b Compatible with the Pragma F24 and Prisma G/GX enclosures and the Prisma P
cabinets
b Degree of protection: IP20B (IP40D for the part outside the enclosure)
b Connection:
v 63 A ratings: tunnel terminals for 1.5 to 50 mm2 copper cables
v 80 to 125 A ratings: tunnel terminals for 16 to 70 mm2 copper cables
v aluminium cables, copper cables with lug or busbar
(see connection accessories)
v on 3P and 4P: upstream voltage taps on each pole, by 6.35 mm Fast-on lugs, for
auxiliary circuit supply.

B curve
b The magnetic trip units operate at 4 In ±20 %.

C curve
b The magnetic trip units operate at 8 In ±20 %.

D curve
b The magnetic trip units operate at 12 In ±20 %.

 version: 3.1 90233E.indd


Protect NG125N circuit breakers
Circuit protection B, C and D curves
IEC 60947-2: 25 kA

Catalogue numbers
NG125N B curve
Type Rating Catalogue Width
(A) numbers in mod.
of 9 mm
3P
80 18663 9
1 3 5 100 18664 9
125 18665 9

2 4 6

4P
80 18666 12
1 3 5 7 100 18667 12
125 18668 12

2 4 6 8

NG125N C curve
1P
10 18610 3
1 16 18611 3
20 18612 3
25 18613 3
32 18614 3
40 18615 3
50 18616 3
63 18617 3
18617 2 80 18618 3

2P
10 18621 6
1 3 16 18622 6
20 18623 6
25 18624 6
32 18625 6
40 18626 6
50 18627 6
63 18628 6
18628 2 4 80 18629 6

3P
10 18632 9
1 3 5 16 18633 9
20 18634 9
25 18635 9
32 18636 9
40 18637 9
50 18638 9
63 18639 9
2 4 6 80 18640 9
18644 100 18642 9
125 18644 9

3P + N
80 18646 12
N 1 3 5 100 18647 12
125 18648 12

N 2 4 6
18648

90233E.indd version: 3.1 


Protect NG125N circuit breakers
Circuit protection B, C and D curves
IEC 60947-2: 25 kA

NG125N C curve (continued)


Type Rating Catalogue Width
(A) number in mod.
of 9 mm
4P
10 18649 12
1 3 5 7 16 18650 12
20 18651 12
25 18652 12
32 18653 12
40 18654 12
50 18655 12
63 18656 12
18662 2 4 6 8 80 18658 12
100 18660 12
125 18662 12

NG125N D curve
3P
80 18669 9
1 3 5 100 18670 9
125 18671 9

2 4 6

4P
80 18672 12
1 3 5 7 100 18673 12
125 18674 12

2 4 6 8

Additional information
Auxiliaries: page 90250/2
Accessories: page 90251/2
Vigi module: page 90243/2
Discrimination table: page 92511/2
Dimensions: page 90148/2
Derating: page 92515/2
Tripping curves: page 90180/2

 version: 3.1 90233E.indd